Siemens ET 200M Manual

Siemens ET 200M Manual

Marshalled termination assemblies remote i/o modules
Table of Contents

Advertisement

Safety Matrix
ET 200M
Marshalled Termination Assemblies
Remote I/O Modules
Manual
08/2016
A5E00482820-12
___________________
Overview
Installation
___________________
Maintenance
___________________
8-Channel Analog Input MTA
8-Channel Analog Input MTA
___________________
8-Channel Analog Output
MTA
___________________
8-Channel RTD Input MTA
8-Channel TC Input MTA
___________________
6-Channel F Analog Input
MTA
___________________
6-Channel F Analog Input
HART MTA
6-Channel F Analog Input
___________________
HART MTA
16-Channel, 24 VDC Discrete
Input MTA
___________________
12/24-Channel, 24 VDC F
Discrete Input MTA
10-Channel, 24 VDC F
___________________
Discrete Output MTA
16-Channel, 24 VDC Discrete
___________________
Output MTA
16-Channel, 24 VDC Discrete
Output MTA
___________________
Failsafe 10-Channel, 24-150
VDC/120-230 VAC Relay
Output MTA
16-Channel, 24-150 VDC/120-
230 VAC Relay Output MTA
Power Monitor Board
8-Channel HART Analog Input
MTA
8-Channel HART Analog
Output MTA
16-Channel, 24 VDC Power
Supply MTA
Previous MTA Revisions
Safety Information for US
Customers
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24

Advertisement

Table of Contents
loading

Summary of Contents for Siemens ET 200M

  • Page 1 Overview Installation ___________________ Maintenance ___________________ 8-Channel Analog Input MTA 8-Channel Analog Input MTA ___________________ 8-Channel Analog Output ET 200M ___________________ Marshalled Termination Assemblies 8-Channel RTD Input MTA Remote I/O Modules 8-Channel TC Input MTA ___________________ 6-Channel F Analog Input Manual...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3 This manual contains information on the use of Siemens Marshalled Termination Assemblies (MTAs) to adapt field wiring to ET200M remote I/O modules. Specifically designed for standard and failsafe I/O modules used in ET 200M assemblies, these field termination solutions support analog inputs and outputs, discrete inputs and outputs, and relay outputs.
  • Page 4 The sales contract contains the entire obligation of Siemens. The warranty contained in the contract between the parties is the sole warranty of Siemens. Any statements continued herein do not create new warranties or modify the existing warranty.
  • Page 5 Preface Approvals Marshalled Part Numbers Agency Approvals Termination Assembly Analog Input 6ES7650-1AA50-2XX0 8-Channel 16 bit EMC in accordance with 6ES7650-1AA51-2XX0 EN61000-6-2 EN61000-6-4 6ES7650-1AA52-2XX0 ATEX in accordance with EN600079-0 Analog Output 6ES7650-1AB50-2XX0 EN600079-15 8-Channel 12 bit 6ES7650-1AB51-2XX0 Safety: RTD Input EN 61131-2:2007 6ES7650-1AG50-2XX0 8-Channel 6ES7650-1AG51-2XX0...
  • Page 6 16-Channel 6ES7650-1BE10-3XX0 24VDC Additional Support If you have questions about the use of products presented in this manual, contact your local Siemens representative: http://www.siemens.com/automation/partner A&D Technical Support Available worldwide, 24 hours a day: United States: Johnson City, TN Worldwide: Nürnberg...
  • Page 7 Service & Support on the Internet In addition to our paper documentation, we also provide all of our technical information on the Internet at: http://www.siemens.com/automation/service&support Here, you will find the following information: • Newsletter providing the latest information on your products •...
  • Page 8 Preface Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 9: Table Of Contents

    Contents Overview System Architecture ................... 17 Marshalled Termination Assemblies (MTAs) ............. 18 General Construction and Dimensions .............. 20 Interconnecting Cables ..................22 Interconnecting Cable Assemblies ..............23 Installation Environmental Considerations ..................29 Mechanical Installation ..................30 Electrical Installation ..................30 2.2.1 Cabinet Guidelines ....................
  • Page 10 Contents 5.11.2 Inputs ......................... 59 5.11.3 Redundancy ....................... 60 5.12 Technical Specifications for 8-Channel Analog Input Module (6ES7 331-7NF00- 0AB0 / 6ES7331-7NF10-0AB0) ................. 60 8-Channel Analog Output MTA Description ......................61 Features ......................61 Operation ......................62 Installation Requirements .................. 62 Maintenance ......................
  • Page 11 Contents Features ......................87 Operation ......................88 Installation Requirements .................. 90 Maintenance ...................... 91 6-Channel F Analog Input Marshalled Termination Assembly ......92 Technical Specifications ..................94 Module Restrictions ................... 95 9.10 Typical Transmitter Connection to Field Terminals ........... 96 9.11 Hardware Configuration ..................
  • Page 12 Contents 10.14.4 FAIH MTA to SAI MTA Cable ................133 10.14.5 Hardware Configuration ................... 135 6-Channel F Analog Input HART MTA 11.1 Description ....................... 137 11.2 Features ......................137 11.3 Modification vs 6-Channel F Analog Input MTA 6ES7650-1AH61-5XX0 ..137 11.4 Operation ......................
  • Page 13 Contents 13.12.3 Module Parameters ..................179 13.12.4 Redundancy ..................... 181 13.13 Technical Specifications for 12/24-Channel, 24 VDC F Discrete Input Module (6ES7 326-1BK00-0AB0 or 6ES7 326-1BK01-0AB0 or 6ES7 326-1BK02-0AB0)182 10-Channel, 24 VDC F Discrete Output MTA 14.1 Description ....................... 183 14.2 Features ......................
  • Page 14 Contents 16.12.2 Outputs ......................218 16.12.3 Redundancy ..................... 219 Failsafe 10-Channel, 24-150 VDC/120-230 VAC Relay Output MTA 17.1 Description ....................... 220 17.2 Features ......................220 17.3 Operation ......................221 17.4 Installation Requirements ................221 17.5 Maintenance ....................222 17.6 Simplified diagram ................... 223 17.7 Failsafe 10-Channel, 24-150 VDC/120-230 VAC Relay Output Marshalled Termination Assembly ..................
  • Page 15 Contents 20.8 Changes to Module Specifications ..............259 20.9 20.10 Typical Wiring Schemes .................. 260 20.11 Hardware Configuration ................... 262 20.11.1 Addresses ......................262 20.11.2 Inputs ....................... 262 20.11.3 Redundancy ..................... 262 20.12 Technical Specifications for 8-Channel HART Analog Input Module (6ES7 331- 7TF01-0AB0) ....................
  • Page 16 Contents Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 17: Overview

    Overview System Architecture Figure 1–1shows MTAs within the system architecture Figure 1–1 System Architecture Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-09...
  • Page 18: Marshalled Termination Assemblies (Mtas)

    Overview Marshalled Termination Assemblies (MTAs) The following table identifies the Siemens Marshalled Termination Assemblies (MTAs) discussed in this manual, including associated SIMATIC PCS 7 ET 200M I/O modules and interconnecting cables. Table 1–1 Marshalled Termination Assembly and Module Cross-Reference Marshalled Termination...
  • Page 19 Overview Table 1–1 Marshalled Termination Assembly and Module Cross-Reference Marshalled Termination PCS 7 ET 200M Module Redundant Assembly Part Numbers Description Part Number HART Analog Input 6ES7650-1AA61-2XX0 6ES7331-7TF01-0AB0 8-Channel HART Analog Output 6ES7650-1AB61-2XX0 6ES7332-8TF01-0AB0 8-Channel 6ES7650-1BE10-3XX0 Marshalled Termination Assemblies for ET200M Remote I/O Modules...
  • Page 20: General Construction And Dimensions

    Overview General Construction and Dimensions Figure 1–2 shows the general construction of a Marshalled Termination Assembly (MTA). There are two basic sizes for MTAs a long version and a short version. Refer to the technical specifications for the MTAs for dimensions. Figure 1–3 shows a typical long version.
  • Page 21 Overview Figure 1–3 Dimensions in inches [mm] Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 22: Interconnecting Cables

    Each MTA requires one of five types of interconnecting cable, available in standard lengths of 3 and 8 meters. See the table below. Table 1–2 Interconnecting Cables Interconnecting Cable Description Order Number Analog Input Siemens 40-pin to D25F for connecting 6ES7331-7NF00-0AB0 8-Channel (6ES7650-1AA52-2XX0) 6ES7922-3BD00-0BA0 (3M Length) 6ES7922-3BJ00-0BA0 (8M Length) for connecting 6ES7331-7NF10-0AB0...
  • Page 23: Interconnecting Cable Assemblies

    Interconnecting cables are intended for stationary installations only. Siemens 40 pin to Female Sub-D 50 The most common interconnecting cable uses a 40 pin Siemens ET200M I/O connector wired to a D50 female connector. See Figure 1–4 Figure 1–4 Interconnecting Cable (6ES7922-3BD00-0AS0 or 6ES7922-3BJ00-0AS0) Key to numbered items in Figure 1–4...
  • Page 24 20-pin Siemens connector (6ES7 392-1AJ00-0AA0) Siemens 40 pin to Female Sub-D 25 A third interconnecting cable uses a 40 pin Siemens ET200M I/O connector wired to a D25 female connector. See Figure 1–6 Figure 1–6 Interconnecting Cable (6ES7922-3BD00-0AN0 or 6ES7922-3BJ00-0AN0,...
  • Page 25 40-pin Siemens connector (6ES7 392-1AM00-0AA0) Siemens 20 pin to Female Sub-D 50 A fifth interconnecting cable uses a 20 pin Siemens ET200M I/O connector wired to a D50 female connector. See Figure 1–8. Figure 1–8 Interconnecting Cable (6ES7922-3BD00-0AU0 or 6ES7922-3BJ00-0AU0) Key to numbered items in Figure 1–8...
  • Page 27: Installation

    Installation This section describes installation of the ET200M Marshalled Termination Assemblies. Topics include: installation considerations and mechanical and electrical installation. This equipment is suitable for use in Class I, Division 2, Groups A, B, C, and D OR non- hazardous locations only. Combinations of equipment in your system are subject to investigation by the local Authority having jurisdiction at the time of installation.
  • Page 28 A service kit with a wrist strap and static dissipative mat is available from Siemens (PN15545-110). Equivalent kits are available from both mail order and local electronic supply companies.
  • Page 29: Environmental Considerations

    Installation Environmental Considerations Operate the ET200M MTAs within their environmental specifications to help ensure reliable, trouble-free operation with minimum down time. Refer to the Technical Specifications sections for each MTA’s operating temperatures limits, operating humidity, and maximum moisture content. Temperature Keep the air surrounding an operating system below 60°C (140°F).
  • Page 30: Mechanical Installation

    Installation Mechanical Installation The MTA housing is designed to be used with 35mm x 15mm Top Hat style DIN rail. Electrical Installation These sections contain electrical connection details for wiring an ET200M MTA. The Cabinet Guidelines provide required restrictions for installation inside a cabinet and the Wiring Guidelines contains specific information about connector identification, wire size, wire selection, and wire routing.
  • Page 31: Wiring Guidelines

    Installation 2.2.2 Wiring Guidelines Electrical Connections - Power, I/O, and network connections to a system are completed through removable connectors. For the analog I/O, Discrete Output 16 Channel and Relay Output 16 Channel MTAs the interconnection cable shield must be connected to ground at the I/O module.
  • Page 32: Installation Procedure

    Installation Installation Procedure 2.3.1 Without Cover and Frame Step Action Mount the MTA to the DIN rail (Recommend 35mm x 15mm Top Hat style) For EMC Compliance connect the MTA Shield stud to earth ground. Plug the interconnecting cable into the PCS7 I/O Modules For analog I/O Modules: Install shield connecting element, strip a section of outer insulation from interconnecting cable and place in shield connecting element Plug the interconnecting cable into the D25 or D50 on the MTA...
  • Page 33: Removal Procedure

    Installation Removal Procedure Should it be necessary to remove or replace a termination assembly, follow the procedures outlined below. 2.4.1 Without Cover Step Action Remove power and signals from the MTA Remove ground connection to MTA shield stud if applied Unplug the interconnecting cable into the D25 or D50 on the MTA Unplug the field terminal connectors into the MTA Unplug the IO power connector into the MTA...
  • Page 34 Installation Figure 2–1 Break-Away Connector Cover and Tabs Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 35: Maintenance

    Siemens sales office. • The use of unauthorized parts in the repair of the equipment or tampering by unqualified personnel will result in dangerous conditions that can cause death, serious injury, or equipment damage.
  • Page 36: Tools And Test Equipment

    Maintenance Tools and Test Equipment The following tools and equipment are necessary for servicing: • Common hand tools for servicing electronic equipment • Digital Multimeter (DMM) Voltmeter Section: Accuracy +/-0.01% of reading Resolution 1.0 mV input Impedance 10 MΩ Ammeter section: Accuracy +/- 0.1% of reading Resolution 100 μA •...
  • Page 37: 8-Channel Analog Input Mta

    This section contains installation information and requirements for Siemens Marshalled Termination Assembly (MTA) (6ES7650-1AA51-2XX0 or 6ES7650- 1AA50-2XX0), which connects to the Siemens ET 200M 8-Channel Analog Input Module (6ES7 331-7NF00-0AB0, E-Stand 5 or higher). Note: The only major difference between the two part numbers is the housing.
  • Page 38: Operation

