Cc1142/43 In Cabinet H67 - Siemens Cerberus CS1140 Planning

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

14
CC11
434
H67G601
1130
300
Control terminal
installed separately
Ò Ò Ò Ò Ò Ò Ò Ò Ò
Ò Ò Ò Ò Ò Ò Ò Ò Ò Ò Ò Ò
Comments:
– E3I020 if used mount
at position 32!
– B2F020 fits any mo-
dule space
If Z3I041 or B3P020
is used, on Pos. 36
E3M060/071/171/120
and E3C011 not pos-
sible!
Mounting of E3X10.:
Terminal block for
E3X10. containing in
cable set Z3I350
+ 2 x Z1I030
EMC Precaution:
Relative to each E3X10.
and E3C011 module po-
sition, two positions to
the right and two posi-
tions to the left must not
be fit with either E3I040
or E3G080 modules
36
Fire & Security Products
Siemens Building Technologies Group
in cabinet H67...
42/43
H67G601/611:
Set with
– door
H67G611
– frame
– module chassis
– mains terminals
– battery supporting plate
– relay rail
B3Q...
H23B010
H23B040
B3Q321
H Extendable system control unit
H With separate main CPU (E3X10.)
H Separate connection block
H Space for accessories
H Batteries as required either 2x 12V/27Ah or 2x 12V/42Ah
H Control terminals usually connected separately
H (installation possible in door)
H Door right hinged with lock (type DOM)
cable duct
01
02
03
04
Ò Ò Ò
11
12
13
Z3I570
21
Ò Ò Ò Ò Ò Ò Ò Ò Ò
cable duct
Ò Ò Ò Ò Ò Ò Ò Ò Ò
31
32
33
34
35
36
37
42
43
44
45
47
52
53
54
55
56
57
61
62
65
(Battery 12V)
(Battery 12V)
AX1201
AX1201
or
AX1209
AX1209
Z1I070 oder Z1I040 oder
Einschub
B3R051
Ò Ò
04
Mains
terminals
1)
Z3I450
14
14
Ò Ò Ò
38
37
Mains
Ò Ò Ò
terminals
1)
Z3I450
48
Special feature:
H67E100 has 3 different hole patterns for mounting. As a
result, the relationship between connection block / modules /
58
batteries can also be arranged differently
Õ see page 38
Important:
or
Comply with max. permissible number of
'nodes' + I-Bus modules!
Õ for details see chapter 7
Z1I050
aufsteckbar im
Anschlussfeld
B2F020
E3X10.
Z3I350
AX12..
Supplied with cabinet sets H67G601/611
absolutely esssential
recommended space allocation
– one or two connection cables Z1I070, Z1I040 or
Z1I050 are required for each module:
Line modules
see page 59
LON module
see page 72
Control modules
see page 66
Extinguishing modules see page 79
Interfaces
see page 75, 82, 86
One Z3I330 terminal block has space for:
either
– 2x Z1I050 or
– 8x Z1I070 or
– 4x Z1I040 or
– 1x Z1I050 and 2x Z1I040
1) Protection elements Õ see page 95
Details on cabinet H67...
Õ see page 55
H67E101
AX12..
e4595e 14
05.2003

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents