Viessmann Vitodens 100 Series Installation And Service Instructions Manual page 67

6.5 to 35.0 kw wall mounted gas condensing boiler. natural gas version
Table of Contents

Advertisement

Fault display
(cont.)
Displayed
System character-
fault code
istics
F03
Burner in a fault
state
F04
Burner in a fault
state
F05
Burner in a fault
state
F07
Burner locked out
F08
Burner in a fault
state
F10
Continuous opera-
tion
Cause
Flame signal is al-
ready present at
burner start
Flame signal is not
present
Fan does not start
when burner starts
Lead break, water
pressure sensor
Gas solenoid
valve relay
blocked
Short circuit, out-
side temperature
sensor or room
temperature sen-
sor
Troubleshooting
Measures
Check ionisation elec-
trode and connecting ca-
ble.
Turn the ON/OFF switch
off and back on again, or
perform a reset – see
F02.
Check the ignition/ionisa-
tion electrodes and con-
necting cable, check the
gas pressure, check the
gas train, check the igni-
tion and ignition module.
Turn the ON/OFF switch
off and back on again, or
perform a reset – see
F02.
Check the fan motor and
connecting cables
Turn the ON/OFF switch
off and back on again, or
perform a reset – see
F02.
Check the water pres-
sure sensor
Turn the ON/OFF switch
off and back on again
(or reset, see F02).
Check relay, gas sole-
noid valve and connect-
ing lead
Turn the ON/OFF switch
off and back on again, or
perform a reset – see
F02.
Check the sensor (see
page 72).
67