    8-Channel Analog Input MTA Operation Power is supplied via the two removable power connectors which are retained by screws and marked L+A, MA, and L+B, MB. Each has circuitry to detect the presence of voltage over 15 VDC and turn on the LED indicator. The LEDs are marked A POWER and B POWER.
  • Page 39: Installation Requirements

    8-Channel Analog Input MTA Installation Requirements See Section 2, Installation, before performing any installation and observe all warnings A common interconnecting cable (6ES7922-3BD00-0AS0 or 6ES7922-3BJ00- 0AS0), supporting eight analog input channels, connects the analog input termination assembly to the 8-channel analog input module (6ES7 331-7NF00- 0AB0, E-Stand 5 or higher).
  • Page 40: 8-Channel Analog Input Marshalled Termination Assembly

    8-Channel Analog Input MTA 8-Channel Analog Input Marshalled Termination Assembly The figure below shows the basic parts of the 8-Channel Analog Input MTA. Figure 4–1 8-Channel Analog Input Marshalled Termination Assembly (6ES7650-1AA51-2XX0 or 6ES7650-1AA50-2XX0) 32 CH7 SHIELD 31 CH7 I- 30 CH7 I+ 29 CH7 POWER 28 CH6 SHIELD...
  • Page 41 8-Channel Analog Input MTA Key to numbered items in Figure 4–1: Item Description Input power connections Input Power Indicators Field Connections I/O Module Connections ( J1 & J2 ) Shield disconnect jumper (W100 & W101) Field power fuses Field power indication ( 1 of 8 ) Input Isolation Jumpers ( W8 –...
  • Page 42: Technical Specifications

    Humidity 5% to 95% Non-condensing Approvals MTA Agency Approvals See Preface section, Approvals Table Note Fuses are available as spare parts from Siemens. Fuse information can be found at: http://www.littelfuse.com http://www.bussmann.com Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 43: Module Restrictions

    8-Channel Analog Input MTA Module Restrictions Restrictions for 8-Channel Analog Input MTA (6ES7650-1AA51-2XX0 or 6ES7650-1AA50-2XX0) I/O Module Restrictions None SAI Module None Voltage +/-5 V, 1 - 5 V, & +/-10 V Current 0 – 20 mA, +/- 20 mA, & 4 – 20 mA Module Accuracy Voltage Input (MTA I/V set to V) See Module Specs...
  • Page 44 8-Channel Analog Input MTA Figure 4–3 Analog Input Voltage Input Connection Example (MTA I/V Jumper set to V) PWR0 +Sig PWR1 Voltage Source -Sig Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 45: Hardware Configuration

    8-Channel Analog Input MTA 4.10 Hardware Configuration Use the I – V jumpers to select voltage or current input signals. Configure the AI8 module to match the input signal type. See Figure 4–1, Item 8, for the location of the isolation jumper and Item 10, for the location of the I - V Jumper.
  • Page 46: Inputs

    8-Channel Analog Input MTA 4.10.2 Inputs Select appropriate module hardware configuration settings. Select Measuring Type and Measuring Range settings to match the input signal connected to the channel inputs. Measurement of signals less than 0 volts or 0 mA requires that the channel isolation jumper be cut.
  • Page 47: Redundancy

    8-Channel Analog Input MTA 4.10.3 Redundancy Figure 4–6 shows the redundant configuration. For non-redundant operation, in the Redundancy box, select None. All other parameters should be set to user preferences. Figure 4–6 8-Channel Analog Input Hardware Configuration: Redundancy Selection Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 48: Technical Specifications For 8-Channel Analog Input Module (6Es7 331-7Nf00-0Ab0)

    8-Channel Analog Input MTA 4.11 Technical Specifications for 8-Channel Analog Input Module (6ES7 331-7NF00-0AB0) Note For a complete functional description and the most current technical specifications for this module, refer to the manual S7-300 Programmable Controller Module Specifications (document number A5E00105505). Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 49: 8-Channel Analog Input Mta

    This section contains installation information and requirements for Siemens Marshalled Termination Assembly (MTA) (6ES7650-1AA52-2XX0) which connects to the Siemens ET 200M 8-Channel Analog Input Module (6ES7 331-7NF00-0AB0, E-Stand 5 or higher) or the Siemens ET 200M 8-Channel Analog Input Module (6ES7 331-7NF10-0AB0; E-Stand 8 or higher). Features This MTA has the following features: •...
  • Page 50: Operation

    8-Channel Analog Input MTA Operation Power is supplied via two power connectors marked L/A+, M/A, and L/B+, M/B. Each has a circuitry to detect the presence of voltage over 15 VDC and turn on the LED indicator (green). The case of polarity reversal of the power supply is indicated by the LEDs illuminating red.
  • Page 51: Installation Requirements

    8-Channel Analog Input MTA Installation Requirements See Section 2, Installation, before performing any installation and observe all warnings Two interconnecting cable types (for Module 6ES7331-7NF00-0AB0: 6ES7922- 3BD00-0BA0 (3m), 6ES7922-3BJ00-0BA0 (8m); for Module 6ES7331-7NF10- 0AB0: 6ES7922-3BD00-0BB0 (3m), 6ES7922-3BJ00-0BB0 (8m)) , supporting eight analog input channels, connects the analog input termination assembly to the 8- channel analog input module (6ES7 331-7NF00-0AB0, E-Stand 5 or higher) or to the 8-channel analog input module (6ES7331-7NF10-0AB0).
  • Page 52: 8-Channel Analog Input Marshalled Termination Assembly

    8-Channel Analog Input MTA 8-Channel Analog Input Marshalled Termination Assembly The figure below shows the basic parts of the 8-Channel Analog Input MTA. Figure 5-1 8-Channel Analog Input Marshalled Termination Assembly (6ES7650-1AA52-2XX0) CH7 SHIELD CH6 SHIELD CH7 I - CH6 I - CH7 I + CH6 I + CH7 POWER...
  • Page 53 8-Channel Analog Input MTA Key to numbered items in Figure 5–1: Item Description Input power connections (L/A+, M/A, L/B+, M/B) Output Power Monitoring System (1, 2) I/O Module Connections (MODULE1, MODULE2) Module fuses (MODULE1, MODULE2) Shield Ground Stud for connecting to earth ground (SHIELD) Input Power Indicators (A POWER, B POWER) Shield disconnect jumper (MODULE 1, MODULE 2) 250Ω...
  • Page 54: Technical Specifications

    Between the channels AC 35V / DC 50V Fuse Ratings / Current Limiting Module 0.5 A (Bussmann P/N: GMA-0.5-R) (Siemens Spare P/N: A5E00755625) Power output for 2-wire transducer supply Supply current for each channel typ. 20 mA Short circuit current 25 …...
  • Page 55 Between the channels AC 60V / DC 75V Fuse Ratings / Current Limiting Module 0.5 A (Bussmann P/N: GMA-0.5-R) (Siemens Spare P/N: A5E00755625) Power output for 2-wire transducer supply Supply current for each channel typ. 20 mA Short circuit current 25 …...
  • Page 56 ± 0,2% Approvals MTA Agency Approvals See Preface section, Approvals Table User's Manual) Note Fuses are available as spare parts from Siemens. Fuse information can be found at: http://www.bussmann.com Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 57: Module Restrictions

    8-Channel Analog Input MTA Module Restrictions Restrictions for 8-Channel Analog Input MTA (6ES7650-1AA52-2XX0) I/O Module Restrictions None 8AI Module None Voltage +/-5 V, 1 - 5 V, +/-10 V Current 0 – 20 mA, +/- 20 mA, 4 – 20 mA 5.10 Typical Transmitter Connection to Field Terminals Figure 5-2 Analog Input Current Input Connection Examples (MTA I/V Jumper set to I and 2/4 Jumper set...
  • Page 58: Hardware Configuration

    8-Channel Analog Input MTA 5.11 Hardware Configuration Use the I – V jumpers to select voltage or current input signals and the 2 – 4 jumpers to select the transducer type. For voltage mode jumper 2 – 4 has to be set to 4.
  • Page 59: Inputs

    8-Channel Analog Input MTA 5.11.2 Inputs Select appropriate module hardware configuration settings. Select Measuring Type and Measuring Range settings to match the input signal connected to the channel inputs. Figure 5-5 shows the all the diagnostic boxes checked. Figure 5-5 8-Channel Analog Input Hardware Configuration: Inputs Setup Note •...
  • Page 60: Redundancy

    8-Channel Analog Input MTA 5.11.3 Redundancy Figure 4–65-6 shows the redundant configuration. For non-redundant operation, in the Redundancy box, select None. All other parameters should be set to user preferences. Figure 5-6 8-Channel Analog Input Hardware Configuration: Redundancy Selection 5.12 Technical Specifications for 8-Channel Analog Input Module (6ES7 331-7NF00-0AB0 / 6ES7331-7NF10-0AB0) Note...
  • Page 61: 8-Channel Analog Output Mta

    This section contains information and requirements to facilitate installation of Siemens Marshalled Termination Assembly (MTA) (6ES7650-1AB51-2XX0 or 6ES7650-1AB50-2XX0), designed to interface with the Siemens ET 200M 8- Channel Analog Output Module (6ES7 332-5HF00-0AB0, E-Stand 3 or higher). Note: The only major difference between the two part numbers is the housing.
  • Page 62: Operation

    8-Channel Analog Output MTA Operation Power is supplied via the two removable power connectors which are retained by screws and marked L+A, MA, and L+B, MB. Each has circuitry to detect the presence of voltage over 15 VDC and turn on the LED indicator. The LEDs are marked A POWER and B POWER.
  • Page 63: 8-Channel Analog Output Marshalled Termination Assembly

    8-Channel Analog Output MTA 8-Channel Analog Output Marshalled Termination Assembly Figure 6–1 below shows the basic parts of the 8-Channel Analog Output MTA. Figure 6–1 8-Channel Analog Output Marshalled Termination Assembly (6ES7650-1AB51-2XX0 or 6ES7650-1AB50-2XX0) 24 CH7 SHIELD 23 CH7- 22 CH7+ 21 CH6 SHIELD 20 CH6- 19 CH6+...
  • Page 64: Technical Specifications

    -25C to +60C Humidity 5% to 95% Non-condensing Approvals MTA Agency Approvals See Preface section, Approvals Table Note Fuses are available as spare parts from Siemens. Fuse information can be found at: http://www.bussmann.com Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 65: Module Restrictions

    8-Channel Analog Output MTA Module Restrictions Restrictions for 8-Channel Analog Output MTA (6ES7650-1AB51-2XX0 or 6ES7650-1AB50-2XX0) I/O Module Restrictions MTA Design There is no Channel to Channel Isolation MTA Design Series diodes lower the output compliance load to less than 600 Ω MTA Design Short Circuit to M not detected MTA Design...
  • Page 66: Hardware Configuration

    8-Channel Analog Output MTA 6.10 Hardware Configuration The Standard Analog Output MTA has no jumpers that affect the Module Hardware Configuration; however, the MTA design restricts the Module output to the current mode only. Note Redundant Operation. If a redundant Analog Output Module loses power (F10x opens) or is removed from service, then the output current will drop to 50% of its value for several controller cycles.
  • Page 67: Outputs

    8-Channel Analog Output MTA 6.10.2 Outputs For normal operation set Type of Output to current (I). The +/- 20 mA output range is not possible due to the MTA Design. All other Module hardware configuration choices under the Outputs tab are left to the user. Figure 6–4 shows the Type of Output set to I and all the diagnostic options are checked.
  • Page 68: Redundancy

    8-Channel Analog Output MTA 6.10.3 Redundancy Figure 6–5 shows redundant configuration. For non-redundant operation the value of the Redundancy field should be None. All other parameters should be set to user preferences. Figure 6–5 8-Channel Analog Output Hardware Configuration: Redundancy Selection 6.11 Technical Specifications for 8-Channel Analog Output Module (6ES7 332-5HF00-0AB0)
  • Page 69: 8-Channel Rtd Input Mta

    This section contains information and requirements to facilitate installation of Siemens Marshalled Termination Assembly (MTA) (6ES7650-1AG51-2XX0 or 6ES7650-1AG50-2XX0), designed to interface with the Siemens ET 200M 8- channel RTD Input Module (6ES7 331-7PF00-0AB0, E-Stand 8 or higher, & 6ES7 331-7PF01-0AB0).
  • Page 70: Installation Requirements

    8-Channel RTD Input MTA Installation Requirements See Section 2, Installation, before performing any installation and observe all warnings A common interconnecting cable (6ES7922-3BD00-0AS0 or 6ES7922-3BJ00- 0AS0), supporting eight RTD input channels, interconnects the RTD input termination assembly to the 8-channel RTD input module (6ES7 331-7PF00-0AB0, E-Stand 8 or higher &...
  • Page 71: 8-Channel, Rtd Input Marshalled Termination Assembly

    8-Channel RTD Input MTA 8-Channel, RTD Input Marshalled Termination Assembly Figure 7–1 shows the basic parts of the 8-Channel RTD Input MTA. Figure 7–1 8-Channel RTD Input Marshalled Termination Assembly (6ES7650-1AG51-2XX0 or 6ES7650-1AG50-2XX0) 2.20 CH7 SHIELD 1.20 CH6 SHIELD 2.19 CH7 I- 1.19 CH6 I- 2.18 CH7 I+ 1.18 CH6 I+...
  • Page 72: Technical Specifications

