This parameter indicates the mode used to change
pumps when the pump is part of a unit (PRI, SEC).
CH01: Indicates that the first pump to come on at the next
request for water will be the one which started-up second
or which did not start-up during the last cycle. The second
pump cannot support the first in this mode (BOOSTER
setting).
CH02: Indicates that the first pump to come on at the next
request for water will be the one which did not start up
during the last cycle. The second pump cannot support
the first in this mode.
CH03: Indicates that the first pump to come on at the next
request for water will be the one which has run for the
Type of exchange
least amount of time (see functioning hours parameter).
The second pump cannot support the first in this mode
(BOOSTER setting).
CH04: Indicates that the first pump to come on at the next
request for water will be the one which has run for the
least amount of time (see functioning hours parameter).
The second pump cannot support the first in this mode.
CH05: In this setting, the first pump to start-up is the one
entered as the primary pump in the "type of pump"
parameter. The second pump can support the first in this
mode; however, the cyclical function is not available.
Minimum
Parameter defining minimum motor rotation frequency.
frequency
Maximum
Parameter defining maximum motor rotation frequency.
frequency
Reactivity factor
Parameter defining the speed with which the motor
responds to changes in pressure. The lower the setting
the faster the motor's response.
Bottom
scale
Parameter defining the sensor at the bottom of the scale.
sensor
(in bar).
Page 15 of 30
15 - GB -
01
01
05
30
20
40
50
40
60
15
1
50
10
2
30