Technical Data; Basic Units Rva78.690 - Siemens Albatros2 RVA78.690 User Manual

Solar compact controller
Hide thumbs Also See for Albatros2 RVA78.690:
Table of Contents

Advertisement

Power supply
Wiring of terminals
Functional data
Inputs
Outputs
Degree of protection
and safety class
Standards, safety, EMC,
etc.
Climatic conditions
Weight
60 / 64
Siemens
Building Technologies
8

Technical data

8.1

Basic units RVA78.690

Rated voltage
Rated frequency
Max. power consumption
Fusing of supply lines
Power supply and outputs
Software class
Mode of operation to EN 60 730
Sensor inputs B6, BX1...BX3
Perm. sensor cables (copper)
with cross-sectional area:
Max. length
Triac outputs Q5, ZX1
Rated current range
ON/OFF mode
(Zero crossing switched)
Speed control
Max. switch-on current
PWM output P1
Signal frequency
Output voltage
degree of modulation
Degree of protection of housing to EN 60
529
Safety class to EN 60 730
Degree of pollution to EN 60 730
CE conformity to
EMC directive
- Immunity
- Emissions
Low-voltage directive
- Electrical safety
Storage to IEC721-3-1 class 1K3
Transport to IEC721-3-2 class 2K3
Operation to IEC721-3-3 class 3K5
Without packaging
Solar compact controller
Technical data
AC 230 V
±
(
10%)
50/60 Hz
RVA78.690: 10 VA
max. 10 AT
solid wire or stranded wire (twisted or with
ferrule):
2
1 core: 0.5...2.5 mm
2
2 cores: 0.5. mm
..1.5 mm
3 cores: not allowed.
A
1.B (automatic operation)
NTC10k
PT1000 (selectable for collector sensor)
0.25
0.5
0.75
1.0
20
40
60
80
AC 0.05...1 (2) A
AC 0.05...0.8 (0.8) A
4 A for <1 second
30 A at <20 ms
3 kHz
V
> + 4 V (with no load)
out_high
V
< +1 V
out_low
3 % ... 97 %
IP 00
low-voltage-carrying parts meet the
requirements of safety class II, if correctly
installed
normal pollution
89/336/EEC
- EN 61000-6-2
- EN 61000-6-3
73/23/EEC
- EN 60730-1, EN 60730-2-9
temperature -20...65°C
temperature -25...70 °C
temperature 0...50 °C (noncondensing)
RVA78.690: 530 g
2
2
1.5
Mm
120
M
CE1U2396en
18.08.2010

Advertisement

Table of Contents
loading

Table of Contents