    -25C to +60C Humidity 5% to 95% Non-condensing Approvals MTA Agency Approvals See Preface section, Approvals Table Note Fuses are available as spare parts from Siemens. Fuse information can be found at: http://www.bussmann.com Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 73: Module Restrictions

    8-Channel RTD Input MTA Module Restrictions Restrictions for 8-Channel RTD Input MTA (6ES7650-1AG51-2XX0 or 6ES7650-1AG50-2XX0) I/O Module Restrictions MTA Design None Module Accuracy RTD Inputs See Module Specs Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 74: Typical R & Rtd Connection To Field Terminals

    8-Channel RTD Input MTA Typical R & RTD Connection to Field Terminals Note When connecting an RTD in 2-wire Mode there will be no resistance error • correction of the field wiring. The 3 wire connection method produces a constant offset. The temperature •...
  • Page 75: Hardware Configuration

    8-Channel RTD Input MTA 7.10 Hardware Configuration Neither the 8-Channel RTD Module nor the MTA supports redundant operation 7.10.1 Addresses Figure 7–3 shows Input address and process image set to a user's preferences. Figure 7–3 8-Channel RTD Input Hardware Configuration: Address Setup Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 76: Inputs - Part 1

    8-Channel RTD Input MTA 7.10.2 Inputs – Part 1 Input parameters should be set to the user preferences that are consistent with the input device being used. Figure 7–4 shows some of the various configuration options for the Interrupts, Diagnostics, and Measuring parameters. Figure 7–4 8-Channel RTD Input Hardware Configuration: Inputs - Part 1 Parameters Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 77: Inputs - Part 2

    8-Channel RTD Input MTA 7.10.3 Inputs – Part 2 Input parameters should be set to the user preferences that are consistent with the input device being used. Figure 7–5 shows Temperature Unit set to degrees Celsius but degrees Fahrenheit is also possible. All settings should be set to user preferences. Figure 7–5 8-Channel RTD Input Hardware Configuration: Inputs - Part 2 Parameters 7.11 Technical Specifications for 8-Channel RTD Input...
  • Page 78 8-Channel RTD Input MTA Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 79: 8-Channel Tc Input Mta

    This section contains information and requirements to facilitate installation of Siemens Marshalled Termination Assembly (MTA) (6ES7650-1AF51-2XX0 or 6ES7650-1AF50-2XX0), designed to interface with the Siemens ET 200M 8- Channel TC Input Module (6ES7 331-7PF10-0AB0, E-Stand 4 or higher, & 6ES7 331-7PF11-0AB0).
  • Page 80: Installation Requirements

    8-Channel TC Input MTA Installation Requirements See Section 2, Installation, before performing any installation and observe all warnings A common interconnecting cable (6ES7922-3BD00-0AS0 or 6ES7922-3BJ00- 0AS0), supporting eight Thermocouple input channels, interconnects the Thermocouple input termination assembly to the 8-channel Thermocouple input module (6ES7 331-7PF10-0AB0, E-Stand 4 or higher &...
  • Page 81: 8-Channel Tc Input Marshalled Termination Assembly

    8-Channel TC Input MTA 8-Channel TC Input Marshalled Termination Assembly Figure 8–1 8-Channel TC Input Marshalled Termination Assembly (6ES7650-1AF51-2XX0 or 6ES7650-1AF50-2XX0) 2.12 CH7 SHIELD 1.12 CH6 SHIELD 2.11 CH7 TC- 1.11 CH6 TC- 2.10 CH7 TC+ 1.10 CH6 TC+ 2.9 CH5 SHIELD 1.9 CH4 SHIELD 2.8 CH5 TC- 1.8 CH4 TC-...
  • Page 82: Technical Specifications

    Approvals MTA Agency Approvals See Preface section, Approvals Table Note Fuses are available as spare parts from Siemens. Fuse information can be found at: http://www.bussmann.com See the Section 8.10, Hardware Configuration, for more information. Marshalled Termination Assemblies for ET200M Remote I/O Modules...
  • Page 83: Module Restrictions

    8-Channel TC Input MTA Module Restrictions Restrictions for 8-Channel TC Input MTA (6ES7650-1AF51-2XX0 or 6ES7650-1AF50-2XX0) I/O Module Restrictions MTA Design External Junction Compensation only Module Accuracy External Compensation Accuracy +/-0.3C or 0.6% of terminal temperature Typical Thermocouple Connection to Field Terminals Figure 8–2 Typical Thermocouple Connection to Field Terminals THERMOCOUPLE TC+0...
  • Page 84: Hardware Configuration

    8-Channel TC Input MTA 8.10 Hardware Configuration Neither the 8-Channel Thermocouple Module nor the MTA supports redundant operation. 8.10.1 Addresses Input address and process image should be set to the user preferences. Figure 8–3 8-Channel TC Input Hardware Configuration: Address Setup Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 85: Inputs - Part 1

    8-Channel TC Input MTA 8.10.2 Inputs – Part 1 Under the Inputs – Part 1 tab the Measuring Type field must be set to TC-EL (External Compensation) or deactivated. The other settings are user preferences. Figure 8–4 shows all the TC Measuring Ranges as Type J but they can be any type or mixed as described in the TC module manual.
  • Page 86: Inputs - Part 2

    8-Channel TC Input MTA 8.10.3 Inputs – Part 2 Figure 8–5 shows the Temperature Unit set to degrees Fahrenheit, but degrees Celsius is also possible. All settings should reflect user preferences. Figure 8–5 8-Channel TC Input Hardware Configuration: Inputs – Part 2 Parameters 8.11 Technical Specifications for 8-Channel TC Input Module (6ES7 331-7PF10-0AB0 &...
  • Page 87: 6-Channel F Analog Input Mta

    This section contains installation information and requirements for the Siemens Marshalled Termination Assembly (MTA) (6ES7650-1AH51-5XX0 or 6ES7650- 1AH50-5XX0), designed to interface with the Siemens ET 200M 6-Channel F Analog Input Module (6ES7 336-1HE00-0AB0, E-Stand 6 or higher). Note: The only major difference between the two part numbers is the housing.
  • Page 88: Operation

    6-Channel F Analog Input MTA Operation The Fail-Safe Analog Input MTA consists of the • Main board • Two diode boards • FET Switch Adapters The diode board marked 1 (MLFB 6ES7650-1BC51-0XX0 or 6ES7650-1BC50- 0XX0 ) uses 6.2 VDC zener diodes. The diode board marked 2 (MLFB 6ES7650- 1BB51-0XX0 or 6ES7650-1BB50-0XX0) uses 5.6 VDC zener diodes.
  • Page 89 6-Channel F Analog Input MTA For a non-redundant I/O module, the Ix- connects to the I/O module input via the diodes on Diode Board 1. The diodes on Diode Board 1 conduct the signal to the non-redundant module plugged into J2. In this case the diodes on board 2 are passive.
  • Page 90: Installation Requirements

    6-Channel F Analog Input MTA Figure 9–2 Non-Redundant FAI Interface FAI MTA 6.2 V CURRENT SOURCE FAI MODULE FET SWITCH BOARD FET SWITCH 5.6 V FET SWITCH MANA FET SWITCH Installation Requirements See Section 2, Installation, before performing any installation and observe all warnings A common interconnecting cable (6ES7922-3BD00-0AS0 or 6ES7922-3BJ00- 0AS0), supporting six analog input channels, interconnects the analog input...
  • Page 91: Maintenance

    6-Channel F Analog Input MTA Maintenance See Section 3, Maintenance, before performing any maintenance and observe all warnings Under normal operation, the A/B Power LED, the Module 1/2 Fuse LED, and all the Channel Fuse LEDs are on. If all are off, check the power supply to MTA. If the A/B Power LED is off, check the power supply to the MTA.
  • Page 92: 6-Channel F Analog Input Marshalled Termination Assembly

    6-Channel F Analog Input MTA 6-Channel F Analog Input Marshalled Termination Assembly Figure 9–3 shows the basic parts of the 6-Channel F Analog Input MTA. Figure 9–3 6-Channel F Analog Input Marshalled Termination Assembly (6ES7650-1AH51-5XX0 or 6ES7650-1AH50-5XX0) 24 CH5 SHIELD 23 CH5 I- 22 CH5 I+ 21 CH5 POWER...
  • Page 93 6-Channel F Analog Input MTA Key to numbered items in Figure 9–3: Item Description Input power connections Input power indicators Field wiring connections I/O module connections Shield disconnect jumper ( W100 & W101 ) Module power fuses Module power fuse indicators Channel power fuse ( 1 of 6 ) Channel power fuse indicator ( 1 of 6 ) Input isolation Jumper ( W200 )
  • Page 94: Technical Specifications

    0,205 – 2,08 mm sq. Power Supply Specifications See Module Specs Fuse Ratings Individual channel 1.5 A Fast blow (Littelfuse P/N: 273 01.5) (Siemens Spare P/N: A5E01568886) Module Power 0.5 A (Bussmann P/N: GMA-0.5A) (Siemens Spare P/N: A5E01568885) Indicators Input Power...
  • Page 95: Module Restrictions

    6-Channel F Analog Input MTA Note Fuses are available as spare parts from Siemens. Fuse information can be found at: http://www.littelfuse.com http://www.bussmann.com Note When using a 1.5A channel fuse it is possible that one or more of the zener diodes on the two Zener Diode Boards may be damaged in the event of a short circuit in the field.
  • Page 96: Typical Transmitter Connection To Field Terminals

    6-Channel F Analog Input MTA 9.10 Typical Transmitter Connection to Field Terminals Figure 9–4 Transmitter Connection to Field Terminals PWR0 PWR0 +Sig +Sig PWR1 PWR1 ISOLATED 2 WIRE 4 WIRE TRANSMITTER TRANSMITTER -Sig -Sig PWR0 +Sig PWR1 NON-ISOLATED 4 WIRE TRANSMITTER -Sig Marshalled Termination Assemblies for ET200M Remote I/O Modules...
  • Page 97: Hardware Configuration

    6-Channel F Analog Input MTA 9.11 Hardware Configuration Under normal operation the hardware configuration can be set up as shown in through Figure 9–8. Figure 9–5 9.11.1 Addresses shows redundant operation, in which the Process Image blocks should Figure 9–5 be changed from the default.
  • Page 98: Inputs - Part 1

    6-Channel F Analog Input MTA 9.11.2 Inputs – Part 1 Figure 9–6 shows the all the diagnostic boxes checked. The Measurement type can be either 2WMT, 4WMT, or Deactivated. Figure 9–6 6-Channel F Analog Input Hardware Configuration: Inputs – Part 1 Parameters Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 99: Inputs - Part 2

    6-Channel F Analog Input MTA 9.11.3 Inputs – Part 2 Figure 9–7 shows the Safety Mode option selected. Single sensor input is shown although two sensors can be chosen. The Monitoring Time may need to be adjusted. Figure 9–7 6-Channel F Analog Input Hardware Configuration: Inputs – Part 2 Parameters Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 100: Redundancy

    6-Channel F Analog Input MTA 9.11.4 Redundancy Figure 9–8 shows the redundant configuration. For non-redundant operation the Redundancy box should be set to None. Figure 9–8 6-Channel F Analog Input Hardware Configuration: Redundancy Setup 9.12 Technical Specifications for 6-Channel F Analog Input Module (6ES7 336-1HE00-0AB0) Note For a complete functional description and the most current technical specifications...
  • Page 101: Zener Diode Boards

    0XX0 ) and the 5.6 VDC (6ES7650-1BB51-0XX0 or 6ES7650-1BB50-0XX0) are used on the ET200M Marshalled Termination Assembly (MTA) (6ES7650-1AH51- 5XX0 or 6ES7650-1AH50-5XX0) designed to interface with the Siemens ET 200M 6-Channel F Analog Input Module (6ES7 336-1HE00-0AB0, E-Stand 4 or higher).
  • Page 102 6-Channel F Analog Input MTA Figure 9–9 Diode Board Interfaces 6ES7 650-1AH50-5XX0 PWR0 CHANNEL FUSE CHANNEL 2 WIRE POWER TRANSMITTER MODULE A HART+ I0R+ DISCONNECT I0R+ ZENER 1 6.2 V DIODE BOARD MANA W200 ISOLATION MODULE B I0R+ ZENER 1 I0R+ 5.6 V DIODE...
  • Page 103: Installation Requirements

    6-Channel F Analog Input MTA 9.13.3 Installation Requirements See Section 2, Installation, before performing any installation and observe all warnings The 6.2 VDC Zener Diode Board, marked 1 is plugged into J100 and J101 on the FAI MTA. It is mechanically held down by two captive screws and standoffs. See Figure 9–11.
  • Page 104: Diode Board Assembly

    6-Channel F Analog Input MTA 9.14 Diode Board Assembly The two figures below show the basic parts of the diode boards. Figure 9–11 6.2V Diode Board Assembly 6ES7650-1BC50-0XX0 Key to numbered items in Figure 9–11: Item Description 6.2V Zener Diode ( 1 of 6 ) Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 105 6-Channel F Analog Input MTA Figure 9–12 5.6V Diode Board Assembly 6ES7650-1BB50-0XX0 Key to numbered items in Figure 9–12: Item Description 5.6V Zener Diode ( 1 of 6 ) Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 106: Fet Switch Adapter

