SELF TESTING NON-MAINTAINED EMERGENCY CEILING MOUNTED LUMINAIRES
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (NiMh)
BATTERY PROTECTION
INDICATIONS - CONTROLS
CHARGE TIME
MINIMUM DURATION
LIGHT SOURCE
EMERGENCY ILLUMINATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIMENSION
WEIGHT
GUARANTEE
GENERAL
This device is used indoors (ta 40 C) in
places where emergency luminaires are
needed. The luminaire has pre-installed the
anti panic lens. The package also contains
the corridor lens that can be replaced by the
user. Each device must be permanently
connected to mains power supply. In normal
operation the battery is charging. In case of
a mains power supply failure, the device
enters emergency mode and the illumination
LED turns on. When the
supply is restored the device turns to normal
operation.
INSTALLATION
To install the luminaire follow the installation
instructions οn page 3.
Battery Charging
The
battery
charging
controlled. In this case, is achieved the
perfect battery maintenance , as well as the
elongation of its duration. When the battery
has completely charged, it charges with a
maintenance current.
Battery Cut-off
The device in this operation when the mains
power supply fails and battery has lost its
energy. During this operation the device
Page 1 from 6
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
Thank you for your trust in our products
Olympia Electronics - European manufacturer
o
mains
power
is
completely
(for LED MODULE specifications see page 5)
GR-220/DUO/M
220-240V AC / 50-60Hz
4.3W / 4.7 VA
4.8V/1.2Ah
Deep discharge and overcharge protection
Charge, lamp fault, battery fault, TEST button
24 hours
1.5 hour
1 white power LED
300lm
IP40
5 to 40 C
Up to 95%
ABS/PC
Ø125 x 62 mm
474gr.
3 years (1 year for the battery)
enters the idle state and battery consumption
is negligible, in order to be protected from
deep discharge.
Manual Test
This test can be done by pushing the test
button. The light source and the emergency
circuit of the device is monitored. The manual
test can be conducted only if the main power
supply and the battery is connected. During
this test period all indication LEDs are OFF.
Automatic Operational Test
This test includes all the operations that
provide the manual test and is conducted
automatically every 15 days. In order to be
performed, the mains power supply and the
battery should be connected.
Automatic Autonomous Test
The Automatic Autonomous Test is conducted
and measures the device's back up operation
and emergency duration. The BATTERY
FAULT LED blinks during the measurement,
indicating this process to the user. This test is
conducted automatically every six months. In
order to be performed, the mains power
supply and the battery should be connected
and fully charged. If the battery is not fully
charged, the test is postponed until the
battery is completely charged. If during this
test, the autonomy is less than the nominal
GR-221/DUO/M
3 hours
150lm
o
923221000_09_001