USER INTERFACE

FC Basic has three main controls plus one optional control:
Dial knob
2 sliders
1
economy slider (optional)
4.1

Set point dial knob

Potentiometer for setting operating set point.
Operating set point is altered on the basis of the angle set, from 5 to 35 Celsius.
Excursion from the potentiometer centre point is an angle of +/- 105°.
IMG INFO
4.1.1

Click-stop dial knob turning

A sensible click-stop mechanism of approx. 0,5° per position gives the user a more accurate feeling during adjustment.
4.1.2

Range limitation

The set point may be limited on all models by positioning 2 pegs, (plugs) which are mounted under the dial knob, at a
specific minimum and maximum value. When the 2 pegs are mounted one next to the other, it is even possible to lock the
set point at a specific value.
Please proceed as follows:
1.
Separate the connector base plate from the main interface, by using a tiny screwdriver. Insert the screwdriver into the
appropriate holes (at the side of the housing), wrest gently till both parts are separated.
2.
Before proceeding with the next step, first turn the dial knob to the mid-position when you want to limit (min. /
max.) the range. When you want to lock the set point, first turn the dial knob in the desired lock position value.Turn
the back of the main interface towards you and you will see a hole somewhere in the middle of the electronic board.
Push gently on the pin connected with the dial knob till it becomes released from the main interface
3.
You can now remove the dial knob on the front of the main interface and the
After you entered the pegs in the desired limitation position, mount the dial knob back onto the interface in the
correct way.
Factory setting of the limitation pegs at 5°C
and 35°C:
1
1
Economy slider (optional)
Range limitation
Operating mode slider
Fan control slider
1
1
2
2
3
3
Example of a range limitation between 15°C
and 25°C:
LED's
range limitation
becomes accessible.
FC BASIC User Manual
11/24