Commissioning, inspection, maintenance
Further details regarding the individual steps
3. Disconnect the cables from fan
motor A, gas train B and electro-
des C.
4. Disconnect Venturi extension D
from the fan.
5. Undo gas supply pipe fitting E.

Checking the burner gasket and burner gauze assembly

Check burner gasket A for damage
and replace if necessary.
B
48
6. Undo 4 screws F and remove the
burner.
!
Replace the burner gauze assembly if it
is damaged.
E
2x
(cont.)
Please note
To prevent damage,
never rest the burner on the
burner gauze assembly.
D
C
A