ADJUSTING AIR AND LIGHT OIL FLOW RATE

Light oil nozzles

The light oil flow rate can be adjusted choosing a nozzle that suits the boiler/utilisation output and setting the delivery and return pres-
sure values according to the ones quoted on the chart below and the diagram on Fig. 20 (as far as reading the pressure values, see
next paragraphs).
NOZZLE
BERGONZO A3
FLUIDICS WR2/UNIGAS M3
Example: as far as over 100kg/h nozzle the 80% of the nozzle rated flow rate is achieved with 18bar return pressure (see Fig. 20).
FLOW RATE kg/h
DIMENSIONS
Min
40
13
50
16
60
20
70
23
80
26
90
30
100
33
115
38
130
43
145
48
160
53
180
59
200
66
225
74
250
82
275
91
300
99
330
109
360
119
400
132
450
148
500
165
550
181
600
198
650
214
700
231
750
250
800
267
Tab. 1
NOZZLE SUPPLY
PRESSURE (bar)
20
25
Max
Pressure at nozzle 25bar
40
50
60
70
80
90
100
115
130
Pressure on return
145
160
180
200
225
250
275
300
Up to 100kg/h
330
360
400
450
500
Over 100kg/h
550
600
650
700
750
800
---------------Atomisation angle according to the return pressure
_________ % Flow rate
HIGH FLAME
RETURN PRESSURE (bar)
11 - 13
19 - 20
Fig. 20
20
LOW FLAME
RETURN PRESSURE (bar)
5 (recommended))
7 (recommended)
Pressure at nozzle 357psi
Atomisation angle
Pressure on return
% Flow rate