Allow the appropriate space in front of C Series modules for cabling clearance, as shown in
the following figure. The different connector types on C Series modules require different
cabling clearances. For a complete list of cabling clearances for C Series modules, visit
ni.com/info
and enter the Info Code
63.5 mm
(2.50 in.)
2
25.4 mm
(1.00 in.)
Ambient Temperature
Measure the ambient temperature at each side of the cRIO-9066, 63.5 mm (2.50 in.) from the
side and 25.4 mm (1.00 in.) forward from the rear of the cRIO-9066, as shown in the
following figure.
Figure 11. cRIO-9066 Ambient Temperature Location
1
63.5 mm
(2.50 in.)
63.5 mm
(2.50 in.)
1
25.4 mm
(1.00 in.)
1. Location for measuring the ambient temperature
Mounting the Device Directly on a Flat Surface
For environments with high shock and vibration, NI recommends mounting the cRIO-9066
directly on a flat, rigid surface using the mounting holes in the cRIO-9066.
crioconn
Figure 10. cRIO-9066 Cabling Clearance
Cabling Clearance
50.8 mm (2.00 in.)
.
29.1 mm
(1.14 in.)
1
NI cRIO-9066 User Manual | © National Instruments | 17
50.8 mm
(2.00 in.)
62.3 mm
2
(2.45 in.)
25.4 mm
(1.00 in.)
63.5 mm
(2.50 in.)
1
63.5 mm
(2.50 in.)
1
25.4 mm
(1.00 in.)
63.5 mm
(2.50 in.)