From a Field Supplied 4 Wire
Static Pressure Transducer
*Acceptable transducer output voltage ranges are 0-10 vdc, 0-5 vdc, 1-5 vdc, and 2-10 vdc.
Default sensor range is 0-10 vdc from factory. Use parameter 4008 to configure sensor low
voltage and parameter 4009 to configure sensor high voltage.
NOTES:
1. All conductors are no. 22 AWG minimum.
2. Install jumpers if fire/smoke detector, low limit thermostat, start/stop or high-pressure switch are not required.
3. Program static pressure control set point using parameter 4011 in volts dc.
Fig. 84 — Field Wiring for Stand-Alone Static Pressure Control with
NOTES:
1. All conductors are no. 22 AWG (American Wire Gage) minimum.
2. Install jumpers if fire/smoke detector, low limit thermostat, or high-pressure switch are not required.
3. Program desired speed set point in Hz using parameter 1202.
Fig. 85 — Field Wiring for High Inertia/Low Horsepower Applications Using VFD as a Starter
* 0-10 v dc
+
Output Signal
-
Field Supplied
Input Connections
Jumper
N.O. Start / Stop Contact
N.C. Fire / Smoke Det. Contact
N.C. Low Limit Thermostat
N.C. High Pressure Switch
4-Wire Static Pressure Transducer (Voltage Output)
1
1 1
AI-2 Cable Shield Ground
2
2 2
3 3
3
4
4 4
5
5 5
AI-2 Static Pressure Signal (+) 0 - 10 v dc
6 6
6
AI-2 Static Pressure Signal (-) 0 - 10 v dc
7 7
7
8
8 8
9 9
9
24 Vdc
10
10 10
Ground – DC Common
11 11
11
12 12
12
Digital Input Common
DI-1 Start / Stop
13 13
13
DI-2 Run Enable
14
14 14
15
15 15
16 16
DI-4 Start Enable 1
DI-5 Start Enable 2
17 17
DI-6 Internal PID Enable
18
a39-2917