Function output P1
44 / 64
Siemens
Building Technologies
6.10.6 Input sensor BX1-3
Line no.
Operating line
5930,5931,
Sensor input BX1, 2, 3
5932
None
DHW sensor B3
DHW sensor B31
Buffer storage tank sensor B4
Buffer storage tank sensor B41
Collector sensor 2 B61
Solar flow sensor B63
Solar return sensor B64
Common return sensor B73
Solid fuel boiler sensor B22
DHW circulation sensor B39
Depending on the selection made, setting of the sensor inputs assigns appropriate
extra functions to the basic diagrams. See Section "Auxiliary functions".
6.10.7 PWM output P1
Line no.
Operating line
6085
Function output P1
None
Per output Q5
P er output ZX1
Output P1 makes possible the control of variable speed pumps with a pulse-width-
modulated low voltage signal.
The relay terminal connections of the relevant pump in that case do not change;
they will only be complemented by the PWM control line.
The corresponding TRIAC output for the pump is switched ON/OFF, but not
modulated.
None
O utput P1 is not controlled.
Per output Q5
The low voltage signal is calculated and issued for collector pump Q5.
Per output ZX1
The low voltage signal is calculated and issed for the pump connected to relay
output ZX1 (Q4, Q16, K9, Q11 or Q10).
Solar compact controller
The settings in detail
CE1U2396en
18.08.2010