Electrical installation
Figure 4-5
Connection
When connecting the dv/dt filter compact plus Voltage Peak Limiter, you must take into
account the following conditions to ensure that it functions correctly:
● Control cables must be routed separately from power cables. Power cables are the motor
cable or the connecting cables from the DC link of the Power Module (terminals
DCPS/DCNS) to the dv/dt filter compact plus Voltage Peak Limiter. In particular, you must
ensure that control cables and power cables are not routed in parallel in a joint cable
raceway, even if all the cables are shielded.
● You must use shielded motor cables. The shield for the motor cable must be attached to
the shield plate and motor housing.
● The ground wire for the motor must be fed directly back to the Power Module.
26
Interface overview dv/dt filter compact plus Voltage Peak Limiter - Voltage Peak Limiter,
Type 4
dV/dt filter compact plus Voltage Peak Limiter
Operating Instructions, 11/2017, A5E02590131A