Viessmann VITOPEND 200 Installation And Service Instructions Manual page 59

Gas fired combi boiler
Table of Contents

Advertisement

Code 2
(cont.)
Coding in the delivered condition
9C:20
Monitoring LON users.
If a user fails to re-
spond, the values de-
faulted by the control
unit will be used after
20 min. Only then will a
fault message be is-
sued. (only for weather‐
compensated control
units)
9F:8
Differential temperature
8 K; only in conjunction
with the mixer circuit
(only for weather‐com-
pensated control units)
Boiler circuit, mixer circuit
A0:0
Without remote control
(only for weather‐com-
pensated control units)
Possible change
9C:0
No monitoring
9C:5
The time is adjustable
to
from 5 to 60 min
9C:60
9F:0
Differential temperature
to
adjustable from 0 to 40 K
9F:40
A0:1
With Vitotrol 200 (auto-
matic recognition)
A0:2
With Vitotrol 300 (auto-
matic recognition)
Coding
59

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents