1 to select ON.
Hear TRIPLE beeps.
4. To verify the status of this option, dial 6 7 and repeat step 2 above.
OUTPUT ZONE/GROUP CONFIGURATIONS
These options apply to zones or groups already configured as outputs (see Program 62, Type of Zone). All
these parameters can be individually optioned per zone. For a summary of these options, see the Programming
Quick Reference Chart at the end of this section.
7 0 SET OUTPUT ZONE TYPE
This option selects the type of output for an individual output zone. The choices here are Audio/Normally Open,
Momentary Open, Normally Closed, System Handshake, Toggle, Phantom, and Attendant Access Handshake.
The Audio/Normally Open option is the default.
When the System Handshake option is chosen, the closure will energize when a valid Off Hook condition has
been detected. The Attendant Access Handshake zone provides an output contact closure when Attendant
Access interface is accessed.
Note: System Handshake is a feature required by certain PBX systems: when they access the paging
system, they require a return acknowledgment signal – the "handshake" – from the Controller.
A Phantom Zone is an output zone that exists only in software. If a page is made to a Phantom zone, the
controller will send a message to an attached monitoring device (if configured) and will issue confirmation tone,
but will take no action with respect to the zone's hardware. This allows uninstalled zones to be used to select
messages on a visual display.
The Momentary Open, Normally Closed and Toggle options are intended to be used for controlling door striker
plates, for instance, to permit a security door to be unlocked. The Momentary Open will stay energized for as
long as the zone is selected. The Toggle will stay energized until the zone is selected again and change relay
until it is accessed again. Normally Closed will open only when the specific zone is selected. Neither of these
modes will respond to an Attendant Access page, an All-Call and/or Zone Grouping page.
Repeat this procedure for each output zone.
1. Dial 7 0 to select this option.
Hear a DOUBLE beep.
2. Enter the output zone number.
Hear a DOUBLE beep.
Note: Use alias numbers, if optioned. Otherwise, use physical zone/group numbers.
3. Enter the code for the type of output you wish to select:
0
selects AUDIO/N.O. (Normally Open)
1
selects Momentary Open
2
selects N/C (Normally Closed)
3
selects Sys HS (System Handshake)
4
selects Toggle
5
selects Phantom
6
selects AA Ready (Attendant Access Handshake)
Hear TRIPLE beeps.
4. To verify the Type of Output assignment, dial 7 1 and repeat steps 2 and 3 above.
7 2 SET PAGE ENABLE
This output zone parameter enables paging for a selected output zone or zone group. The choice for this
selection is YES/NO, with the default being YES. Repeat this procedure for each output zone or zone group.
Note: If you make an all-call page and this option is selected NO in either a zone group or individual
ones, then an all-call page will be made to all other zones except the ones specified. If the decision
is NO for the all-call zone and an all-call page is made, then an error tone will be returned to you.
1. Dial 7 2 to select this option.
Hear a DOUBLE beep.
23