    FET Switch Adapter. The FET Switch Adapter (6ES7650-1BD51-0XX0 or 6ES7650-1BD50-0XX0) is used on the ET200M Marshalled Termination Assembly (MTA) (6ES7650-1AH51-5XX0 or 6ES7650-1AH50-5XX0), which interfaces with the Siemens ET 200M 6-Channel F Analog Input Module (6ES7 336-1HE00-0AB0, E-Stand 4 or higher). Note: The two part numbers are interchangeable.
  • Page 107: Maintenance

    6-Channel F Analog Input MTA 9.15.4 Maintenance See Section 3, Maintenance, before performing any maintenance and observe all warnings Under normal operation the switches in the FET Switch Adapter are energized and will conduct the input signal from the MTA to the FAI module input circuitry. Periodic maintenance of the FAI modules requires that the FET Switch Adapter operate correctly, so it should be tested when the FAI module is removed from service.
  • Page 108 6-Channel F Analog Input MTA Figure 9–14 FET Switch Adapter FET ON Test Setup 6ES7 650-1AH50-5XX0 PWR0 CHANNEL FUSE 24VDC SW1 shown in "OFF" position POWER SUPPLY FET SWITCH shown in "OFF" position FET Switch CHANNEL Board 1 1000 Ohms 1 Watt POWER MODULE A HART+...
  • Page 109 6-Channel F Analog Input MTA Figure 9–15 FET Switch Adapter FET OFF Test Setup 6ES7 650-1AH50-5XX0 PWR0 CHANNEL FUSE 24VDC SW1 shown in "OFF" position POWER FET SWITCH shown in "OFF" SUPPLY 1000 Ohms 1 Watt position FET Switch CHANNEL Board 1 POWER MODULE A...
  • Page 110: Technical Specifications

    6-Channel F Analog Input MTA Figure 9–16 FET Switch Adapter Assembly (MALE DB50) (FEMALE DB50) 9.15.5 Technical Specifications Technical Specifications for FET Switch Adapter (6ES7650-1BD51-0XX0 or 6ES7650-1BD50-0XX0) Dimensions L x W x D – inches 2.5 x 2.75 x 0.75 L x W x D –...
  • Page 111: Input Sharing

    Failsafe Analog Input module (6ES7 336-1HE00-0AB0, E-Stand 4 or higher) and a Standard Analog Input Module (6ES7 331-7NF00-0AB0, E-Stand 5 or higher), using the Siemens FAI Marshalled Termination Assembly (MTA) (6ES7650- 1AH51-5XX0 or 6ES7650-1AH50-5XX0) and the Siemens AI Marshalled Termination Assembly (MTA) (6ES7650-1AA51-2XX0 or 6ES7650-1AA50-2XX0).
  • Page 112: Fai Mta To Sai Mta Cable

    6-Channel F Analog Input MTA 9.16.4 FAI MTA to SAI MTA Cable The FAI MTA to SAI MTA Input Sharing cable uses only 13 conductors. The FAI Channel 0 to Channel 5 input signals have been mapped to Channels 0 through 5 on the SAI MTA.
  • Page 113 6-Channel F Analog Input MTA Figure 9–17 FAI MTA to SAI MTA Interconnecting Cable Key to numbered items in Figure 9–17: Item Part Name 50-PIN FEMALE sub-D connector Wires with crimped pins Figure 9–18 FAI SAI Input Sharing FAI MTA SAI MTA SAI MODULE CH IN...
  • Page 114: Hardware Configuration

    6-Channel F Analog Input MTA 9.16.5 Hardware Configuration FAI: Redundancy not supported. The HW configuration should be setup for Non- redundant operation. See section 9.11. SAI: The SAI MTA supports redundancy for the Standard Modules and redundant modules can be used, as selected by the user. See section 4.10. Addresses FAI: Input address and process image should be set to the user preferences.
  • Page 115 6-Channel F Analog Input MTA Figure 9–19 SAI 8-Channel Analog Input Hardware Configuration: Inputs Sharing Configuration Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 116 6-Channel F Analog Input MTA Redundancy FAI: Redundancy not supported. The HW configuration should be setup for non- redundant operation. See section 9.11. SAI: The SAI MTA supports redundant and non-redundant operation. See section 4.10. Figure 9–20 shows a non-redundant SAI configuration. Figure 9–20 SAI 8-Channel Analog Input Hardware Configuration for Non-redundant Operation Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 117: 10 6-Channel F Analog Input Hart Mta

    10.1 Description This section contains installation information and requirements for the Siemens Marshalled Termination Assembly (MTA) (6ES7650-1AH61-5XX0) designed to interface with the Siemens ET 200M 6-Channel F Analog Input HART Module (6ES7 336-4GE00-0AB0). 10.2 Features The following features have been incorporated into this MTA: •...
  • Page 118: Operation

    6-Channel F Analog Input HART MTA 10.3 Operation The Fail-Safe Analog Input HART (FAIH) MTA consists of the • Main board • Two diode boards The diode board marked 1 (MLFB 6ES7650-1BC51-0XX0 or 6ES7650-1BC50- 0XX0 ) uses 6.2 VDC zener diodes. The diode board marked 2 (MLFB 6ES7650- 1BB51-0XX0 or 6ES7650-1BB50-0XX0) uses 5.6 VDC zener diodes.
  • Page 119 6-Channel F Analog Input HART MTA Figure 10–1 Redundant FAIH Interface FAIH MTA FAI MODULE A 6.2 V CURRENT SOURCE MANA FAI MODULE B 5.6 V MANA Figure 10–2 Non-Redundant FAI Interface FAIH MTA 6.2 V CURRENT SOURCE FAI MODULE 5.6 V MANA Marshalled Termination Assemblies for ET200M Remote I/O Modules...
  • Page 120: Installation Requirements

    6-Channel F Analog Input HART MTA 10.4 Installation Requirements See Section 2, Installation, before performing any installation and observe all warnings A common interconnecting cable (6ES7922-3BD00-0AU0 or 6ES7922-3BJ00- 0AU0), supporting six analog input channels, interconnects the analog input termination assembly to the 6-channel analog input module (6ES7 336-4GE00- 0AB0).
  • Page 121: 6-Channel F Analog Input Hart Marshalled Termination Assembly

    6-Channel F Analog Input HART MTA 10.6 6-Channel F Analog Input HART Marshalled Termination Assembly Figure 10–3 shows the basic parts of the 6-Channel F Analog Input HART MTA. Figure 10–3 6-Channel F Analog Input HART Marshalled Termination Assembly (6ES7650-1AH61-5XX0) 24 CH5 SHIELD 23 CH5 I- 22 CH5 I+...
  • Page 122 6-Channel F Analog Input HART MTA Key to numbered items in Figure 10–3: Item Description Input power connections Input power indicators Field wiring connections I/O module connections Shield disconnect jumper ( W100 & W101 ) Module power fuses Module power fuse indicators Channel power fuse ( 1 of 6 ) Channel power fuse indicator ( 1 of 6 ) Input isolation Jumper ( W200 )
  • Page 123: Technical Specifications

    See Module Specs Fuse Ratings Individual channel - Normal 0.1 A Fast blow (Littelfuse P/N: 273.100) (Siemens Spare P/N: A5E01568889) Individual channel – Optional - Recommended for 1.5 A Fast blow (Littelfuse P/N: 273 01.5) 4 wire transmitters (Siemens Spare P/N: A5E01568886) Module Power 0.5 A (Bussmann P/N: GMA-0.5A)
  • Page 124: Changes To The Technical Specifications For 6-Channel F Analog Input Hart Module (6Es7 336-4Ge00-0Ab0)

    It is recommended that the diode boards be tested or replaced in the event a 1.5A channel fuse opens. Note Fuses are available as spare parts from Siemens. Fuse information can be found at: http://www.littelfuse.com http://www.bussmann.com 10.8...
  • Page 125: Typical Transmitter Connection To Field Terminals

    6-Channel F Analog Input HART MTA 10.9 Typical Transmitter Connection to Field Terminals Figure 10–4 Transmitter Connection to Field Terminals PWR0 PWR0 +Sig +Sig PWR1 PWR1 ISOLATED 2 WIRE 4 WIRE TRANSMITTER TRANSMITTER -Sig -Sig PWR0 +Sig PWR1 NON-ISOLATED 4 WIRE TRANSMITTER -Sig 10.10...
  • Page 126: Zener Diode Boards

    0XX0 ) and the 5.6 VDC (6ES7650-1BB51-0XX0 or 6ES7650-1BB50-0XX0) are used on the ET200M Marshalled Termination Assembly (MTA) (6ES7650-1AH51- 5XX0 or 6ES7650-1AH50-5XX0) designed to interface with the Siemens ET 200M 6-Channel F Analog Input HART Module (6ES7 336-4GE00-0AB0). Note: The two part numbers for the 5.6 V Diode Board are interchangeable. The two part numbers for the 6.2 V Diode Board are also interchangeable.
  • Page 127 6-Channel F Analog Input HART MTA Figure 10–5 Diode Board Interfaces 6ES7 650-1AH61-5XX0 PWR0 CHANNEL FUSE CHANNEL 2 WIRE POWER TRANSMITTER MODULE A HART+ I0R+ DISCONNECT I0R- ZENER 1 W200 6.2 V ISOLATION DIODE BOARD MANA MODULE B I0R+ I0R- ZENER 1 5.6 V HART-...
  • Page 128: Installation Requirements

    6-Channel F Analog Input HART MTA 10.12.3 Installation Requirements See Section 2, Installation, before performing any installation and observe all warnings The 6.2 VDC Zener Diode Board, marked 1 is plugged into J100 and J101 on the FAI MTA. It is mechanically held down by two captive screws and standoffs. See Figure 10–7.
  • Page 129 6-Channel F Analog Input HART MTA Figure 10–6 5.6V Diode Board Test Setup ZENER DIODE BOARD TEST SETUP 6ES7 650-1AH61-5XX0 PWR0 CHANNEL FUSE FIELD TERMINAL CONNECTIONS 24VDC POWER 1K RESISTOR VOLTMETER SUPPLY CHANNEL FROM FROM CH 0 PWR0 CHANNEL 1000 Ohms 1 Watt POWER CH 1 PWR1...
  • Page 130: Diode Board Assembly

    6-Channel F Analog Input HART MTA 10.13 Diode Board Assembly The two figures below show the basic parts of the diode boards. Figure 10–7 6.2V Diode Board Assembly 6ES7650-1BC51-0XX0 Key to numbered items in Figure 10–7: Item Description 6.2V Zener Diode (1 of 6) Screw Flat washer Lock Washer...
  • Page 131 6-Channel F Analog Input HART MTA Figure 10–8 5.6V Diode Board Assembly 6ES7650-1BB51-0XX0 Key to numbered items in Figure 10–8: Item Description 5.6V Zener Diode ( 1 of 6 ) Screw Flat washer Lock Washer Standoff Retaining Washer Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 132: Input Sharing

    This section contains information and requirements for input sharing between a Failsafe Analog Input module (6ES7 336-4GE00-0AB0) and a Standard Analog Input Module (6ES7 331-7NF00-0AB0, E-Stand 5 or higher), using the Siemens FAIH Marshalled Termination Assembly (MTA) (6ES7650-1AH61-5XX0 and the Siemens AI Marshalled Termination Assembly (MTA) (6ES7650-1AA51-2XX0 or 6ES7650-1AA50-2XX0).
  • Page 133: Operation

    6-Channel F Analog Input HART MTA 10.14.3 Operation The signal source is connected to the FAIH MTA in the normal manner. The cable plugged into J1 is wired from IxR+ to Ix+ on TBy of the Standard Analog Input (SAI) MTA (6ES7650-1AA51-2XX0 or 6ES7650-1AA50-2XX0) and the Ix- pin to Ix- on TBy of the SAI MTA.
  • Page 134 6-Channel F Analog Input HART MTA Figure 10–10 FAIH MTA to SAI MTA Interconnecting Cable Key to numbered items in Figure 10–10: Item Part Name 50-PIN FEMALE sub-D connector Wires with crimped pins Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 135: Hardware Configuration

    6-Channel F Analog Input HART MTA 10.14.5 Hardware Configuration FAI: Redundancy not supported. The HW configuration should be setup for Non- redundant operation. SAI: The SAI MTA supports redundancy for the Standard Modules and redundant modules can be used, as selected by the user. See section 4.10. Addresses FAI: Input address and process image should be set to the user preferences.
  • Page 137: 11 6-Channel F Analog Input Hart Mta

    11.1 Description This section contains installation information and requirements for the Siemens Marshalled Termination Assembly (MTA) (6ES7650-1AH62-5XX0) designed to interface with the Siemens ET 200M 6-Channel F Analog Input HART Module (6ES7336-4GE00-0AB0). 11.2 Features The following features have been incorporated into this MTA: •...
  • Page 138: Operation

    6-Channel F Analog Input HART MTA 11.4 Operation Power is supplied via the two power connectors which are marked L/A+, M/A, and L/B+, M/B. Each has a green LED to indicate the presence of voltage over 15 VDC. The case of polarity reversal of the power supply is indicated by the LEDs illuminating red.
  • Page 139 6-Channel F Analog Input HART MTA Figure 11–1 Redundant FAIH Interface L/A+ L/B+ MTA - FAIH 2-wire 2 wire transducer supply FAIH MODULE 1 150 Ohm 6.2 V 4 wire transducer/ current source FAIH MODULE 2 150 Ohm 5.6 V Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 140 6-Channel F Analog Input HART MTA Figure 11–2 Non-Redundant FAI Interface L/A+ L/B+ 2-wire 2 wire supply transducer 6.2 V 4 wire transducer/ current source FAIH MODULE 150 Ohm 5.6 V Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 141: Installation Requirements

