8 Transponders and loop elements
•
Control of local plant facilities with feedback
•
General earth fault monitoring (can be disable
•
In-/outputs are electrically isolated from the FDne
Collective monitored line:
Compatible with following Sie
MS 6 (with LED), MS 7, MS 9, SIGMACON, DS1100,
FDOOT 241-9, FDF 221-9, FDF 241-9, FDL 241-9 and similar, as well as manual call points
with 680 ohm alarm resistance.
•
Maximum line data:
•
Monitoring current
•
Maximum current on all d
•
Terminal on automatic detectors:
C
ompatible with threshold detectors with alarm resistance which meet the following
conditions (e.g. Synova 300):
•
Max. rest current on all d
•
Pulse current on alarm event
•
Reset voltage
•
Reset time
•
Settling time after
•
Alarm status:
•
Voltage in event of a
•
Alarm holding current:
•
Monitoring current
•
Terminal
•
Maximum line data
C
ontact inputs:
•
Rest resis
•
Signal resistance:
•
Inverse monitoring:
•
Maximum line data
46 / 128
mens Cerberus series:
etectors
etectors in a line
reset
larm:
tance
d)
t
DF 119x, S 2406,A 2400, DLO 1191,
150Ω
1µF
4.5 m
A
3.2 mA
Transzo
rb diode
20 V ±5%
1.5 kW pulse pow
er
< 3.2 mA
approx. 80
mA
< 1 V
< 3 s
< 10 s
410 Ω ...
600 Ω
4 V ... 14 V
< 10 mA
17 mA
Transzo
rb diode
20 V ±5%
er
1.5 kW pulse pow
150 Ω
1 µF
3k3
560 Ω
configu
rable
150 Ω
1 µF
BMT Project Planning Guidelines
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)