Siemens SITRANS F Series Function Manual page 56

Profibus (from firmware 4.0) coriolis flowmeters
Hide thumbs Also See for SITRANS F Series:
Table of Contents

Advertisement

Communication
2.10 Acyclic communication
Index
Parameter Name
26
VIEW_1
Manufacturer Specific
36
PROCESS_VALUE_
UNITS_TEXT
Table 2-17
Slot 12: Analog Input block - Frame temperature
Index
Parameter Name
16
BLOCK_OBJECT
17
CURRENT_MODE
22
PROCESS_VALUE
23
PROCESS_VAL‐
UE_UNITS
24
DAMPING
25
SIMULATE
26
VIEW_1
Manufacturer Specific
36
PROCESS_VAL‐
UE_UNITS_TEXT
56
Data Type
Access
Annotation
Read
Read-only parameter to read
only
● CURRENT_MODE
● STANDARD VOLUME FLOW
● STANDARD VOLUME FLOW UNITS
● DAMPING
● SIMULATE
Visible‐
Read
only
String (8)
Data Type
Access
Annotation
DS-32
Read
Constant block information
only
Unsigned8
Read
Follows the target mode of the Physical Block
only
8: Automatic
128: Out of service
DS-101
Read
Process value with quality code
only
Un‐
Read
Read-only copy of the transducer block unit setting
signed16
only
Float32
Read /
Low-pass filter of the input value. Value in seconds. Valid
write
range: 0...100 s
DS-50
Read /
Possibility to simulate the PROCESS_VAUE parameter (in‐
write
cluding the quality code). This could be used to verify the
PLC program behavior.
Read
Read-only parameter to read
only
● CURRENT_MODE
● FRAME TEMPERATURE
● FRAME TEMPERATURE UNITS
● DAMPING
● SIMULATE
Visible‐
Read
String(8)
only
FCT030 Profibus (From firmware 4.0)
Function Manual, 06/2018, A5E39931906-AB