    6-Channel F Analog Input HART MTA 11.5 Installation Requirements See Section Installation, before performing any installation and observe all warnings. A common interconnecting cable (6ES7922-3BD00-0AU0 or 6ES7922-3BJ00- 0AU0), supporting six analog input channels, interconnects the analog input termination assembly to the 6-channel analog input module (6ES7336-4GE00-0AB0).
  • Page 142: Maintenance For 2-Wire Transducer Supply

    6-Channel F Analog Input HART MTA 11.6.1 Maintenance for 2-wire transducer supply The power supply for 2-wire transducer is individually short circuit proofed for each channel. In case of a external short circuit, provided by a faulty wiring, the current is limited up to 40 mA.
  • Page 143 6-Channel F Analog Input HART MTA Figure 11–3 2-wire transducer supply test setup MTA - FAIH 2-wire supply 2-wire Power supply transducer FAIH MODULE 1 150 Ohm 6.2 V FAIH MODULE 2 150 Ohm 5.6 V Current indicator The correct function of the 2-wire transducer supply can be checked without modifying the wiring.
  • Page 144: 6-Channel F Analog Input Hart Marshalled Termination Assembly

    6-Channel F Analog Input HART MTA 11.6.2 6-Channel F Analog Input HART Marshalled Termination Assembly Figure 10–3 shows the basic parts of the 6-Channel F Analog Input HART MTA. Figure 11–4 6-Channel F Analog Input HART Marshalled Termination Assembly (6ES7650-1AH62-5XX0) Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 145 6-Channel F Analog Input HART MTA Key to numbered items in Figure 10–3: Item Description Input power connections (L/A+, M/A, L/B+, M/B) Input power indicators (A POWER, B POWER) Field wiring connections Output Power Monitor System (1, 2) Shield disconnect jumper ( X100, X101 ) Module power fuses (MODULE 1, MODULE 2) Module power fuse indicators Input isolation Jumper ( X300 )
  • Page 146: Technical Specifications

    < 0.5 A channels 20 mA) Power Dissipation (typical) Fuse Ratings Module Power 0.5 A (Bussmann P/N: GMA-0.5A) (Siemens Spare P/N: A5E01568885) Power output for 2-wire transducer supply Supply current for each channel typ. 20 mA Short circuit current max. 40 mA Load capability >...
  • Page 147: Changes To The Technical Specifications For 6-Channel F Analog Input Hart Module (6Es7 336-4Ge00-0Ab0)

    High Demand (PFH) according to SIL 3 < 1,9 E-9 1/h (per channel) Proof-test interval 20 years Note Fuses are available as spare parts from Siemens. Fuse information can be found at: http://www.littelfuse.com http://www.bussmann.com 11.8 Changes to the Technical Specifications for 6-Channel...
  • Page 148: Typical Transmitter Connection To Field Terminals

    6-Channel F Analog Input HART MTA 11.9 Typical Transmitter Connection to Field Terminals Figure 11–5 Transmitter Connection to Field Terminals + Sig Isolated 2 wire + Sig 4 wire transducer transducer - Sig - Sig Non- Isolated + Sig 4 wire transducer - Sig Marshalled Termination Assemblies for ET200M Remote I/O Modules...
  • Page 149: Hardware Configuration

    6-Channel F Analog Input HART MTA Hardware Configuration For hardware configuration refer to the manual S7-300 Automation System Fail- Safe Signal Modules (document number A5E00085586). 11.10 Technical Specifications for 6-Channel F ANALOG INPUT HART Module (6ES7 336-4GE00-0AB0) Note For a complete functional description and the most current technical specifications for this module, refer to the manual S7-300 Automation System Fail-Safe Signal Modules (document number A5E00085586).
  • Page 150: Input Sharing

    Failsafe Analog Input module (6ES7 336-4GE00-0AB0) and a Standard Analog Input Module (6ES7 331-7NF00-0AB0, E-Stand 5 and higher or 6ES7 331-7NF10- 0AB0, E-Stand 8 or higher), using the Siemens FAIH Marshalled Termination Assembly (MTA) (6ES7650-1AH62-5XX0 and the Siemens AI Marshalled Termination Assembly (MTA) (6ES7650-1AA52-2XX0).
  • Page 151: Operation

    6-Channel F Analog Input HART MTA 11.11.3 Operation The signal source is connected to the FAIH MTA in the normal manner. The cable plugged into the connector MODULE 1 is wired from IxR+ to Ix+ and Ix- to Ix- on field connections of the Standard Analog Input MTA-AI8 (6ES7650-1AA52-2XX0).
  • Page 152 6-Channel F Analog Input HART MTA Figure 11–7 FAIH MTA to SAI MTA Interconnecting Cable Key to numbered items in Figure 10–10: Item Part Name 50-PIN FEMALE sub-D connector Wires with crimped pins Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 153: Hardware Configuration

    6-Channel F Analog Input HART MTA 11.11.5 Hardware Configuration FAI: Redundancy not supported. The HW configuration should be setup for Non- redundant operation. SAI: The SAI MTA supports redundancy for the Standard Modules and redundant modules can be used, as selected by the user. See section 4.10. Addresses FAI: Input address and process image should be set to the user preferences.
  • Page 154 6-Channel F Analog Input HART MTA Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 155 6-Channel F Analog Input HART MTA Redundancy FAI: Redundancy not supported. The HW configuration should be setup for non- redundant operation. SAI: The SAI MTA supports redundant and non-redundant operation. See section 4.10. Figure 11–9 SAI 8-Channel Analog Input Hardware Configuration for Non-redundant Operation Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 156: 16-Channel, 24 Vdc Discrete Input Mta

    This section contains information and requirements for Siemens Marshalled Termination Assembly (MTA) (6ES7650-1AC11-3XX0 or 6ES7650-1AC10-3XX0), designed to interface with the Siemens ET 200M 16-Channel, 24 VDC Discrete Input Module (6ES7 321-7BH01-0AB0, E-Stand 2 or higher) Note: The only major difference between the two part numbers is the housing.
  • Page 157: Operation

    16-Channel, 24 VDC Discrete Input MTA 12.3 Operation Power is supplied via the two removable power connectors which are retained by screws and marked L+A, MA, and L+B, MB. Each has a LED to indicate the presence of voltage over 15 VDC. The LEDs are marked A POWER and B POWER.
  • Page 158: 16-Channel, 24 Vdc Discrete Input Marshalled Termination Assembly

    16-Channel, 24 VDC Discrete Input MTA 12.6 16-Channel, 24 VDC Discrete Input Marshalled Termination Assembly Figure 12–1 shows the basic parts of the 16-Channel, 24 VDC Discrete Input MTA. Figure 12–1 16-Channel, 24 VDC Discrete Input Marshalled Termination Assembly (6ES7650-1AC11-3XX0 or 6ES7650-1AC10-3XX0) 2.24 CH15 SHIELD 2.23 CH15- 2.22 CH15+...
  • Page 159: Technical Specifications

    Humidity 5% to 95% Non-condensing Approvals MTA Agency Approvals See Preface section, Approvals Table Note Fuses are available as spare parts from Siemens. Fuse information can be found at: http://www.littelfuse.com http://www.bussmann.com Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 160: Module Restrictions

    16-Channel, 24 VDC Discrete Input MTA 12.8 Module Restrictions Restrictions for 16-Channel, 24 VDC Discrete Input MTA (6ES7650-1AC11-3XX0 or 6ES7650-1AC10-3XX0) I/O Module Restrictions MTA Design: Module Vs not used Cross circuit between channels of a channel group - not detected MTA Design: Module Vs not used Cross circuit between channels in different channel groups - not detected...
  • Page 161: Typical Transmitter Connection To Field Terminals

    16-Channel, 24 VDC Discrete Input MTA 12.9 Typical Transmitter Connection to Field Terminals Figure 12–2 16 Channel DI MTA Field Terminal Connection to Transmitter 16 CHANNEL DI MTA CH0+ CH0- CH1+ INPUT SWITCH CH1- CH2+ CH2- 2 WIRE TRANSMITTER CH3+ CH3- CH12+ CH12-...
  • Page 162: Hardware Configuration

    16-Channel, 24 VDC Discrete Input MTA 12.10 Hardware Configuration The 16 channel Standard Discrete Input Module and its MTA support Redundant and Non-redundant operation. 12.10.1 Addresses Non-redundant Operation The choice of the Input Address and Process Image are left to the user. Redundant Operation Process Image should be set to something other than the default.
  • Page 163: Inputs

    16-Channel, 24 VDC Discrete Input MTA 12.10.2 Inputs The inputs of the SDI module are capable of wire break detection if a resistor is wired in parallel with the sensor, the resistor should be located near the sensor. See Figure 12–4. The Wire Break option must be checked for each channel that will use this feature.
  • Page 164: Time-Of-Day Stamp

    16-Channel, 24 VDC Discrete Input MTA 12.10.3 Time-of-Day Stamp All of these options should be set to user preferences. Figure 12–5 16-Channel Discrete Input Hardware Configuration: Time-of-Day Stamp Options Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 165: Redundancy

    16-Channel, 24 VDC Discrete Input MTA 12.10.4 Redundancy Figure 12–6 shows a redundant SDI configuration. Figure 12–6 16-Channel Discrete Input Hardware Configuration: Redundancy Selection 12.11 Technical Specifications for 16-Channel, 24 VDC Discrete Input Module (6ES7 321-7BH01-0AB0) Note For a complete functional description and the most current technical specifications for this module, refer to the manual S7-300 Programmable Controller Module Specifications (document number A5E00105505).
  • Page 167: 12/24-Channel, 24 Vdc F Discrete Input Mta

    This section contains information and requirements to facilitate installation of Siemens Marshalled Termination Assembly (MTA) (6ES7650-1AK11-7XX0 or 6ES7650-1AK10-7XX0), designed to interface with the Siemens ET 200M 12/24- Channel, 24 VDC F Discrete Input module (6ES7 326-1BK02-0AB0, E-Stand 1 or higher).
  • Page 168: Operation

    12/24-Channel, 24 VDC F Discrete Input MTA 13.3 Operation Power is supplied via the two removable power connectors which are retained by screws and marked L+A, MA, and L+B, MB. Each has a LED to indicate the presence of voltage over 15 VDC. The LEDs are marked A POWER and B POWER.
  • Page 169: Simplified Diagram

    12/24-Channel, 24 VDC F Discrete Input MTA check the power supply to the MTA. If the Module 1/2 Fuse LED is off, check the channel fuse and replace as necessary. 13.6 Simplified diagram Figure 13–1 12/24-Channel, 24 VDC F Discrete Input Marshalled Termination Assembly (6ES7650- 1AK11-7XX0 or 6ES7650-1AK10-7XX0) Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 170 12/24-Channel, 24 VDC F Discrete Input MTA L/A+ L/B+ DI11 Module 1 CHx+ DI12 CHx- DI23 Module 2 DI12 MTA – DO16 DI23 Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 171: 12/24-Channel, 24 Vdc F Discrete Input Marshalled Termination Assembly

    12/24-Channel, 24 VDC F Discrete Input MTA 13.7 12/24-Channel, 24 VDC F Discrete Input Marshalled Termination Assembly The figure below shows the basic parts of the 12/24-Channel, 24 VDC F Discrete Input MTA. Figure 13-2 12/24-Channel, 24 VDC F Discrete Input Marshalled Termination Assembly (6ES7650-1AK11- 7XX0 or 6ES7650-1AK10-7XX0) F Discrete Input 6ES7650-1AK11-7XX0...
  • Page 172: Technical Specifications

    0,205 – 2,08 mm sq. Power Supply Specifications See Module Specs Fuse Ratings Individual channel 0.05 A (Littelfuse P/N: 273.050) (Siemens Spare P/N: A5E01568887) Module Power 1.0 A (Bussmann P/N: GMA-1.0A) (Siemens Spare P/N: A5E01568882) Indicators Input Power Green LED on when input power available...
  • Page 173: Technical Specifications

    0,205 – 2,08 mm sq. Power Supply Specifications See Module Specs Fuse Ratings Individual channel 0.05 A (Littelfuse P/N: 273.050) (Siemens Spare P/N: A5E01568887) Module Power 2.0 A (Bussmann P/N: GMA-1.0A) (Siemens Spare P/N: A5E01568882) Indicators Marshalled Termination Assemblies for ET200M Remote I/O Modules...
  • Page 174: Module Restrictions

    0 1/h (no dangerous undetected failures for DI MTA) (per channel) Proof-test time 20 years Note Fuses are available as spare parts from Siemens. Fuse information can be found at: http://www.littelfuse.com http://www.bussmann.com 13.10 Module Restrictions Restrictions for 12/24-Channel, 24 VDC F Discrete Input MTA...
  • Page 175 12/24-Channel, 24 VDC F Discrete Input MTA Restrictions for 12/24-Channel, 24 VDC F Discrete Input MTA (6ES7650-1AK11-7XX0 or 6ES7650-1AK10-7XX0) MTA Design: Module Vs not used Cross circuit between channels of a channel group - not detected MTA Design: Module Vs not used Cross circuit between channels in different channel groups - not detected MTA Design: Module Vs not used...
  • Page 176: Typical Transmitter Connection To Field Terminals

