General purpose programmable controller

Advertisement

FX-PCG16 General Purpose Programmable Controller
Installation Instructions
FX-PCG1611-x, FX-PCG1621-x
Application
The FX-PCG16 controller is part of the Facility Explorer
Controller FX-PCG family. The FX-PCG16 controller runs
pre-engineered and user-programmed applications and
provides the inputs and outputs required to monitor and
control a wide variety of HVAC equipment.
The FX-PCG controllers operate on an RS-485 BACnet®
Master-Slave/Token-Passing (MS/TP) Bus as BACnet
Application Specific Controllers (B-ASC) and integrate
into Johnson Controls® and third-party BACnet systems.
With Release 10.1, you can use the FX-PCT software
to switch the FX-PCG to use the N2 protocol.
The FX-PCG16 controller is available with or without an
integral LCD and push button user interface.
Switchable Communications
Protocols
By default, the FX-PC family controllers and network
sensors communicate using the standard BACnet
protocol, based on the ANSI/ASHRAE 135-2004.
The BACnet protocol is a standard for ANSI, ASHRAE,
and the International Standards Organization (ISO) for
building controls.
FX-PCG, FX-PCX, and FX-PCV controllers are BTL-
tested and listed as BACnet Application Specific
Controllers (B-ASCs). FX-PCA field controllers are
BTL-listed as BACnet Advanced Application Controllers
(B-AACs). The NS Series Sensors are BTL-listed as
BACnet Smart Sensors (B-SSs).
Release 10.1 of FX-PCT and later can be used to switch
the Field Bus communications protocol in FX-PC
Controllers to be either the standard BACnet
Master-Slave/Token-Passing (MS/TP) or the N2 protocol.
BACnet MS/TP is the default communications protocol
for all new controllers. Switchable communications
protocols provide a cost-effective upgrade and
modernization path for customers with existing N2
controllers. The Modernization Guide for Legacy N2
Controllers (LIT-12012045) and the controller-specific
documentation provide installation and commissioning
support and include tips for efficient and safe
replacement. Refer to the N2 Compatibility Options
chapter of the Controller Tool Help (LIT-12011147) for
information about mapping N2 Objects in controllers with
switchable communications protocols.
FX-PCG16 General Purpose Programmable Controller Installation Instructions
Part No. 24-10143-152, Rev. G
Refer to the
QuickLIT website
The N2-capable FX-PC controllers can be used as
functional replacements for legacy N2 controllers. The
N2-capable FX-PC controllers:
have the I/O quantities and characteristics of the
FX-PC family controllers
must be programmed with FX-PCT, which has
programming capabilities that are similar (but not
identical) to HVACPro, GX9100, GPL, and other
legacy tools
support SA Bus devices
support FX-WRZ wireless sensors from the controller
using the FX-WRZ7860 receiver when configured for
BACnet MS/TP communication
The N2-capable FX-PC controllers:
do not support Zone Bus (for example, TMZ sensors
and M100 actuators)
do not support pass through in the commissioning
mode
do not support remote downloading or commissioning
using BACnet routing
do not support wireless connection to the N2 bus
Issued April 2016
for the most up-to-date version of this document.
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FX-PCG1621 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Johnson Controls FX-PCG1621 Series

  • Page 1 Master-Slave/Token-Passing (MS/TP) Bus as BACnet identical) to HVACPro, GX9100, GPL, and other Application Specific Controllers (B-ASC) and integrate legacy tools into Johnson Controls® and third-party BACnet systems. With Release 10.1, you can use the FX-PCT software • support SA Bus devices to switch the FX-PCG to use the N2 protocol.
  • Page 2: North American Emissions Compliance

    North American Emissions Mounting Compliance Observe these guidelines when mounting an FX-PCG: • Ensure the mounting surface can support the Canada controller, DIN rail, and any user-supplied enclosure. This Class (A) digital apparatus meets all the • Mount the controller horizontally on 35 mm DIN rail requirements of the Canadian Interference-Causing whenever possible.
  • Page 3: Din Rail Mount Applications

