Fault codes
(cont.)
Display
Const.
Weath.‐
fault
comp.
code
F3
X
X
F4
X
X
F5
X
X
F6
X
X
F8
X
X
System char-
Cause
acteristics
Burner control
Flame signal
unit fault
is already
present at
burner start
Burner control
No flame sig-
unit fault
nal.
Fault on bur-
The air pres-
ner control
sure switch
unit
is closed
during the
burner start
or does not
close when
the ignition
load speed
has been
reached
Fault on bur-
The gas
ner control
pressure
unit
switch is
closed dur-
ing the bur-
ner start or is
not closed at
the end of
the flame
stabilisation
phase
Burner control
Fuel valve
unit fault
closes too
late
Troubleshooting
Remedy
Check the ionisa-
tion electrode and
connecting leads;
press "E"
Check the ionisa-
tion electrode,
ignition, ignition
module, connect-
ing cables and
leads, gas pres-
sure, gas combi-
nation valve and
the ionisation cur-
rent; press "E"
Check the flue
gas/ventilation
system, the air
pressure switch
hoses, the air
pressure switch
and connecting
leads
Check gas pres-
sure switch, gas
pressure and gas
combination valve
Check the gas
combination valve
and both control
paths; press "E"
85