Delta T-controller
Pump overrun time
Siemens
Building Technologies
6.7.2
Boiler / burner control
Line no.
Operating line
4130
Temp diff on
4131
Temp diff off
4133
Comparative temp
DHW sensor B31
Buffer storage tank sensor B4
Buffer storage tank sensor B41
Flow temperature setpoint
Setpoint min
For the boiler pump to be put into operation, a sufficiently great temperature
differential between boiler temperature and comparative temperature is required.
T
Bx
On
QX
Off
TKx
Boiler temperature
Bx
Actual comparative temperature
On / Off
Boiler pump
SDon
Temp diff on
SDoff
Temperature differential solar OFF
6.7.3
Overtemperature protection
Line no.
Operating line
4140
Pump overrun time
If the boiler temperature drops below the minimum temperature differential or the
minimum setpoint, the boiler pump keeps running for the parameterized overrun
time.
Solar compact controller
The settings in detail
TKx
SDon
SDoff
t
CE1U2396en
33 / 64