    3. Drill holes in the wall or surface at the locations DIN Rail Mount Applications marked in Figure 2, and insert appropriate wall Mounting the controller horizontal on 35 mm DIN rail is anchors in all of the mounting holes (if necessary). the preferred mounting method.
  • Page 4 Figure 3: FX-PCG16 Physical Features Table 1: FX-PCG Physical Features Callouts and Descriptions Callout Physical Feature: Description and References Binary Output (BO) Source Power Selection Jumpers (See Binary Output (BO) Source Power Selection Jumpers) Device Address DIP Switch Block (See Figure Mounting Clip Configurable Output (CO) Terminal Blocks (See...
  • Page 5: Terminal Wiring Guidelines, Functions, Ratings, And Requirements

    Table 1: FX-PCG Physical Features Callouts and Descriptions Callout Physical Feature: Description and References Sensor Actuator (SA) Bus Terminal Block (See SA Bus Terminal Block) Sensor Port (Sensor Actuator [SA] Bus, RJ-12 6-pin Modular Jack) (See Figure Binary Inputs (BIs) Terminal Block (See Table Universal Inputs (UIs) Terminal Blocks (See Table...
  • Page 6 Figure 4: FC Bus Terminal Block Wiring Note: The SA PWR terminal supplies 15 VDC. The SA PWR terminal can be used to connect (daisy chain) the 15 VDC power leads on the SA bus. FC Bus Port The FC bus port on the front of the controller is an RJ-12, 6-position modular jack that provides a connection for the FX-BTCVT Bluetooth®...
  • Page 7 Supply Power Terminal Block Important: Connect 24 VAC supply power to the The 24 VAC supply power terminal block is a gray, controller and all other network devices so removable, 3-terminal plug that fits into a board-mounted that transformer phasing is uniform across jack on the top right of the controller.
  • Page 8: Termination Diagrams

    Termination Diagrams A set of termination diagrams provides details for wiring inputs and outputs to the controllers. See the figures in this section for the applicable termination diagrams. Table 2: Termination Details Type of Field Device Type of Termination Diagrams Input/Output Temperature Sensor Voltage Input - External...
  • Page 9 Table 2: Termination Details Type of Field Device Type of Termination Diagrams Input/Output Current Input - Internal Source (3 wire) Current Input - External Source (in Loop) Feedback from EPP-1000 Dry Contact (Binary Input) UI or BI 0–20 VDC Output to Actuator (External Source) 0–10 VDC Output to Actuator (Internal Source)
  • Page 10 Table 2: Termination Details Type of Field Device Type of Termination Diagrams Input/Output 24 VAC Triac Output (Switch Low, External Source) Incremental Control to Actuator (Switch Low, Externally Sourced) Incremental Control to Actuator (Switch High, Externally Sourced) 24 VAC Binary Output (Switch Low, Externally Sourced) 24 VAC Binary Output...
  • Page 11 Table 2: Termination Details Type of Field Device Type of Termination Diagrams Input/Output Incremental Control to Actuator (Switch Low, Externally Sourced) Network Stat with Phone SA Bus Jack (Fixed Address = 199) FX-PCG16 General Purpose Programmable Controller Installation Instructions...
  • Page 12 Table 2: Termination Details Type of Field Device Type of Termination Diagrams Input/Output Network Stat with SA Bus Terminals Addressable Network Stat with SA Bus Terminals (Fixed Address = 199) FX-PCG16 General Purpose Programmable Controller Installation Instructions...
  • Page 13: Input And Output Wiring Guidelines

    Table Internal 12 V. 15k ohm pull up Qualified Sensors: 0-2k ohm potentiometer, RTD (1k Nickel [Johnson Controls® sensor], 1k Platinum, and A99B Silicon Temperature Sensor) Negative Temperature Coefficient (NTC) Sensor (10k Type L, 10k JCI Type II, 2.252k Type...
  • Page 14 Table 3: FX-PCG Terminal Blocks, Functions, Ratings, Requirements, and Cables Terminal Block Terminal Function, Ratings, Requirements Determine Wire Size and Label Label Maximum Cable Length BINARY Binary Input - Dry Contact Maintained Mode See Guideline A in Table (Inputs) 0.01 second minimum pulse width Internal 18 V.
  • Page 15: Cable And Wire Length Guidelines

