17.9 Module Restrictions; Module Restrictions For 6Es7650-1Am30-6Xx0 - Siemens ET 200M Manual

Marshalled termination assemblies remote i/o modules
Table of Contents

Advertisement

Failsafe 10-Channel, 24-150 VDC/120-230 VAC Relay Output MTA

17.9 Module Restrictions

Note
Module restrictions differ slightly for the two MTA part numbers. Note the part
number and refer to the appropriate sections below.
17.9.1

Module Restrictions for 6ES7650-1AM30-6XX0

Restrictions for 10-Channel, 24-150 VDC/120-230 VAC Relay Output MTA
I/O Module Restrictions
Module Design - Diode Outputs used
Relay
Maximum Relay Contact Ratings
Coil Resistance
Minimum Output Rating (Wetting Rating)
Relay Output Fuse
Minimum operations
Mechanical
Electrical
Relay Contact Restrictions
Relay Output Fusing
Relay Voltage Restrictions
230
(6ES7650-1AM30-6XX0)
See module specifications for limitations
Resistive Load:
Max Switched Power: 150 W 0r 1250 VA
Max Switched Current:
5 Amps at 120 VAC – 230 VAC
5 Amps at 24 VDC
0.4 A at 120 VDC
¼ HP @ 120 VAC motor load
1200 Ohm (Nominal)
0.1 A at 5 VDC
None - External Fusing required
30 million operations
5
1 x 10
at 10 A, 24 VDC or 120 VAC
5
2 x 10
at 8 A, 230 VAC
Fuses for the relay output connection must be
provided externally to the MTA
For voltages up to 150 VDC channels may be
mixed mode.
For voltages greater than 150 VDC, all
channels must be of the same voltage.
For AC voltages all channels must be the
same phase.
Marshalled Termination Assemblies for ET200M Remote I/O Modules
A5E00482820-12