Reader Input; Door Terminal Associations - Honeywell SEC-H-600 Installation Instructions Manual

Security controller
Table of Contents

Advertisement

Reader Input

The SEC-H-600 controller has two door reader inputs, each supporting a Wiegand-type 12Vdc reader. Each reader input has a 7-
position connector, on the circuit board labeled as Card Reader 2 and 1 (see Fig. 4 on page 12). Typical wiring is shown below in
Fig. 8. Pinouts for each card reader connector are shown in Table 5.
NOTE: A door wired to a reader input has other I/O points, see "Door Terminal Associations," page 15.
Terminal
Terminal Name
DC+
+12Vdc to Reader
GND
Ground
D0
Reader Data 0
D1
Reader Data 1
AX1
Auxiliary 1
AX2
Auxiliary 2
AX3
Auxiliary 3
Reader Wiring Notes
• Mount the reader, referring to the specific manual for that reader for instructions.
• Use shielded, twisted-pair, cabling (Belden #8725 or #8723 or equivalent, as needed) to connect the reader to the Security
Controller. Maximum cable distance is 500 feet (152m).
• Run this cabling from the reader to the Security Controller, bringing it through an appropriate knockout in the enclosure used.
Allow sufficient slack cable for servicing.
• Tie all shield wires together, and connect to the designated grounding point at the enclosure. SeeFig. 5 on page 13.
• Place the appropriate wires in the appropriate screw terminals of the 7-position reader connector. Refer to the pinouts in
Table 5 above for reader input designations. Figure 8 above lists typical wiring colors.
Fig. 8. Reader wiring to Security Controller.
Shields
NOTE: Maximum current rating for
both reader inputs (combined) is:
• Peak current maximum:
• Average current maximum:0.30A
Table 5. Pinouts for Card Reader Inputs
Terminal Notes
Always wire these four terminals to the
corresponding reader terminals.
Optional, wire to reader's Green LED
control
Optional, wire to reader's Red LED control At reader, typically Brown wire.
Optional, wire to reader's Beeper control
SEC-H-600 SECURITY CONTROLLER
Reader
0.40A
Typical cabling colors
Typically Red wire.
Typically Black wire.
Typically Green wire.
Typically White wire.
At reader, typically Orange wire.
At reader, typically Blue or Yellow
wire.
17
95-7759—07

Hide quick links:

Advertisement

Table of Contents
loading