    Table 3: FX-PCG Terminal Blocks, Functions, Ratings, Requirements, and Cables Terminal Block Terminal Function, Ratings, Requirements Determine Wire Size and Label Label Maximum Cable Length CONFIGURABLE OUTn Analog Output - Voltage Mode (0–10 VDC) See Guideline A in Table (Outputs) 10 VDC maximum output voltage 10 mA maximum output current Required an external load of 1,000 ohm or more.
  • Page 16: Maximum Cable Length Versus Load Current

    Figure 8 to estimate the maximum cable length Maximum Cable Length versus relative to the wire size and the load current (in mA) when Load Current wiring inputs and outputs. Note: Figure 8 applies to low-voltage (<30V) inputs and outputs only. Figure 8: Maximum Wire Length for Low-Voltage (<30V) Inputs and Outputs by Current and Wire Size •...
  • Page 17 Table 5: Communications Bus and Supply Power Terminal Blocks, Functions, Ratings, Requirements, and Cables Terminal Terminal Function, Electrical Ratings/Requirements Recommended Cable Type Block/Port Labels Label FC Bus Communications 0.6 mm (22 AWG) stranded, 3-wire FC BUS twisted, shielded cable recommended Signal Reference (Common) for Bus communications SHLD Isolated terminal (optional shield drain connection)
  • Page 18: Setup And Adjustments

    Table 6 describes the FC bus and SA bus devices controllers wired slave devices, which do not addresses for Johnson Controls® MS/TP operate on MS/TP buses, but will not interfere communications bus applications. with bus operation. Set a valid and unique device...
  • Page 19 Table 6: SA/FC Bus Device Address Descriptions for MS/TP Controllers Device Use on Description Address 4 to 127 Used for MS/TP master devices (FX-PC controllers) that are hardwired to an SA Bus (Switch or FC Bus. 128 Off) 0 to 3 Reserved addresses for wired slave devices (not for use on FX-PC controllers).
  • Page 20: Removing The Controller Cover

    Removing the Controller Cover Figure 11: End-of-Line Switch Positions Important: Electrostatic discharge can damage controller components. Use proper electrostatic discharge precautions during installation, setup, and servicing to avoid damaging the controller. Important: Disconnect all power sources to the controller before removing the cover and changing the position of any jumper or the To set the EOL switch on a controller: EOL switch on the controller.
  • Page 21: Setting The Input And Output Jumpers

    Setting the Input and Output Universal Input Current Loop Jumpers Jumpers The Universal Input (UI) current loop fail-safe jumpers are on the circuit board under the controller cover near Binary Output (BO) Source Power the UI terminals (Figure 10). When a UI is defined (in the system software) as a 4-20 mA Analog Input and the UI’s Selection Jumpers current loop jumper is in the Disabled (default) position...
  • Page 22: Troubleshooting Controllers

    Off Steady = EOL switch in Off position devices) Repair Information If a controller fails to operate within its specifications, replace the controller. For a replacement controller, contact your Johnson Controls® representative. FX-PCG16 General Purpose Programmable Controller Installation Instructions...
  • Page 23: Technical Specifications

    Table 9 for controller accessories ordering Accessories information. Table 9: Accessories Ordering Information Product Code Number Description FX-BTCVT-1 Bluetooth Commissioning Converter, with Bluetooth® Technology FX-DIS1710-0 Local Controller Display (for use with FX-PCG1611 model only) FX-ZFR1811-0 Wireless Field Bus Router TP-2420 Transformer, 120 VAC Primary to 24 VAC secondary, 20 VA, Wall Plug Y65T31-0 Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount,...
  • Page 24 Canada: UL Listed, File E107041, CCN PAZX7 CAN/CSA C22.2 No.205, Signal Equipment Industry Canada Compliant, ICES-003 Europe: Johnson Controls, Inc. declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive. Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant...
  • Page 25 The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these specifications, consult the local Johnson Controls® office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

This manual is also suitable for:

Fx-pcg16 seriesFx-pcg1611 seriesFx-pcg16

Table of Contents