Fig. 14. RS-485 cabling between Security Controller and expansion modules not mounted in-line.
15Vdc from
WEBs-AX
Security
Enclosure
SEC-
H-R2R
SEC-
SEC-H-RIO
H-R2R

POWER WIRING

For UL 294 installations, the SEC-H-600 must be powered by the approved NPB-PWR-UN-H, regulated 15Vdc power source.
For related information, see "Estimating Power and Battery Requirements," page 6.
CAUTION
Door strike power, as well as power for other loads switched by the SEC-H-600 and/or its expansion modules,
should always be provided from a different source.
Do not apply power to the SEC-H-600 until all other mounting and wiring is completed. See "Power Up and Initial
Checkout," page 26.

Enclosure Power Supply

The integral power supply (NPB-PWR-UN-H) in a WEBs-AX Security Enclosure (SEC-ENC-H-1 or SEC-ENC-H-2) provides 30W
of regulated 15Vdc power to an Security Controller and its connected expansion modules, and is required for UL 294. Input
voltage is 120Vac to 240Vac, single phase. You mount the Security Controller on the top DIN rail in the enclosure, where it
connects into this power supply (see Fig. 3 on page 11). If an SEC-ENC-H-2 enclosure, a provided 6-wire harness lets you
connect expansion modules on the second (lower) DIN rail.
Security
Controller
SEC-H-RIO
SEC-
H-R2R
SEC-H-600 SECURITY CONTROLLER
NOTE: Not shown is 15Vdc power
and battery backup connections,
which use the other (top) 3 positions
on the 6-position connector plugs.
Shielded, twisted
pair cabling
Connect
RS-485
shield wire to
ground at
one end only.
25
+
s
Terminals on the
6-position
connector plugs
used for RS-485
between
assemblies.
95-7759—07