    12/24-Channel, 24 VDC F Discrete Input MTA 13.11 Typical Transmitter Connection to Field Terminals Figure 13–3 Field Terminal Connections for 12/24-Channel, 24 VDC F Discrete Input MTA CH0+ CH0- CH1+ INPUT SWITCH CH1- 2 WIRE TRANSMITTER Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 177: Hardware Configuration

    12/24-Channel, 24 VDC F Discrete Input MTA 13.12 Hardware Configuration The 12/24 channel Fail-Safe Discrete Input Module and its MTA support Redundant and Non-redundant operation. 13.12.1 Addresses Non-redundant Operation The choice of the Input Address and Process Image are left to the user. Redundant Operation Process Image should be set to something other than the default.
  • Page 178: Parameters

    12/24-Channel, 24 VDC F Discrete Input MTA 13.12.2 Parameters The Parameters tab of the FDI Hardware Configuration has many options that can be set by the user. The Operating mode should be set to the user preference: Standard operation or Safety mode.
  • Page 179: Module Parameters

    12/24-Channel, 24 VDC F Discrete Input MTA 13.12.3 Module Parameters Because of the MTA design some parameters must be set manually. Encoder supply The Encoder supply via module boxes for both Supply group Vs1/Vs3 and Supply group Vs2/Vs4 must NOT be checked because the sensor does not use the VS from the module as a power supply.
  • Page 180 12/24-Channel, 24 VDC F Discrete Input MTA Time-of-day Stamp All of these options should be set to the user preferences, as shown in Figure 13–. Figure 13–7 12/24-Channel Fail-Safe Discrete Input Hardware Configuration: Parameters Time-of Day Stamp Settings Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 181: Redundancy

    12/24-Channel, 24 VDC F Discrete Input MTA 13.12.4 Redundancy All of these options should be set to the user preferences. Figure 13–shows a redundant FDI configuration. Figure 13–8 12/24-Channel Fail-Safe Discrete Input Hardware Configuration: Redundancy Settings Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 182: Technical Specifications For 12/24-Channel, 24 Vdc F Discrete Input Module

    12/24-Channel, 24 VDC F Discrete Input MTA 13.13 Technical Specifications for 12/24-Channel, 24 VDC F Discrete Input Module (6ES7 326-1BK00-0AB0 or 6ES7 326-1BK01-0AB0 or 6ES7 326-1BK02-0AB0) Note For a complete functional description and the most current technical specifications for this module, refer to the manual S7-300 Automation System Fail-Safe Signal Modules (document number A5E00085586).
  • Page 183: 10-Channel, 24 Vdc F Discrete Output Mta

    This section contains information and requirements to facilitate installation of Siemens Marshalled Termination Assembly (MTA) (6ES7650-1AL11-6XX0 or 6ES7650-1AL10-6XX0), designed to interface with the Siemens ET 200M 10- Channel, 24 VDC F Discrete Output module (6ES7 326-2BF10-0AB0, E-Stand 3 or higher).
  • Page 184: Operation

    Non-redundant systems have one module connected to either J1 or J2. Connection from the MTA to the I/O Module is accomplished with a 40 pin Siemens connector wired to a D25 female connector. This cable has larger wires than the other cables because of the higher current capabilities of the module.
  • Page 185: Maintenance

    10-Channel, 24 VDC F Discrete Output MTA 14.5 Maintenance See Section 3, Maintenance, before performing any maintenance and observe all warnings Under normal operation, the A/B Power LED and the Module 1/2 Fuse LED are on. If all are off, check the power supply to MTA. If the A/B Power LED is off, check the power supply to the MTA.
  • Page 186: Simplified Diagram

    10-Channel, 24 VDC F Discrete Output MTA 14.6 Simplified diagram Figure 14–1 12/24-Channel, 24 VDC F Discrete Output Marshalled Termination Assembly (6ES7650- 1AL11-6XX0 or 6ES7650-1AL10-6XX0) L/A+ L/B+ DO10 Module 1 Chx+ Load Chx- DO10 Module 2 MTA – FDO Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 187: 10-Channel, 24 Vdc F Discrete Output Marshalled Termination Assembly

    10-Channel, 24 VDC F Discrete Output MTA 14.7 10-Channel, 24 VDC F Discrete Output Marshalled Termination Assembly Figure 14–2 10-Channel, 24 VDC F Discrete Output Marshalled Termination Assembly (6ES7650-1AL11- 6XX0 or 6ES7650-1AL10-6XX0) 2.15 CH9 SHIELD 2.14 CH9- 2.13 CH9+ 2.12 CH7 SHIELD 2.11 CH7- 2.10 CH7+ 2.9 CH5 SHIELD...
  • Page 188: Technical Specifications

    Power Supply Specifications See Module Specs Fuse Ratings Individual channel – Normal 1.0 A (Littelfuse P/N: 273 001) (Siemens Spare P/N: A5E01568884) Individual channel – Optional 3.0 A (Littelfuse P/N: 273 003) Module Power 10 A (Schurter P/N: 0034.1526) (Siemens Spare P/N: A5E01574409)
  • Page 189: Technical Specifications

    Power Supply Specifications See Module Specs Fuse Ratings Individual channel – Normal 1.0 A (Littelfuse P/N: 273 001) (Siemens Spare P/N: A5E01568884) Individual channel – Optional 3.0 A (Littelfuse P/N: 273 003) Module Power 10 A (Schurter P/N: 0034.1526) (Siemens Spare P/N: A5E01574409)
  • Page 190: Module Restrictions

    50 °C Horizontal 60 °C 70 °C Vertical 60 °C Note Fuses are available as spare parts from Siemens. Fuse information can be found at: http://www.littelfuse.com http://www.schurter.com 14.10 Module Restrictions Restrictions for 10-Channel, 24 VDC F Discrete Output MTA (6ES7650-1AL11-6XX0 or 6ES7650-1AL10-6XX0)
  • Page 191 10-Channel, 24 VDC F Discrete Output MTA Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 192: Typical Load Connection To Field Terminals

    10-Channel, 24 VDC F Discrete Output MTA 14.11 Typical Load Connection to Field Terminals Figure 14–3 Load Connection to Field Terminals of 10-Channel, 24 VDC F Discrete Output CH0+ CH0- 24 VDC CH1+ LOAD CH1- 14.12 Hardware Configuration The 10 channel Fail-Safe Discrete Output Module and its MTA support Redundant and Non-redundant operation.
  • Page 193 10-Channel, 24 VDC F Discrete Output MTA Figure 14–4 10-Channel Fail-Safe Discrete Output Hardware Configuration: Addresses for Redundant Operation Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 194: Outputs

    10-Channel, 24 VDC F Discrete Output MTA 14.12.2 Outputs The FDO MTA uses the series diode outputs from the FDO module for both redundant and non-redundant operation. This determines which diagnostics are generated. More information about these effects can be found in the I/O Restrictions section of the Technical Specifications table and the module specifications.
  • Page 195: Redundancy

    10-Channel, 24 VDC F Discrete Output MTA 14.12.3 Redundancy Figure 14– shows a redundant FDO configuration. Figure 14–6 10-Channel Fail-Safe Discrete Output Hardware Configuration: Redundancy Selections 14.13 Technical Specifications for 10-Channel, 24 VDC F Discrete Output Module (6ES7 326-2BF10-0AB0) Note For a complete functional description and the most current technical specifications for this module, refer to the manual S7-300 Automation System Fail-Safe Signal Modules (document number A5E00085586).
  • Page 197: 16-Channel, 24 Vdc Discrete Output Mta

    15.1 Description This section contains information and requirements to facilitate installation of Siemens Marshalled Termination Assembly (MTA) (6ES7650-1AD10-2XX0), designed to interface with the Siemens ET 200M 16-Channel, 24 VDC Discrete Output module (6ES7 322-8BH01-0AB0, E-Stand 1 or higher). 15.2 Features The following features have been incorporated into this MTA: •...
  • Page 198: Operation

    MTA. The MTA uses the channel outputs without series diodes from the I/O module. Connection from the MTA to the I/O Module is accomplished with a 40 pin Siemens connector wired to a D25 male connector.
  • Page 199: Maintenance

    16-Channel, 24 VDC Discrete Output MTA 15.6 Maintenance See Section 3, Maintenance, before performing any maintenance and observe all warnings Under normal operation, the A/B Power LEDs and the Module 1/2 Fuse LEDs are on. If an A/B Power LED is off, check the power supply to the MTA. If a Module 1/2 Fuse LED is off, check and replace the module fuse.
  • Page 200: Technical Specifications

    All outputs OFF 0.26 A maximum Power Dissipation (typical) 10 W Fuse Ratings 10 A/125V (Bussmann P/N: GMA-10A) Module (Siemens Spare P/N: A5E01568881) or (Schurter P/N: 0034.1526) (Siemens Spare P/N: A5E01574409) Environmental Ambient Temperature -25C to +60C Humidity 5% to 95% Non-condensing...
  • Page 201 16-Channel, 24 VDC Discrete Output MTA Note Fuses are available as spare parts from Siemens. Fuse information can be found at: http://www.bussmann.com http://www.schurterinc.com Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 202: Changes To 16-Channel, 24 Vdc Discrete Output Module (6Es7 322-8Bh01-0Ab0) Specifications

    16-Channel, 24 VDC Discrete Output MTA 15.9 Changes to 16-Channel, 24 VDC Discrete Output Module (6ES7 322-8BH01-0AB0) Specifications This section contains changes to the I/O module specifications when it is used with the MTA. Changes to 16-Channel, 24 VDC Discrete Output Module (6ES7 322-8BH01-0AB0) Specifications when used with 16-Channel, 24 VDC Discrete Output MTA (6ES7650-1AD10- 2XX0) Isolation between groups of 4 channels...
  • Page 203: Technical Specifications For 16-Channel, 24 Vdc Discrete Output Module (6Es7 322-8Bh01-0Ab0)

    Discrete Output Module (6ES7 322-8BH01-0AB0) Note For a complete functional description and the most current technical specifications for this module, refer to the manual SIMATIC ET 200M Signal Modules for Process Automation (document number A5E00085262-4, Edition 10/2004, Entry ID: 7215812).
  • Page 204: Hardware Configuration

    16-Channel, 24 VDC Discrete Output MTA 15.12 Hardware Configuration The 16-Channel Discrete Output Module and its MTA support redundant and non- redundant operation. 15.12.1 Addresses Non-redundant Operation The choice of the Input Address and Process Image are left to the user. Redundant Operation Process Image should be set to something other than the default.
  • Page 205: Outputs

    16-Channel, 24 VDC Discrete Output MTA 15.12.2 Outputs All options should be set for the user preferences. Figure 15–4 16-Channel Discrete Output Hardware Configuration: Outputs Configured with all diagnostics enabled Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 206: Redundancy

    16-Channel, 24 VDC Discrete Output MTA 15.12.3 Redundancy Figure 15–5 16-Channel Discrete Output Hardware Configuration: Redundancy Selections Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 207: 16-Channel, 24 Vdc Discrete Output Mta

    16.1 Description This section contains information and requirements to facilitate installation of Siemens Marshalled Termination Assembly (MTA) (6ES7650-1AD11-2XX0), designed to interface with the Siemens ET 200M 16-Channel, 24 VDC Discrete Output module (6ES7 322-8BH10-0AB0. 16.2 Features The following features have been incorporated into this MTA: •...
  • Page 208: Installation Requirements

    Digital Output Module DO16xDC24V/0,5A and not on the MTA. CHx- is the field device return. Redundant operation uses two Digital Output Modules. Connection from the MTA to the I/O Module is accomplished with a 40 pin Siemens connector wired to a D25 male connector. Caution The heat sink can be over 100 °C.
  • Page 209 16-Channel, 24 VDC Discrete Output MTA Note Status LED With a normally connected load, the green Status LED is on when the channel is switched ON, and OFF when the channel is switched off. The green Status LED is also on when the channel is switched OFF and not connected to the external load (wire break is indicated in module diagnostic).
  • Page 210: Simplified Diagram

    16-Channel, 24 VDC Discrete Output MTA 16.6 Simplified diagram Figure 166–1 16-Channel, 24 VDC Discrete Output Marshalled Termination Assembly (6ES7650-1AD11- 2XX0) L/A+ L/B+ & DO16 Module 1 Chx+ Load Chx- DO16 Module 2 MTA – DO16 Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 211: Component Identification

    16-Channel, 24 VDC Discrete Output MTA 16.7 Component Identification Figure 166–2 16-Channel, 24 VDC Discrete Output Marshalled Termination Assembly (6ES7650-1AD11- 2XX0) SH15 SH14 CH15- CH14- CH15+ CH14+ SH13 SH12 CH13- CH12- CH13+ CH12+ SH11 SH10 CH11- CH10- CH11+ CH10+ CH9- CH8- CH9+ CH8+...
  • Page 212 16-Channel, 24 VDC Discrete Output MTA Key to numbered items in Figure 15–1: Item Description Output Power Monitor System Ground stud for connecting shield to earth ground Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 213: Technical Specifications

