Adjusting light oil flow rate

The light oil flow rate can be adjusted choosing a by-pass nozzle that suits the boiler/utilisation output and setting the delivery and
return pressure values according to the ones quoted on the chart below and the diagram on Fig. 15 (as far as reading the pressure
values, see next paragraphs).
NOZZLE
FLUIDICS WR2
FLOW RATE kg/h
DIMENSIONS
Min
40
13
50
16
60
20
70
23
80
26
90
30
100
33
115
38
130
43
145
48
160
53
180
59
200
66
225
74
250
82
275
91
300
99
330
109
360
119
400
132
450
148
500
165
550
181
600
198
650
214
700
231
750
250
800
267
Tab. 4
Example: as for over 100kg/h nozzles, the 80% of the nozzle flow rate can be obtained with a return pressure at about 18bar (see Fig.
15Fig. 15).
C.I.B. UNIGAS - M039196CC
DELIVERY
PRESSURE
bar
25
Max
Pressure at nozzle 25bar
40
50
60
70
80
90
100
115
130
Pressure on return
145
160
180
200
225
250
275
Up to 100kg/h
300
330
360
400
450
Over 100kg/h
500
550
600
650
700
750
800
---------------Atomisation angle according to the return pressure
_________ % Flow rate
RETURN
PRESSURE MAX.
bar
19-20
Fig. 15
21
RETURN
PRESSURE MIN.
bar
7 - 9 (recommended)
Pressure at nozzle 357psi
Atomisation angle
Pressure on return
% Flow rate