Supported Sinteso™ Elements; Figure 17: Fdnet Overview - Siemens SIGMASYS C Manual

Multifunctional danger control and indicating panels
Table of Contents

Advertisement

12 Monitored lines

Figure 17: FDnet overview

Loop planning
Note the following if there are several FDC modules:
For improved safety, FDnet loops that are as independent of one another as possible should
be applied to different modules.
The loops should also be distributed over different modules when using alarm sounders
and signal bases as evacuation alarms on the loops, in order to improve the safety of the
acoustic alarm.
Examples:
In buildings with several storeys, apply the loop of one storey to one FDC module and
the LOOP of the next storey to another FDC module.
In the case of large buildings with multiple loops, distribute these alternately over two
different FDC modules.
12.6.2
Supported Sinteso™ elements
Detector
Optical detector
Heat detector
86 / 128
Detector
Detector
S-LINE
C-LINE
FDO221
FDO241
FDT221
FDT241
Comment / Applications
Used as smoke detector
2 selectable parameter sets
Used as smoke detector
3 selectable parameter sets
Used as heat detector
2 selectable parameter sets
Used as heat detector
4 selectable parameter sets
BMT Project Planning Guidelines
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)