Sigmaspace Gateway; Zone Operating Panel Spf 3300 - Siemens SIGMASYS C Manual

Multifunctional danger control and indicating panels
Table of Contents

Advertisement

8 Transponders and loop elements
The following data applies:
Fault, short circuit, wire breakage:
Alarm:
Idle:
The signal must last for at least 1.4
signals".
Installation
The contact coupler SPF 5300 can be installed on a 15 mm top-hat rail in the space provided
for option equipment in the control and indicating panel or in a distribution cabinet (AP...).
8.2.5
SIGMASPAC
The gateway radio is a loop element which can administer up to 30 radio components inside
a radio cell (spatial area). From the perspective of SIGMALOOP, the gateway is the same as
a transponder that occupies a separate address for itself and each radio component.
Concept
similar to transponder
occupies a variable number of address elements depending on the number of radio
components used: up to 31, the gateway occupies a loop address. Max. number on
loop
There are two radio gateways for connecting radio detector
cating panels.
SPU6102 gateway in the housing
SPU6100 gateway as intermediate ring for SIGMA
The radio gateways connect the radio detector DOW 1171 to SIGMALOOP.
The SIGMASPACE hybrid system docum
project planning, "Project planning a radio
8.2.6

Zone operating panel SPF 3300

The SIGMASYS zone operating panel is an operating and display element for all SIGMASYS
control and indicating panels. It requires an address as an element for the SIGMALOOP
transmission procedure.
57 texts with 16 characters each ca
The first event is displayed. The others can be viewed by scrolling.
Events can only be sent by the MPC to which the zone operating panel is connected. An
event can only be assigne
Technical signals are displayed as alarms. Detector numbers are not displayed.
The detector type is displayed in line 1 depending on the priority:
Alarm
Fault
Disablement
48 / 128
E gateway
see chapter Load factors" on page 84.
d to one zone operating panel.
<300 Ohm
; >4.3 kΩ
Alarm resist
ance 560 Ω – 680 Ω
Termination with 3.3 kΩ (normal open NO)
to 4.2 s
econds for it to be dis
SYS detector base SPF 3600.
entation in the standard collection are to be used for
cell", A24205-A337-A910.
n be assigned and are freely programmable.
played. See "Cycle times for
s to SIGMASYS control and indi-
BMT Project Planning Guidelines
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)