Viessmann Vitodens 100 Series Installation And Service Instructions Manual page 21

6.5 to 35.0 kw wall mounted gas condensing boiler. natural gas version
Table of Contents

Advertisement

Mounting the boiler and making connections
Connecting the safety valve and condensate drain
A
Filling the trap with water
Installation sequence
(cont.)
Connect condensate pipe A to the
public sewage system with a constant
fall and a pipe vent.
Treating and draining off condensate:
■ A neutralising system is available as
an accessory on request.
■ Do not drain condensate that has not
been neutralised through pipes made
from steel or other metallic materials.
■ Do not close off the condensate pipe
or change its position.
■ Observe local rules and waste water
regulations for draining off conden-
sate.
Note
Fill the trap with water before commis-
sioning.
Pour at least 0.3 l of water into the flue
gas connection.
!
Please note
During commissioning, flue gas
may escape from the conden-
sate drain.
Always fill the trap with water
before commissioning.
21