Carrier AERO 39MN Installation, Start-Up And Service Instructions Manual page 100

Indoor and weathertight outdoor air handlers
Table of Contents

Advertisement

J1 – DIP Switches for Analog Inputs
The switch is one of two types:
Original
Examples:
BOTH SWITCHES IN
VOLTAGE POSITION
BOTH SWITCHES IN
CURRENT POSITION
WIRING
1. Select a suitable location in the bottom panel of the by-
pass box to connect field-supplied power source.
2. Before drilling any hole, be sure the hole and any field-
supplied conduit fittings will not interfere with the door
or components inside the enclosure.
3. Drill the appropriate size hole and connect the field-sup-
plied conduit to the enclosure.
4. Refer to the wiring diagram supplied with the bypass
and connect the line voltage power source to the line
voltage terminals (L1, L2, L3) as shown.
5. Refer to the factory-supplied voltage warning label and
verify that the power source is correct.
6. Connect the ground wire to the grounding lug provided
on the bottom of the bypass box.
7. Refer to the VFD Steps 7 and 8 to connect VFD control
wiring.
START-UP AND TEST — Before applying power to the
VFD Bypass and VFD, verify that the motor overload inside
the bypass has been set to the full load amperage (FLA or
RLA) as specified on the motor nameplate.
IMPORTANT: Some bypass assemblies (208/230-60,
200/230-50, 380/400/415-50) contain a multi-tap control
transformer. The line voltage tap on the control trans-
former must be adjusted to the appropriate line voltage.
NOTE: Bypasses with a 115-v control transformer can be
field modified to incorporate a normally closed safety con-
tact. This safety contact (in addition to the VFD shutdown
AI1: (in Voltage Position)
AI2: (in Current Position)
Alternate
Fig. 86 — Setting AI Switch to Voltage Position
Illustration of available switch
positions; not default settings
wiring) wires into the fire alarm system to shut down the unit
even if the unit is running in the bypass position. See
Fig. 87A and 87B.
1. Set the switch on the front of the bypass to the OFF po-
sition.
2. Verify that the fan freely rotates and remove and loose
items inside the fan section.
3. Close and secure the fan access door and the bypass and
VFD covers.
4. Apply power.
5. Set the switch to the LINE position and verify that the
fan operates.
For 3-phase motors:
Place the switch back in the OFF position and carefully
open the fan access door.
Verify that the fan wheel is rotating in the proper direc-
tion. If it is not, remover power and reverse any two of
the line voltage connections in the bypass box (L1, L2,
L3). DO NOT swap the motor leads; this will cause the
fan to rotate in the reverse direction when operating
from the VFD.
6. Make sure the bypass cover is closed then apply power.
7. Set the switch to the DRIVE position and verify that the
VFD operates.
8. Press the Hand button and verify that the fan operates.
9. Press the Auto button and verify that the drive operates
from the EMS interface. Verify that all VFD interface
functions between the VFD and the EMS system are
working.
99