Notes on the relay contacts and on the monitoring
and protection contacts

Overview

Relay Contacts, Monitoring & Protection
Cable cross-section: 0.14 - 4 mm²
Tightening torque of terminals: 0.5 Nm
Max. continuous current: 16 A
Min. switching load: 500 mW (10 V / 5 mA)
Switching capacity: 16 A / 250 V (AC1) and 16 A / 30 V (DC1)
(1)
NC1

Relay contacts

SC1
NO1
NC2
SC2
NO2
The relay outputs are not fuse-protected.
Relay contacts can be assigned different functions in the Basic service menu.
The access code 22742 must be entered to access the Basic service menu:
-
-
-
-
-
-
12
(1)
(2)
(3)
NC for relay contact 1
Relay contact 1
NO for relay contact 1
NC for relay contact 2
Relay contact 2
NO for relay contact 2
Press the 'Menu' key
Select 'Setup' mode
Press the unassigned 'Esc' button five times
Enter the access code 22742
Select the 'Switch contact 1' or 'Switch contact 2' parameter
Set the desired relay contact function
(4)
(1) - (4) ... 0,5 Nm
*
*