6.10.12 Heat request
Line no.
Operating line
6207
Heat request K27
A heat request can be output to an external, controllable heat generator via relay
Z
X1. The setting defines the situations when heat request is output.
Domestic hot water
Heat request is output if a temperature demand is pending for DHW storage tank.
Buffer sensor
Heat request is output if a temperature demand is pending for buffer storage tank.
6.10.13 Overtemperature protection
Line no.
Operating line
6208
Excess heat dischar sensor
6209
Excess heat discharge temp
6210
Swi diff excess heat disch
Define the sensor used to monitor overtemperature protection.
B3
In the DHW storage tank with comparative temperature B3
B31
In the DHW storage tank with comparative temperature B31
B4
In the buffer storage tank with comparative temperature B4
B41
In the buffer storage tank with comparative temperature B41
B22
In the solid fuel boiler
B6
Vir collectors to the environment
Limit value for the overtemperature protection function. It is considered
overtemperature if the measured temperature is above this value and
overtemperature protection is started.
The overtemperature protection stops as soon as the measured temperature is
below the "overtemperature protection" (6209) by the switching differential as set
here.
6.10.14 Device data
Line no.
Operating line
6220
Software version
6222
Device hours run
The software version indicated here represents the current controller version.
This indicates the total number of operating hours since the controller was first
commissioned.