16.3 Drinking water connection

Only drinking water that corresponds with the drinking water ordinance may be used for the water supply.
Only the original connecting hoses provided in delivery may be used for the connection to the water supply.
The operating pressure of a minimum of 0.35 MPa and a maximum of 0.7 MPa and a water temperature of a
minimum of 8°C and a maximum of 30°C may not be undershot or exceeded, respectively.
In case of a chlorine content over 0.1 mg/l, the standard water filter (5 μm) must be replaced by a dual filter (5
μm/carbon) (optionally available as an accessory). If the iron content of the drinking water exceeds a value of 0.1 mg/l,
an iron filter should also be built into the water inlet pipe upstream of the fine filter. The device can be used for a
maximum water hardness of 26°dH.
If this value is exceeded, the service life of the reverse osmosis membrane is considerably reduced!
Water connection set (Accessories) consisting of:
2 pcs connection hoses a 1.5 m
2 pcs plastic screw connections
1 pc wall mounting bracket
Mounting diagram:
In case of a defect (leakage), the safety valve closes and the uncontrolled discharge of water is prevented. To re-establish proper
function: close the water valve, remove the hose, unscrew the safety valve, and press the red button on the output side of the valve.

16.4 Warm water heater battery connection

The heater battery (supply line and return line) is to be connected to the heating system via a circulation pump and a 3-
way motor mixer valve. The supply line temperature should amount to at least 50°C and must be available constantly
during the heating period.
Pumps/mixer connection set (optional accessories) consisting of:
1 pc circulation pump 230 V
2 pcs screw connections, R 1/2a / 15 mm MS (brass)
1 pc 3-way-mixer valve with actuator 230 V, Rp1/2", DN 15, run time 120 seconds
Image 2 – Circulation pump with screw connections
1 pc safety valve
1 pc filter casing
1 pc water filter
Image 3 – 3-way-mixer valve with actuator