Carrier AERO 39MN Installation, Start-Up And Service Instructions Manual page 97

Indoor and weathertight outdoor air handlers
Table of Contents

Advertisement

GROUP NUMBER
PARAMETER NUMBER
99
10
11
12
13
14
16
20
21
22
26
30
31
34
40
*Factory Programmed as follows: For 208-230v / 60 Hz = 208, 460v / 60 Hz = 460, 200-230v / 50 Hz = 200, 380 / 50 Hz = 400.
†Motor Nameplate Amps. Factory programmed per Programmed Settings in Table 28. This value should always be compared to the actual motor nameplate value
before start-up.
**Maximum Output Amps — Factory programmed per Table 28.
Table 29 — Air Handler VFD Factory-Set Parameters
DESCRIPTION
9902
Application Macro
9904
Motor Control Mode
9905
Motor Nominal Voltage
9906
Motor Nominal Current
9907
Motor Nominal Frequency
9908
Motor Nominal Speed
9909
Motor Nominal Power
1001
EXT1 Commands
1002
EXT2 Commands
1003
1104
REF1 Minimum
1105
REF1 Maximum
1201
Constant Speed Select
1202
Constant Speed Value
1301
Minimum AI-1
1302
Maximum AI-1
1303
1304
Minimum AI-2
1305
Maximum AI-2
1306
1401
Relay Output 1
1402
Relay Output 2
1403
Relay Output 3
1601
1608
Start Enable 1
1609
Start Enable 2
2002
Maximum Fan Speed
2003
Maximum Current
2007
Minimum Frequency
2008
Maximum Frequency
2101
Start Function
2102
Stop Function
2202
Accelerate Time
2203
Decelerate Time
2605
Volt/Freq Ratio
2606
Switching Frequency
2607
Switching Frequency Control
3006
Motor Thermal Time
3007
Motor Load Curve
3008
Zero Speed Load
3009
Break Point Frequency
3010
Stall Function
3011
Stall Frequency
3012
3017
3101
Number of Retries
3102
3103
3104
AR Overcurrent
3105
AR Overvoltage
3106
AR Undervoltage
3107
AR AI< Minimum
3108
AR External Fault
3415
Signal Parameter 3
3416
Signal 3 Minimum
3417
Signal 3 Maximum
3418
Output 3 DSP Form
3419
Output 3 DSP units
3420
Output 3 Minimum
3421
Output 3 Maximum
4001
4002
Integration Time
4005
Error Value Invert
4006
4007
Display Format
4010
Setpoint Select
4011
Internal Setpoint
4012
Setpoint Minimum
4013
Setpoint Maximum
4016
4027
PID 1 Parameter Set
Direction
Filter AI-1
Filter AI-2
Run Enable
Stall Time
Earth Fault
Trial Time
Delay Time
Gain
Units
ACT 1 Input
96
VALUE
Supply Fan
Scalar
*
60 Hz or 50 Hz
Nameplate rpm at Load
Nameplate Hp
DI-1 Start / Stop
(0) N/A
Forward
9.33 Hz at 60 Hz / 7.78 Hz at 50 Hz
62.7 Hz at 60 Hz / 52.2 Hz at 50 Hz
DI-3
Field Program (8 Hz – Motor Nominal Freq.)
0%
100%
1 sec
0%
100%
1 sec
Started
Run
Fault (Inverted)
DI-2
DI-4
DI-5
Per Fan
**
8 Hz
Belt Drive: 60 Hz/50 Hz
Direct Drive: Calculated Per Fan and Motor
FlyStart
Coast
60 Seconds
60 Seconds
Linear
8 KHz
ON
1050
105%
70%
35 Hz
Fault
20 Hz
20 sec
Fault
2
600 sec
5 sec
Enable
Enable
Enable
Disable
(0) Disable
SPEED
0
30000
0
rpm
0
30000
0.7
30 sec
NO
Volts
x.xxx
Internal
Field Program (0.0 v – 10.0 v)
0.0 v
10.0 v
AI-2
SET 1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mw03-110

Table of Contents