Outdoor Fan Motor - Carrier 40MBAB Series Service Manual

Air handler unit ductless system
Hide thumbs Also See for 40MBAB Series:
Table of Contents

Advertisement

40MBAB: Service Manual
Index:
1. Indoor DC Fan Motor (control chip is on PCB)
Power on the unit and when the unit is in the STANDBY mode, measure the pin1&pin2 voltage of CN15, and pin3 of CN34 in the fan motor
connector. If the voltage value is not in the range shown in Table 12, the PCB has an issue and needs to be replaced.
2. Outdoor DC Fan Motor (control chip is in outdoor PCB)
Release the UVW connector. Measure the resistance of U-V, U-W, V-W. If the resistance is not equal to each other, the fan motor has an issue and
needs to be replaced. Otherwise the PCB has an issue and needs to be replaced.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Table 12 — CN34
NO.
COLOR
1
/
2
Black
3
Orange
4
Blue
Table 13 — CN15
NO.
COLOR
1
Yellow
2
Black
3
Yellow-Green
Fig. 17 — Outdoor DC Fan Motor
SIGNAL
VOLTAGE
/
GND
PWM
FG
SIGNAL
VOLTAGE
208/230VAC
208/230VAC
GND
21
5-12VDC
0-12DVC