Valor 474 Valentia Installation And Owner's Manual page 12

Balanced flue room sealed radiant / convector gas fire
Table of Contents

Advertisement

Key
A*
Directly below an opening, air brick, opening window etc.
B*
Above an opening, air brick, opening window etc.
C*
Horizontally to an opening, air brick, opening window etc.
D
Below gutters, soil pipes or drain pipes.
E
Below eaves.
F
Below balconies or car port roof.
G
From a vertical drain pipe or soil pipe.
H** From an internal or external corner.
I
Above ground, roof or balcony level.
J
From a surface facing the terminal.
K
From a terminal facing the terminal.
L
From an opening in a car port (e.g. door, window) into dwelling.
M
Vertically from a terminal on the same wall.
N
Horizontally from a terminal on the same wall.
*In addition, the terminal should not be nearer than 300mm to an opening in the
building fabric formed for the purpose of accommodating a built-in element such as
a window frame or door frame (See figure 4).
** The reference to external corners does not apply to building protrusions not
exceeding 450mm, such as disused chimneys on external walls.
FIG. 3
©
GDC Group Ltd. 2014
INSTALLER GUIDE
Terminal position
Page 12
Minimum
distance.
300mm
300mm
300mm
300mm
300mm
600mm
300mm
600mm
300mm
600mm
600mm
1200mm
1500mm
300mm