12 Monitored lines

Figure 14: SIGMAPLUS SDF2200 Optical smoke detector

Operating conditions
P1
Difficult detectionconditions
High risk for persons, buildings and merchandise.
Hazardous storage goods
High level of smoke thinning, for example,as a result of
ventilation, room height, etc.False alarm contributing fac-
tors only permittedin rooms with very high ceilings.
P2
Highest value concentration
High risk for persons and material assets
Very low false alarm contributing factors
No smoking areas
P3
Rooms with high ceilings
Risk for persons and material assets
Room height over 5 m
Low and short-term false alarm contributing factors
P4
High value concentration
Risk for material assets and persons Room height aver-
age or over 5 m
Low and medium short-term deception values
P5
Medium value concentration/Standard
Risk for material assets and persons
Room height up to 5 m
Low to medium and short-term false alarm contributing
factors
P6
Medium value concentration and interference
Risk for material assets and persons
Medium and long-term false alarm contributing factors
for example, tobacco smoke, water vapor, short-term
P7
Low value concentration and high interference
Risk for material assets
High and long-term false alarm contributing factors for,
for example:
smoke, dust *)/dirt accumulation, vapor, dewfall, etc,.
SDF3100 should be used to monitor high risk areas

Table 28: Operating conditions and sample applications

*) Use filtered priming systems for light dust (e.g. from cement, feed industry)!
82 / 128
Sample applications
Not compliant with EN 54-7
rooms with very high ceilings open
oper warehoses chem.. industry
VdS-tested in accordance with EN 54-7
EDP, telephone switches
Museums
Hospitals, health care facilities
VdS-tested in accordance with EN 54-7
Clean rooms (fabrication facilities)
Shopping centers
VdS-tested in accordance with EN 54-7
Fabrication facilities
Industry
VdS-tested in accordance with EN 54-7
Offices
Corridors
VdS-tested in accordance to EN 54-7
Offices where smoking is permitted,
Shops,
Hotel rooms,
Restaurants, assembly buildings
Not compliant with EN 54-7
Vulcanization
Heavy industry
Garage for heavy goods vehicles
Priming systems
ventilation systems
BMT Project Planning Guidelines