    8.3 A maximum All outputs OFF 0.26 A maximum Power Dissipation (typical) Fuse Ratings 10 A/125V (Bussmann P/N: GMA-10A) Module (Siemens Spare P/N: A5E01568881) or (Schurter P/N: 0034.1526) (Siemens Spare P/N: A5E01574409) Environmental Ambient Temperature -25C to +60C Humidity 5% to 95% Non-condensing...
  • Page 214 16-Channel, 24 VDC Discrete Output MTA Note Fuses are available as spare parts from Siemens. Fuse information can be found at: http://www.bussmann.com http://www.schurterinc.com Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 215: Changes To 16-Channel, 24 Vdc Discrete Output Module (6Es7 322-8Bh10-0Ab0) Specifications

    16-Channel, 24 VDC Discrete Output MTA 16.9 Changes to 16-Channel, 24 VDC Discrete Output Module (6ES7 322-8BH10-0AB0) Specifications This section contains changes to the I/O module specifications when it is used with the MTA. Changes to 16-Channel, 24 VDC Discrete Output Module (6ES7 322-8BH10-0AB0) Specifications when used with 16-Channel, 24 VDC Discrete Output MTA (6ES7650-1AD11- 2XX0) Isolation between groups of 4 channels...
  • Page 216: Typical Load Connection To Field Terminals

    16-Channel, 24 VDC Discrete Output MTA 16.11 Typical Load Connection to Field Terminals Figure 166–3 Load Connection to Field Terminals of 16-Channel, 24 VDC Discrete Output CH0+ CH1+ load CH0- 24 V DC CH1- 0,5A CH2+ Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 217: Hardware Configuration

    16-Channel, 24 VDC Discrete Output MTA 16.12 Hardware Configuration The 16-Channel Discrete Output Module and its MTA support redundant and non- redundant operation. 16.12.1 Addresses Non-redundant Operation The choice of the Input Address and Process Image are left to the user. Redundant Operation Process Image should be set to something other than the default.
  • Page 218: Outputs

    16-Channel, 24 VDC Discrete Output MTA 16.12.2 Outputs All options should be set for the user preferences. Figure 166–5 16-Channel Discrete Output Hardware Configuration: Outputs Configured with all diagnostics enabled Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 219: Redundancy

    16-Channel, 24 VDC Discrete Output MTA 16.12.3 Redundancy Figure 166–6 16-Channel Discrete Output Hardware Configuration: Redundancy Selections Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 220: Failsafe 10-Channel, 24-150 Vdc/120-230 Vac Relay Output Mta

    Siemens, 24-150 VDC/120-230 VAC Relay Output Marshalled Termination Assembly (MTA) (6ES7650-1AM31-6XX0 or 6ES7650-1AM30-6XX0), designed to interface with the Siemens ET 200M 10-Channel Failsafe Discrete Output Module (6ES7 326-2BF10-0AB0, E-Stand 3 or higher). Note: The only major difference between the two part numbers is the housing.
  • Page 221: Operation

    Failsafe 10-Channel, 24-150 VDC/120-230 VAC Relay Output MTA 17.3 Operation Power is supplied via the two removable power connectors which are retained by screws and marked L+A, MA, and L+B, MB. Each has a LED to indicate the presence of voltage over 15 VDC. The LEDs are marked A POWER and B POWER.
  • Page 222: Maintenance

    Failsafe 10-Channel, 24-150 VDC/120-230 VAC Relay Output MTA 17.5 Maintenance See Section 3, Maintenance, before performing any maintenance and observe all warnings Under normal operation, the A/B Power LED and the Module 1/2 Fuse LED are on. If all are off, check the power supply to MTA. If the A/B Power LED is off, check the power supply to the MTA.
  • Page 223: Simplified Diagram

    Failsafe 10-Channel, 24-150 VDC/120-230 VAC Relay Output MTA 17.6 Simplified diagram Figure 17–1 12/24-Channel, 24 VDC F Discrete Input Marshalled Termination Assembly (6ES7650- 1AM31-6XX0 or 6ES7650-1AM30-6XX0) L/A+ L/B+ DO10 Module 1 NO x NC x COM x DO10 Module 2 MTA –...
  • Page 224: Failsafe 10-Channel, 24-150 Vdc/120-230 Vac Relay Output Marshalled Termination Assembly

    Failsafe 10-Channel, 24-150 VDC/120-230 VAC Relay Output MTA 17.7 Failsafe 10-Channel, 24-150 VDC/120-230 VAC Relay Output Marshalled Termination Assembly Figure 17– shows the basic parts of the 10-Channel, 24-150 VDC/120-230 VAC Relay Output MTA. Figure 17–2 10-Channel, 24-150 VDC/120-230 VAC Relay Output Marshalled Termination Assembly (6ES7650-1AM30-6XX0 or 6ES7650-1AM31-6XX0) 40 NOT USED 39 CH9 NO...
  • Page 225 Failsafe 10-Channel, 24-150 VDC/120-230 VAC Relay Output MTA Key to numbered items in Figure 17–: Item Description Input power connections Input power indicators Field wiring connections I/O module connectors Shield disconnect jumpers Module power fuses Module power indicators Module output fuse ( 1 of 10 ) Relay ( 1 of 10 ) Shield Ground Stud for connecting to earth ground Marshalled Termination Assemblies for ET200M Remote I/O Modules...
  • Page 226: Technical Specifications

    24 – 14 gauge AWG / 0,205 – 2,08 mm sq. Power Supply Specifications See Module Specs Fuse Ratings Module Power 1.0 A (Bussmann P/N: GMA-1.0A) (Siemens Spare P/N: A5E01568881) Individual channel – Normal 0.10 A (Littelfuse P/N 273.100) (Siemens Spare P/N: A5E01568889) Indicators Input Power...
  • Page 227: Technical Specification For 6Es7650-1Am31-6Xx0

    Failsafe 10-Channel, 24-150 VDC/120-230 VAC Relay Output MTA Overvoltage Installation Category Category III 150V maximum Category II 250V maximum Environmental Ambient Temperature -25C to +60C Humidity 5% to 95% Non-condensing Approvals MTA Agency Approvals See Preface section, Approvals Table Max achievable Safety Integrity Level in safety mode In Accordance with IEC 61508 SIL 2 Fail-safe performance Characteristics...
  • Page 228 Failsafe 10-Channel, 24-150 VDC/120-230 VAC Relay Output MTA Fuse Ratings Module Power 1.0 A (Bussmann P/N: GMA-1.0A) (Siemens Spare P/N: A5E01568882) Individual channel – Normal 0.10 A (Littelfuse P/N 273.100) (Siemens Spare P/N: A5E01568889) Indicators Input Power Green LED on when input power available...
  • Page 229 1350 VAC/2sec (all channels to sec. + shield) Rated voltage 100V < Ue < 150V 820 VAC/2sec (between channels for 150 VDC) Note Fuses are available as spare parts from Siemens. Fuse information can be found at: http://www.littelfuse.com http://www.bussmann.com Relays are available as spare parts from Siemens.
  • Page 230: 17.9 Module Restrictions

    Failsafe 10-Channel, 24-150 VDC/120-230 VAC Relay Output MTA 17.9 Module Restrictions Note Module restrictions differ slightly for the two MTA part numbers. Note the part number and refer to the appropriate sections below. 17.9.1 Module Restrictions for 6ES7650-1AM30-6XX0 Restrictions for 10-Channel, 24-150 VDC/120-230 VAC Relay Output MTA (6ES7650-1AM30-6XX0) I/O Module Restrictions Module Design - Diode Outputs used...
  • Page 231: Module Restrictions For 6Es7650-1Am31-6Xx0

    Failsafe 10-Channel, 24-150 VDC/120-230 VAC Relay Output MTA 17.9.2 Module Restrictions for 6ES7650-1AM31-6XX0 Restrictions for 10-Channel, 24-150 VDC/120-230 VAC Relay Output MTA (6ES7650-1AM31-6XX0) I/O Module Restrictions Module Design - Diode Outputs used See module specifications for limitations Relay Maximum Relay Contact Ratings Resistive Load: Max Switched Power: 120 W or 1150 VA Max Switched Current:...
  • Page 232: Typical Load Connection To Field Terminals

    Failsafe 10-Channel, 24-150 VDC/120-230 VAC Relay Output MTA 17.10 Typical Load Connection to Field Terminals Figure 17–3 10-Channel, 24-150 VDC/120-230 VAC Relay Output MTA Load Connection to Field Terminals 120 - 230 VAC NC 0 COM 0 NO 0 120 - 230 VAC LOAD NC 1 COM 1...
  • Page 233: Hardware Configuration

    Failsafe 10-Channel, 24-150 VDC/120-230 VAC Relay Output MTA 17.11 Hardware Configuration The 10 channel Fail-Safe Discrete Output Module and its Relay Output MTA support Redundant and Non-redundant operation. 17.11.1 Addresses Non-redundant Operation The choice of the Input Address and Process Image are left to the user. Redundant Operation Process Image should be set to something other than the default.
  • Page 234: Outputs

    Failsafe 10-Channel, 24-150 VDC/120-230 VAC Relay Output MTA 17.11.2 Outputs The Relay Output MTA uses the series diode outputs from the FDO module for both redundant and non-redundant operation. This determines which diagnostics are generated. More information about these effects can be found in the I/O Restrictions section of the Technical Specifications table and the module specifications.
  • Page 235: Redundancy

    Failsafe 10-Channel, 24-150 VDC/120-230 VAC Relay Output MTA 17.11.3 Redundancy Figure 17– shows a redundant FDO configuration. Figure 17–6 10-Channel Fail-Safe Discrete Output Hardware Configuration: Redundancy Selections 17.12 Technical Specifications for 10-Channel, 24 VDC F Discrete Output Module (6ES7 326-2BF10-0AB0) Note For a complete functional description and the most current technical specifications for this module, refer to the manual S7-300 Automation System Fail-Safe Signal...
  • Page 237: 16-Channel, 24-150 Vdc/120-230 Vac Relay Output Mta

    Description This section contains information and requirements to facilitate installation of Siemens, 24-150 VDC/120-230 VAC Relay Output Marshalled Termination Assembly (MTA) (6ES7650-1AM30-3XX0), designed to interface with the Siemens ET 200M 16-Channel Discrete Output Module ( , E-Stand 1 or 6ES7 322-8BH01-0AB0 higher).
  • Page 238: Operation

    16-Channel, 24-150 VDC/120-230 VAC Relay Output MTA 18.3 Operation Power is supplied via the removable power connector marked L+A, MA, and L+B, MB. Each has a LED to indicate the presence of voltage over 15 VDC. The LEDs are marked A POWER and B POWER. There is also a connector for a Power Monitor board used to indicate the presence of both A and B power.
  • Page 239: Maintenance

    16-Channel, 24-150 VDC/120-230 VAC Relay Output MTA 18.5 Maintenance See Section 3, Maintenance, before performing any maintenance and observe all warnings Under normal operation, the A/B Power LEDs and the Module 1/2 Fuse LEDs are on. If all are off, check the power supply to MTA. If the A/B Power LEDs are off, check the power supply to the MTA.
  • Page 240: Component Identification

    16-Channel, 24-150 VDC/120-230 VAC Relay Output MTA 18.6 Component Identification Figure 18–1 16-Channel, 24-150 VDC/120-230 VAC Relay Output Marshalled Termination Assembly (6ES7650-1AM30-3XX0). Shown without cover and frame. Reference figure 1-2 for cover and frame information. TO REMOVE RELAY PUSH PLASTIC CLIP TO THE SIDE AND USE NEEDLE NOSE PLYERS TO GRIP RELAY AND REMOVE 2.24 CH15 COM...
  • Page 241 16-Channel, 24-150 VDC/120-230 VAC Relay Output MTA Key to numbered items in Figure 18–1: Item Description Input power connections (Power A, Power B) Input power indicators (Power A, Power B) Field wiring connections I/O module connectors (Module 1, Module 2) Shield disconnect jumpers (Module 1, Module 2) Module power fuses (Module 1, Module 2) Module power indicators (Module 1, Module 2)
  • Page 242: Technical Specifications

    Power Dissipation (typical) Wire Size – US / Metric 24 to 14 AWG / 0,205 – 2,08 mm sq. Fuse Ratings Module 2.0 A (Bussmann P/N: GMA-3.0A) (Siemens Spare P/N: A5E01574387) Environmental Ambient Temperature -25C to +60C Humidity 5% to 95% Non-condensing...
  • Page 243 5 Amps at 120 VAC – 230VAC 5 amps at 24 VDC 0.4 A at 150 VDC UL Contact Ratings: 5A/250 VAC General Purpose (Siemens Spare P/N A5E02164559) Resistive load max. 0.1Hz Switching Frequency Coil Resistance 1440 Ohms (Nominal) Minimum Output Rating (Wetting Rating)
  • Page 244: Changes To 16-Channel, 24 Vdc Discrete Output Module (6Es7 322-8Bh01-0Ab0) Specifications

    16-Channel, 24-150 VDC/120-230 VAC Relay Output MTA Fuses are available as spare parts from Siemens. Note Fuse information can be found at: http://www.bussmann.com Relays are available as spare parts from Siemens. Relay Information can be found at: http://www.azettler.com 18.8 Changes to 16-Channel, 24 VDC Discrete Output Module (6ES7 322-8BH01-0AB0) Specifications This section contains changes to the I/O module specifications when it is used with the MTA.
  • Page 245: Technical Specifications For 16-Channel, 24 Vdc Discrete Output Module (6Es7 322-8Bh01-0Ab0)

