Viessmann VITOPEND 200 Installation And Service Instructions Manual page 64

Gas fired combi boiler
Table of Contents

Advertisement

Coding
Code 2
(cont.)
Parameter ad-
With heating circuit pump logic function:
dress b5:...
Heating circuit pump "OFF"
1:
RT
Actual
2:
RT
Actual
3:
RT
Actual
4:
RT
Actual
5:
RT
Actual
6:
RT
Actual
7:
RT
Actual
8:
RT
Actual
Coding in the delivered condition
Boiler circuit, mixer circuit
C5:20
Electronic minimum
limit of the flow tem-
perature 20 °C (only for
weather‐compensated
control units)
C6:74
Electronic maximum
limit of the flow tem-
perature 74 °C (only for
weather‐compensated
control units)
d3:14
Heating curve slope =
1.4 (only for weather‐
compensated control
units)
d4:0
Heating curve slope = 0
(only for weather‐com-
pensated control units)
d5:0
The external heating
program changeover
changes the heating
program to "Constant
operation with reduced
room temperature"
(only for weather‐com-
pensated control units)
64
> RT
+ 5 K
Set
> RT
+ 4 K
Set
> RT
+ 3 K
Set
> RT
+ 2 K
Set
> RT
+ 1 K
Set
> RT
Set
‐ 1 K
> RT
Set
‐ 2 K
> RT
Set
Possible change
C5:1
to
C5:127
C6:10
to
C6:127
d3:2
to
d3:35
d4:–13
to
d4:40
d5:1
Heating circuit pump "ON"
RT
< RT
+ 4 K
Actual
Set
RT
< RT
+ 3 K
Actual
Set
RT
< RT
+ 2 K
Actual
Set
RT
< RT
+ 1 K
Actual
Set
RT
< RT
Actual
Set
‐ 1 K
RT
< RT
Actual
Set
‐ 2 K
RT
< RT
Actual
Set
‐ 3 K
RT
< RT
Actual
Set
Minimum limit adjustable
from 1 to 127 °C
Maximum limit adjustable
from 10 to 127 °C
Heating curve slope ad-
justable from 0.2 to 3.5
(see page 43)
Heating curve level ad-
justable from –13 to 40
(see page 43)
The external heating pro-
gram changeover
changes to "Constant
central heating with stan-
dard room temperature"