Fault - Siemens Albatros2 RVA78.690 User Manual

Solar compact controller
Hide thumbs Also See for Albatros2 RVA78.690:
Table of Contents

Advertisement

Acknowledgements
Error history
Reset history
Siemens
Building Technologies
6.11

Fault

If a fault is pending
, the associated error message on the information level can
be queried via the info button or the error history on OL 6800-6808. The display
describes the cause of the error.
Pending errors are assigned priorities. As of priority < 6 any configured alarm
output K10 (OL 5890) is enabled.
Code
Text
25
25:Boiler sensor solid fuel
47
47:Common return sensor
50
50:DHW sensor 1
52
52:DHW sensor 2
57
57:DHW circulation sensor
70
70:Storage tank sensor 1
71
71:Storage tank sensor 2
73
73:Collector sensor 1
74
74:Collector sensor 2
126
126:DHW charg temp
127
127:Legionella temp
201
201:Frost alarm
241
241:Flow sensor yield
242
242:Return sensor yield
324
324:BX same sensors
330
330:BX1 no function
331
331:BX2 no function
332
332:BX3 no function
339
339:Coll pump Q5 missing
340
340:Coll pump Q16 missing
341
341:Coll sensor B6 missing
342
342:Solar DHW B31missing
343
343:Solar integration missing
344
344:Solar buffer K8 missing
346
346:Boiler pump Q10 missing
347
347:Solid fuel boil comp sens
349
349:Buff valve Y15 missing
Line no.
Operating line
6710
Reset alarm relay
No
Yes
When a fault is pending, an alarm can be triggered on relay ZX1. Relay ZX1 must
be configured accordingly.
This setting is used to reset the relay, but the alarm is maintained.
Line no.
Operating line
6800...6808
Time stamp and error history 1 - 5
The basic unit stores the last 5 faults in non-volatile memory. Any additional entry
deletes the oldest in the memory. For each error entry, error code and time of
occurrence are saved.
Possible error messages are listed in Section "List of displays".
Line no.
Operating line
6820
Reset history
No
Yes
The error history with the last 5 errors, the associated actual values and setpoints
and the relay output states will be deleted.
Solar compact controller
The settings in detail
Description of error
Solid fuel boiler temperature (wood) sensor error
Common return temperature sensor error
DHW temperature 1 sensor error
DHW temperature 2 sensor error
DHW circulation temperature sensor error
Buffer storage tank temperature 1 sensor error
Buffer storage tank temperature 2 sensor error
Collector temperature 1 sensor error
Collector temperature 2 sensor error
DHW - loading supervision
Legionella temperature not reached
Frost alarm
Flow sensor, solar sensor error
Return sensor, solar sensor error
BX same sensors
Sensor BX1 no function
Sensor BX2 no function
Sensor BX3 no function
Collector pump Q5 missing
Collector pump Q16 missing
Collector sensor B6 missing
Solar DHW sensor B31 missing
Solar integration missing
Solar controlling element buffer K8 missing
Solid fuel boiler pump Q10 missing
Solid fuel boiler comparison sensor missing
Buffer return valve Y15 missing
Prio
6
6
6
6
6
6
6
6
6
6
6
9
6
6
3
3
3
3
3
3
3
3
3
3
3
3
3
47 / 64
CE1U2396en