Code 1
(cont.)
Coding in the delivered condition
Max. boiler temp.
06:...
Maximum limit of the
boiler water tempera-
ture, defaulted in °C by
the boiler coding card
Gas type
1E:0
Operation with natural
gas
Venting/filling
2F:0
Program disabled
User no.
77:1
LON user number (only
for weather‐compen-
sated control units)
Summer econ. A1
A5:5
With heating circuit
logic function (only for
weather‐compensated
control units)
Min. flow temp. A1/M2
C5:20
Electronic minimum
limit of the flow tem-
perature 20 °C (only for
weather‐compensated
control units)
Max. flow temp. A1/M2
C6:75
Electronic maximum
limit of the flow tem-
perature 75 °C (only for
weather‐compensated
control units)
Possible change
06:20
Maximum limit of the boi-
to
ler water temperature
06:127
within the ranges de-
faulted by the boiler
1E:1
Operation with LPG
2F:1
Venting program enabled
2F:2
Filling program enabled
77:2
LON user number, adjus-
to
table from 1 to 99:
77:99
1‐4 = boiler
5 = Cascade
10 ‐ ... = Vitotronic 050
99 = Vitocom
Note
Allocate each number
only once.
A5:0
Without heating circuit
pump logic function
C5:1
Minimum limit adjustable
to
from 1 to 127 °C
C5:127
C6:10
Maximum limit adjustable
to
from 10 to 127 °C
C6:127
Coding
51