32

Power supply

32.1
Power supply for the control unit
– battery charging unit contained in E3X10.
– is one of the max. 16 I-Bus modules
CC11
Battery charging unit
E3X10.
* TF = Temperature sensor for battery temperature monitoring
Fire & Security Products
Siemens Building Technologies Group
Concept
The power supply for the CS1140 fire detection system consists of:
Converter
Battery charging unit
Batteries (lead)
Special functions
automatic battery load test
Battery charging characteristic can be programmed according to make
Application
Determine required battery capacity individually Õ
Protection of mains lead only in special cases Õ
max. 42Ah per battery charging unit ( > 42Ah = auxiliary power supply)
Parallel operation of several battery charging units possible
Battery lead without EMI-protection (battery cannot be mounted separately)
Õ Battery charging unit is integrated in the E3X10. master module
CC11
Õ Battery charging module E3C011 required
CI11
Mains
B2F020
Batteries
TF*
AX12..
40...220VA
29,6V
I-Bus
(mains voltage Õ system voltage 29,6V)
(integrated in E3X10. or by means of E3C011)
(capacity as required)
see page 95
CI11
AlgoPilot
B3Q...
see page 91
Mains
B2F020
E3C011
40...220VA
29,6V
I-Bus
Batteries
AX12..
TF*
87
e4595e 32
05.2003