Troubleshooting and fault elimination

8.3 Fault indications

Display
Fault
---
No fault
EEr
External fault (TRIP-Set)
H05
Internal fault
LU
Undervoltage
OC1
Short circuit
OC2
OC2
Earth fault
Earth fault
OC3
Overload inverter during
acceleration or short
circuit
circuit
OC4
Overload controller during
deceleration
OC5
I x t overload
OC6
Overload motor
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Cause
Remedy
-
-
A digital input assigned to the
Check external encoder
TRIP-Set function has been
activated
Contact Lenze
DC-bus voltage too low
D Check mains voltage
D Check supply module
Short circuit
Find out cause of short circuit; check
cable
Excessive capacitive charging
Use motor cable which is shorter or of
current of the motor cable
lower capacitance
Grounded motor phase
Check motor; check cable
Excessive capacitive charging
Use motor cable which is shorter or of
current of the motor cable
lower capacitance
Acceleration time too short
D Increase acceleration time
(C012)
D Check drive selection
Defective motor cable
Check wiring
Interturn fault in the motor
Check motor
Deceleration time too short
D Increase deceleration time
(C013)
D Check the selection of the brake
resistor or connect the brake
chopper
Check drive dimensioning
Frequent and too long
acceleration processes with
overcurrent
Permanent overload with
I
> 1.05 x I
motor
Nx
Motor is thermally overloaded, for
instance, because of
D impermissible continuous
D Check drive selection
current
D frequent or too long
D Check the setting under C120
acceleration processes
UOMu_^MVMO
8-3