Download Print this page

Technical Data - Gira 0384 00 Operating Instructions

Leak sensor

Advertisement

GIRA
Leak Sensor
Info
Operating Instructions
Connecting zero-voltage contact
1. Deenergise device
2. Pull off cover
3. Replace blind plug (5) with screwed cable gland (6)
4. Insert cable through gland
5. Connect cable for zero-voltage contact to terminal block (7)
Contact via terminal 2 and 3:
Contact via terminal 1 and 3:
6. Tighten gland
7. Screw on cover
Alarm test
Immerse sensor in water.
LED alarm (3) red and acoustic signal.
Dry sensor following contact with liquid.

Technical data

Power supply:
Ambient temperature:
Display
Operation:
Alarm:
Zero-voltage contact:
Construction:
Protection class:
Dimensions:
Connection cable length:
Sensor cable length:
Directives/Standard
EC EMC Directive 89/336/EEC
Leak Sensor
Closed in case of alarm
Open in case of alarm
230 V AC / 50 Hz / 1.2 VA
0 - 60 °C
LED green
LED red and acoustic signal
AC 230 V/1,800 VA
DC 100 V/300 W
Polyester housing IP 65
II (protective insulation)
110 x 75 x 55 mm
1.5 m
2 m
08/96