    Discrete Output Module (6ES7 322-8BH01-0AB0) For a complete functional description and the most current technical specifications Note for this module, refer to the manual SIMATIC ET 200M Signal Modules for Process Automation (document number A5E00085262-04). 18.10 Typical Load Connection to Field Terminals Figure 18–2 16-Channel, 24-150 VDC/120-230 VAC Relay Output MTA Load Connection to...
  • Page 246: Hardware Configuration

    16-Channel, 24-150 VDC/120-230 VAC Relay Output MTA 18.11 Hardware Configuration The 16-Channel Discrete Output Module and its MTA support redundant and non- redundant operation. 18.11.1 Addresses Non-redundant Operation The choice of the Input Address and Process Image are left to the user. Redundant Operation Process Image should be set to something other than the default.
  • Page 247: Outputs

    16-Channel, 24-150 VDC/120-230 VAC Relay Output MTA 18.11.2 Outputs The Relay Output MTA uses the series diode outputs from the DO16 module for both redundant and non-redundant operation. All options should be set to user preferences. Figure 18–4 shows the DO16 configured with all the diagnostics enabled. Figure 18–4 16-Channel Discrete Output Hardware Configuration: Outputs Configured for Standard Mode Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 248: Redundancy

    16-Channel, 24-150 VDC/120-230 VAC Relay Output MTA 18.11.3 Redundancy Figure 18–5 shows a redundant 16-Channel Discrete Output configuration. Figure 18–5 16-Channel Discrete Output Hardware Configuration: Redundancy Selections Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 249: Power Monitor Board

    6ES7650-1BA02-0XX0 19.1 Description This section contains information and requirements to facilitate installation of Siemens Power Monitor Board (6ES7650-1BA02-0XX0), designed to interface with the Siemens ET 200M MTAs. Caution A previous version of the Power Monitor Board (6ES7650-1BA00) exists. The previous version is not suitable for use on MTAs with covers.
  • Page 250: Power Monitor Board

    Power Monitor Board 19.4 Power Monitor Board Figure 19–1 Power Monitor Board Key to numbered items in Figure 19–1: Item Description Relays Input Connector Field Terminals 1 & 2 (Output Contacts) Mounting Screw Lock Washer Flat Washer Standoff Retaining Washer Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 251: Technical Specifications

    Power Monitor Board 19.5 Technical Specifications Technical Specifications for Power Monitor Board (6ES7650-1BA02-0XX0) Dimensions L x W x D – inches 1.40 x .95 x 1.0 L x W x D – mm 35.6 x 24.1 x 25.4 Relay Output Contact Ratings Maximum Switched Voltage 30 VDC Maximum Switched Current...
  • Page 253: 20 8-Channel Hart Analog Input Mta

    6ES7650-1AA61-2XX0 20.1 Description This section contains installation information and requirements for Siemens Marshalled Termination Assembly (MTA) (6ES7650-1AA61-2XX0), which connects to the Siemens ET 200M 8-Channel HART Analog Input Module (6ES7 331- 7TF01-0AB0). 20.2 Features This MTA has the following features: •...
  • Page 254: Operation

    8-Channel HART Analog Input MTA 20.3 Operation Power is supplied via a removable power connector marked L+A, MA, L+B, and MB. There is circuitry to detect the presence of voltage over 15 VDC and turn on the LED indicator. The LEDs are marked A POWER and B POWER. There is also a connector for a Power Monitor board used to indicate the presence of both A and B power.
  • Page 255: Installation Requirements

    8-Channel HART Analog Input MTA 20.4 Installation Requirements See Section 2 Installation, before performing any installation and observe all warnings A common interconnecting cable (6ES7922-3BD01-0AM0 or 6ES7922-3BJ01- 0AM0), supporting eight analog input channels, connects the analog input termination assembly to the 8-channel analog input module (6ES7 331-7TF01- 0AB0).
  • Page 256: 8-Channel Hart Analog Input Marshalled Termination Assembly

    8-Channel HART Analog Input MTA 20.6 8-Channel HART Analog Input Marshalled Termination Assembly The figure below shows the basic parts of the 8-Channel HART Analog Input MTA. Figure 20–1 8-Channel HART Analog Input Marshalled Termination Assembly (6ES7650-1AA61-2XX0) MODULE 1 MODULE 2 32 CH7 SHIELD 28 CH6 SHIELD 31 CH7 I-...
  • Page 257: Technical Specifications

    Between the channels Fuse Ratings / Current Limiting Module 0.5 A (Bussmann P/N: GMA-0.5A) (Siemens Spare P/N: A5E01568885) Channel (2 wire transducer connection) short circuit current about 40 - 60 mA Characteristic Data of Transducer Supply Output voltage for transducer and field wiring at ≥15 V (at Un = 24 V)
  • Page 258 5% to 95% Non-condensing Approvals MTA Agency Approvals See Preface section, Approvals Table User's Manual) Note Fuses are available as spare parts from Siemens. Fuse information can be found at: http://www.bussmann.com Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 259: Changes To Module Specifications

    8-Channel HART Analog Input MTA 20.8 Changes to Module Specifications Changes to 8-Channel HART Analog Input Module (6ES7 322-7TF01-0AB0) Specifications when used with 8-Channel HART Analog Input MTA (6ES7 650-1AA61-2XX0) Redundant Mode When using the MTA, the I/O module must be used in the redundant mode.
  • Page 260: Typical Wiring Schemes

    8-Channel HART Analog Input MTA 20.10 Typical Wiring Schemes 2 Wire Transducer, Non Redundant Modules Application: The transducer is connected to either Module 1 or 2 via the HAI MTA. The jumper on the HAI MTA is placed in the 2 Wire position. 2 Wire Transducer, Redundant Modules Application: The transducer is connected to both Module 1 and 2 via the HAI MTA.
  • Page 261 8-Channel HART Analog Input MTA 4 Wire Transducer, Non Redundant Modules Application: The transducer is connected to either Module 1 or 2 via the HAI MTA. The jumper on the HAI MTA is placed in the 4 Wire position. 4 Wire Transducer, Redundant Modules Application: The transducer is connected to both Module 1 and 2 via the HAI MTA.
  • Page 262: Hardware Configuration

    Input Module (6ES7 331-7TF01-0AB0) Note For a complete functional description and the most current technical specifications for this module, refer to the manual ET 200M distributed I/O device HART analog modules (document number A5E00434623). Marshalled Termination Assemblies for ET200M Remote I/O Modules...
  • Page 263: 21 8-Channel Hart Analog Output Mta

    21.1 Description This section contains information and requirements to facilitate installation of Siemens Marshalled Termination Assembly (MTA) (6ES7650-1AB61-2XX0), designed to interface with the Siemens ET 200M 8-Channel HART Analog Output Module (6ES7 332-8TF01-0AB0). 21.2 Features The following features have been incorporated into this MTA: •...
  • Page 264: Operation

    8-Channel HART Analog Output MTA 21.3 Operation Power is supplied via the two removable power connectors which are retained by screws and marked L+A, MA, and L+B, MB. Each has circuitry to detect the presence of voltage over 15VDC and turn on the LED indicator. The LEDs are marked A POWER and B POWER.
  • Page 265: 8-Channel Hart Analog Output Marshalled Termination Assembly

    8-Channel HART Analog Output MTA 21.6 8-Channel HART Analog Output Marshalled Termination Assembly Figure 21–1 below shows the basic parts of the 8-Channel HART Analog Output MTA. Figure 21–1 8-Channel HART Analog Output Marshalled Termination Assembly (6ES7650-1AB61-2XX0) 24 CH7 SHIELD 23 CH7- 22 CH7+ 21 CH6 SHIELD...
  • Page 266: Technical Specifications

    With 500 VDC Between the channels Fuse Ratings / Current Limiting Module 0.5 A (Bussmann P/N: GMA-0.5A) (Siemens Spare P/N: A5E01568885) Indicators Input Power Green LED on when input power available, red LED on if power supply is reversed Module Fuse OK...
  • Page 267: Module Restrictions

    Approvals MTA Agency Approvals See Preface section, Approvals Table User's Manual) Note Fuses are available as spare parts from Siemens. Fuse information can be found at: http://www.bussmann.com 21.8 Module Restrictions Changes to 8-Channel HART Analog Output Module (6ES7 322-8TF01-0AB0) Specifications...
  • Page 268: Typical Wiring Schemes

    8-Channel HART Analog Output MTA 21.9 Typical Wiring Schemes Non-Redundant Module Application: The load or actuator is connected to either Module 1 or 2 via the AOH MTA. Redundant Modules Application: The load or actuator is connected to both Module 1 and Module 2 via the AOH MTA. Figure 21–2 Typical wiring scheme for connecting load field terminals.
  • Page 269: Hardware Configuration

    Output Module (6ES7 332-8TF01-0AB0) Note For a complete functional description and the most current technical specifications for this module, refer to the manual ET 200M distributed I/O device HART analog modules (document number A5E00434623). Marshalled Termination Assemblies for ET200M Remote I/O Modules...
  • Page 270 8-Channel HART Analog Output MTA Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 271: 16-Channel, 24 Vdc Power Supply Mta

    16-Channel, 24 VDC Power Supply MTA Part No. 6ES7650-1BE10-3XX0 22.1 Description This section contains information and requirements to facilitate installation of Siemens Marshalled Termination Assembly (MTA) (6ES7650-1BE10-3XX0), designed to energize 4-wire transducers 22.2 Features The following features have been incorporated into this MTA: •...
  • Page 272: Installation Requirements

    16-Channel, 24 VDC Power Supply MTA Power is supplied via the power connector marked L+A, MA, and L+B, MB. Each has a green LED to indicate the presence of voltage over 15 VDC. In the case of polarity reversal of the power supply, the LEDs will illuminate red. The LEDs are marked A POWER and B POWER.
  • Page 273: Simplified Diagram

    16-Channel, 24 VDC Power Supply MTA 22.6 Simplified diagram Figure 226–1 16-Channel, 24VDC Power Supply Marshalled Termination Assembly (6ES7650-1BE10- 3XX0) L/A+ L/B+ & PWRx 4-wire transducer MTA – PS Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...
  • Page 274: Component Identification

    16-Channel, 24 VDC Power Supply MTA 22.7 Component Identification Figure 226–2 16-Channel, 24 VDC Power Supply Marshalled Termination Assembly (6ES7650-1BE10- 3XX0) Key to numbered items in Figure 15–1: Item Description Input power connections (Power A, Power B) Input power indicators (Power A, Power B) Output Power Monitor System Output Short Circuit Detection Heat sink...
  • Page 275: Technical Specifications

    16-Channel, 24 VDC Power Supply MTA 22.8 Technical Specifications Technical Specifications: 16-Channel, 24 VDC Power Supply MTA (6ES7650-1BE10-3XX0) Dimensions - See Section 1, Figure 1.3, Short Version Mounting DIN Rail 35mm (deep top hat style) Orientation horizontal or vertical Power Input Voltage Input for Single or Redundant Feed 21.6 to 28.8 VDC Total current...
  • Page 276 16-Channel, 24 VDC Power Supply MTA Indicators Input Power Green LED on when input power available, Red LED on when power polarity is reversed Power Output Status Green LED Field Connections Wire Size US 24 to 14 AWG Wire Size metric 0.2 to 2.08 mm Environmental Ambient Temperature...
  • Page 277: Typical Load Connection To Field Terminals

    16-Channel, 24 VDC Power Supply MTA 22.9 Typical Load Connection to Field Terminals Figure 226–3 Load Connection to Field Terminals of 16-Channel, 24 VDC Power Supply MTA-PS MTA-AI8 AI module 1 MTA-FAIH Supply - Output Sensor Input Current 4-wire AI module 2 Transducer 22.10 Hardware Configuration...
  • Page 279: Previous Mta Revisions

    Previous MTA Revisions Previous MTA Revisions This section contains information about previous revisions of the ET200M MTAs. 23.1 8 Channel Analog Input MTA Part No. 6ES7650-1AA50-2XX0 8-Channel Analog Input Marshalled Termination Assembly Figure 23–1 8-Channel Analog Input Marshalled Termination Assembly (6ES7650-1AA50-2XX0) B POWER CR105 ZR101...
  • Page 280 Previous MTA Revisions Key to numbered items in Figure 23–1: Item Description Input power connections Input Power Indicators Field Connections I/O Module Connections ( J1 & J2 ) Shield disconnect jumper (W100 & W101) Field power fuses Field power indication ( 1 of 8 ) Input Isolation Jumper ( W200) HART connectivity Input Mode Jumper ( I –...
  • Page 281: Safety Information For Us Customers

    Safety Information for US Customers Safety Information for US Customers Conventions and Symbols The following symbols may appear in this manual and may be applied to the equipment. The reader should become familiar with the symbols and their meaning. Symbols are provided to quickly alert the user to safety related situations, issues, and text.
  • Page 282 The current version, in Portable Document Format (PDF), is available at http://sitescape.sea.siemens.com/. For the purpose of this publication and product labels, a qualified person is one who is familiar with the installation, construction, and operation of the equipment, and the involved hazards.
  • Page 283 A properly grounded conductive wrist strap must be worn whenever an electronics module or circuit board is handled or touched. A service kit with a wrist strap and static dissipative mat is available from Siemens (PN15545- 110). Equivalent kits are available from both mail order and local electronic supply companies.
  • Page 284 Safety Information for US Customers Marshalled Termination Assemblies for ET200M Remote I/O Modules A5E00482820-12...

Table of Contents