Input/Output Test - Siemens Albatros2 RVA78.690 User Manual

Solar compact controller
Hide thumbs Also See for Albatros2 RVA78.690:
Table of Contents

Advertisement

Relay test
Relay test Q5/ZX1
Modulation signal
Q5/ZX1
Sensor test
Pulse counter
48 / 64
Siemens
Building Technologies
6.12

Input/output test

Line no.
Operating line
7705
Mod setpoint Q5 relay test
7708
Modulation signal Q5 test
7711
Mod setpoint ZX1 relay test
7712
Modulation signal ZX1 test
The input / output test checks for proper operation and correct wiring of the
connected components.
A signal from 0-100% can be output on the corresponding output.
The value in % corresponds to the desired water volume.
View of present modulation signal on output Q5 or ZX1
Line no.
Operating line
7750
Collector temp B6
7820
Sensor temp BX1
7821
Sensor temp BX2
7822
Sensor temp BX3
Select a sensor test to display the corresponding input and check it in this manner.
The selected sensor values are updated within a maximum of 5 seconds.
The display is made with no measured value correction.
Line no.
Operating line
7842
Pulse counter H1
Display of the sum total of pulses on input H1 since the pulse counter was
comissioned. (Input H1 is set programmed for pulse counting and is not used by
another function).
Solar compact controller
The settings in detail
CE1U2396en
18.08.2010