DRAW-THRU — Trap against all upstream static pressure in-
cluding the drain pan section (cooling coil section).
MIXING
BOX
Return
Clean
MXB
Duct
Filter
0.4 in. wg
0.5 in. wg
0.2 in. wg
Fig. 79A — Draw-Thru Example
TYPE
Forward-Curved (FC)
• Double-width, double-inlet (DWDI) construction.
Side View
• Best at low or medium pressure (approximately 0 to 5 in. wg).
• Horsepower increases continuously with increase in air quantity (overloads) as
• Less expensive than AF fans.
• Runs at relatively low speed, typically 400 to 1200 rpm.
• Blades curve toward direction of rotation.
Airfoil (AF)
• Double-width, double-inlet (DWDI) construction.
Side View
• Best in high capacity and high-pressure applications (4 to 8 in. wg).
• Horsepower peaks at high capacities.
• Most expensive of centrifugal fans.
• Operates at high speeds, typically 1200 to 2800 rpm. About double the speed of
• Blades have aerodynamic shape similar to airplane wing and are curved away
Plenum (PAF)
End View
• Single-width, single-inlet (SWSI) construction.
• Characteristics similar to DWDI airfoil fan.
• Blades have aerodynamic shape similar to airplane wing and are curved away
H
C
E
O
A
FAN
O
T
L
Heating
Cooling
Coil
Coil
0.2
1.2 in. wg
in. wg
CHARACTERISTICS
static pressure decreases.
FC fan for similar air quantity.
from direction of rotation.
from direction of rotation. Fewer blades and wider blade spacing than AF fans.
Fig. 80 — Fan Type and Application
BLOW-THRU — Trap against the external static pressure of
the fan only.
MIXING
FAN
BOX
Trap Against Static Pressure Downstream of Fan - Static Pressure
Between Fan and Drain =
2.3 in. wg - 1.2 in. wg = 1.1 in. wg
Fig. 79B — Blow-Thru Example
Fan Motor Wiring Recommendations —
are rated for use with variable frequency drives. Full load
amp (FLA) efficiency and power factors are listed in
Table 27. Refer to Fig. 80 for fan type and application.
90
C
PLENUM
O
O
L
Static Pressure Between the Fan
Static Pressure Between the Fan
and Drain
and Drain
(Coil and Plenum Section)
(Coil and Plenum Section)
1.2 in. wg
1.2 in. wg
External Static Pressure
Downstream of Fan
2.3 in. wg
Motors
APPLICATION
For low to medium pressure
air-handling applications.
For medium to high air capacity
and pressure applications.
Best in applications with limited
space or multiple ducts.