Main Cpu Limits (Ci/Cc) - Siemens Cerberus CS1140 Planning

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

7.1

Main CPU limits (CI/CC)

7.1.1
Maximum number of devices (RAM) per station
select station
with higher
RAM capacity or
an additional
station
number
of devices
no
< X ?
yes
Fire & Security Products
Siemens Building Technologies Group
The limits within the station types are given by
hard- and software.
Verify all given limits for each required station
by going through this flow chart
For the stationtypes CI1142, CC1142, CC1143, this limit is depending on the setup of the
logical structure.
The following graph allows to find this limit depending on the estimated average number
of ELEMENTS per ZONE.
Max. number of devices
3500
3400
3300
3200
3100
3000
2900
2800
2700
2600
2500
2400
2300
2200
2100
2000
1900
1800
1700
1600
CC1142
1500
1400
1300
1200
1100
1000
900
800
700
600
CI1142 (B3Q660/680/685)
500
400
300
200
100
0
1
2
Important:
i
Above values correspond to the ones already given for EP5.
However, for the following configurations, these limits must be reduced further.
Number of ZONES per SECTION (average) < 3
Use of ELEMENT texts
CC1143
Example:
average of 3 ELEMENTS per ZONE
Result: max. 3000 devices
CI1142 (B3Q460/480/670)
200
600
300
3
4
5
ELEMENTS per ZONE (average)
! Do not go to the limits !
plan reserves for:
– Project changes
– Site expansions
– Upgrade to future versions
Example:
average of 5 ELEMENTS per ZONE
configured in control unit: 300 devices
free memory: 600 devices (-200 spare)
(use of this value see chapter 7.2.1)
6
7
8
CI1142:
CC1142:
CC1143:
CI1142:
CC1142:
CC1143:
9
10
–15%
–20%
–10%
–10%
17
e4595e−7
05.2003