Circulation pump <
Wat.Soft.Pump
Motor
<
Valve
<
Discharge pump <
E-heating
1
<
Open mixer
<
Close mixer
<
Fan
<
UV lamp
<
Horn
<
• When E-Heating Act. Is set, the Open Mixer and
Close Mixer items are replaced by
E-heating
2
<
UVC check
<
• With the UVC Check parameter is set, the current
light output of the UVC pipe is determined. At the right
bottom, the current value and the value calibrated
underneath that (light output of the new pipe) is
displayed. In comparison with the calibrated value, the
light output is shown as a percentage.
Floating switch<
• This parameter is used to check the function of the
floating switch. When the float is raised, the ">"
character changes from Off to On.
.
Time valv.wat.rep
• The opening time for the water valve is set when
the water tank is filled (water level after water
replacement).
Setting range: 20 – 600 seconds
Factory setting: 260 seconds KWL HB 250,
180 seconds KWL HB 500
Time valve ctrl.
<
Circulation pump On<
Off
Wat.Soft.Pump On<
Off
Motor
On<
Off
Valve
On<
Off
Discharge pump On<
Off
E-heating
1 On<
Off
Open mixer
On<
Off
Close mixer
On<
Off
Fan
On<
Off
UV lamp
On<
Off
Horn
On<
Off
and
E-heating
3
UVC check
3.65
80%
Cal: 4.56
Floating switch
>On
Off
Time valv.wat.rep.
260s
Time valve ctrl.
030s
• This parameter is used to set the refill time of the
water during humidity control. The air humidity is
determined every minute. When the reference value is
undershot, the valve is opened according to a set
value.
Setting range: 1 – 70 seconds
Factory setting: 30 seconds KWL HB 250
Runtime mixer
• With this parameter, the runtime of the mixer can be
set.
Setting range: 2 – 30 seconds
Factory setting: 6 seconds
Time Int. Mixer
• With the Time Interval Mixer parameter, the interval
time according to which the control system readjusts
the mixer can be set.
Setting range: 1 – 120 minutes
Factory setting: 5 minutes
Time rinsing
• Defines the runtime of the rinsing programme.
Setting range: 1 – 20 minutes
Factory setting: 10 minutes
UVC operation
• Indicates the operating hours of the UVC pipe.
<
Reset UVC
• Deletes the operating hours meter of the UVC pipe.
Can be performed after every UVC pipe change.
Error messages<
• Occurring error messages are logged automatically
and can be queried under this menu item.
Fact. setting
• If Factory Setting is selected in the programme, all
saved settings are deleted. The control system must
be recommissioned and reset. In addition, a test
menu for testing the individual components appears.
40 seconds KWL HB 500
Runtime mixer
<
006s
Time Int. Mixer
<
005min
Time rinsing
<
010min
UVC operation
<
00001 h
Reset UVC
<
Yes
01: No error
occured
Load fact.
<
setting?
No<
Yes<
No
14