Advantech ADAM-5510/P31 Manual page 162

Table of Contents

Advertisement

Testing conditions:
(1) ADAM-5510/P31: 3 pieces
(2) ADAM-5018: 4 pieces in each ADAM-5510/P31
(3) Advantech Paradym-31 v4.1
Testing results:
Response time for each measured signal:
731.75 ms +/- 32.70 ms (95% confidence interval)
maximum response time: 1232 ms
Testing conditions:
(1) ADAM-5510/P31: 5 pieces
(2) ADAM-5050: 4 pieces in each ADAM-5510/P31
(3) Advantech Paradym-31 v4.1
Testing results:
Response time for each measured signal:
191.61 ms +/- 12.25 ms (95% confidence interval)
maximum response time: 361 ms