Viessmann Vitodens 100 Series Installation And Service Instructions Manual page 69

6.5 to 35.0 kw wall mounted gas condensing boiler. natural gas version
Table of Contents

Advertisement

Fault display
(cont.)
Displayed
System character-
fault code
istics
F78
Function at the ex-
ternal extension faul-
ty
F80
Function at the ex-
ternal extension faul-
ty
F88
Function at the ex-
ternal extension faul-
ty
F90
Function at the ex-
ternal extension faul-
ty
F98
Function at the ex-
ternal extension faul-
ty
Fb0
Burner locked out
Cause
Lead break, col-
lector temperature
sensor S1 at the
external extension
Short circuit, lower
cylinder tempera-
ture sensor S2 at
the external exten-
sion
Lead break, lower
cylinder tempera-
ture sensor S2 at
the external exten-
sion
Short circuit, upper
cylinder tempera-
ture sensor S3 at
the external exten-
sion
Lead break, upper
cylinder tempera-
ture sensor S3 at
the external exten-
sion
Short circuit, flue
gas temperature
sensor
Troubleshooting
Measures
Checking the sensor
Installation and
service instruc-
tions for external
extension
Checking the sensor
Installation and
service instruc-
tions for external
extension
Checking the sensor
Installation and
service instruc-
tions for external
extension
Checking the sensor
Installation and
service instruc-
tions for external
extension
Checking the sensor
Installation and
service instruc-
tions for external
extension
Check flue gas tempera-
ture sensor (see
page 77).
69