ANNEX I. COMMUNICATION OBJECTS
"Functional range" shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a particular meaning
because of the specifications or restrictions from both the KNX standard or the application program itself.
Number
Size
1
1 Bit
2
1 Bit
1 Bit
3
1 Bit
4
1 Byte
5, 35, 65, 95
2 Bytes
6, 36, 66, 96
2 Bytes
7, 37, 67, 97
2 Bytes
8,38, 68, 98
1 Byte
1 Bit
9, 39, 69, 99
1 Bit
1 Bit
10, 40, 70, 100
1 Bit
1 Bit
11, 41, 71, 101
1 Bit
1 Bit
12, 42, 72, 102
1 Bit
13, 43, 73, 103
1 Bit
14, 44, 74, 104
1 Bit
15, 45, 75, 105
1 Byte
16, 46, 76, 106 2 Bytes
http://www.zennio.com
I/O
Flags
Data type (DPT)
C T - - -
DPT_Trigger
C T - - -
DPT_Trigger
E
C - - W -
DPT_Switch
E
C - - W -
DPT_Switch
E
C - - W -
DPT_SceneControl
C - - W -
E
DPT_Value_Temp
C - - W -
E
DPT_Value_Temp
C T R - -
S
DPT_Value_Temp
E
C - - W -
DPT_HVACMode
E
C - - W -
DPT_Trigger
E
C - - W -
DPT_Switch
E
C - - W -
DPT_Trigger
E
C - - W -
DPT_Switch
E
C - - W -
DPT_Trigger
E
C - - W -
DPT_Switch
C - - W -
E
DPT_Trigger
C - - W -
E
DPT_Switch
C - - W -
E
DPT_Window_Door
E
C - - W -
DPT_Trigger
S
C T R - -
DPT_HVACMode
E
C - - W -
DPT_Value_Temp
Functional Range
0/1
Reset 0
0/1
Reset 1
0/1
Manual Control Lock
0/1
Manual Control Lock
0-63; 128-191
[Thermostat] Scene Input
-273.00 - 670760.00 [Tx] Temperature Source 1
-273.00 - 670760.00 [Tx] Temperature Source 2
-273.00 - 670760.00 [Tx] Effective Temperature
1=Comfort
2=Standby
[Tx] Special Mode
3=Economy
4=Building Protection
0/1
[Tx] Special Mode: comfort
0/1
[Tx] Special Mode: comfort
0/1
[Tx] Special Mode: standby
0/1
[Tx] Special Mode: standby
0/1
[Tx] Special Mode: economy
0/1
[Tx] Special Mode: economy
0/1
[Tx] Special Mode: protection
0/1
[Tx] Special Mode: protection
0/1
[Tx] Window Status (input)
0/1
[Tx] Comfort Prolongation
1=Comfort
2=Standby
[Tx] Special Mode Status
3=Economy
4=Building Protection
-273.00 - 670760.00 [Tx] Setpoint
Name
Voltage Recovery -> Sending of 0
Voltage Recovery -> Sending of 1
0 = Lock; 1 = Unlock
0 = Unlock; 1 = Lock
Scene Value
External Sensor Temperature
External Sensor Temperature
Effective Control Temperature
1-byte HVAC Mode
0 = Nothing; 1 = Trigger
0 = Off; 1 = On
0 = Nothing; 1 = Trigger
0 = Off; 1 = On
0 = Nothing; 1 = Trigger
0 = Off; 1 = On
0 = Nothing; 1 = Trigger
0 = Off; 1 = On
0 = Closed; 1 = Open
0 = Nothing; 1 = Timed Comfort
1-byte HVAC Mode
Thermostat Setpoint Input
Technical Support:
http://zennioenglish.zendesk.com
MAXinBOX 66
Function
19
Need help?