5742640-TIM-A-0419
Table 8: Electrical data: single-phase gas heat, belt drive
ZDT03 through T05 - Without Powered Convenience Outlet (Belt Drive Single Phase Gas Heat)
Compressors
Size
(each)
Volt
(Tons)
RLA LRA
208-1-60 15.4
83.9
T03
(3)
230-1-60 15.4
83.9
208-1-60 19.6
130
T04
(4)
230-1-60 19.6
130
208-1-60 24.4 144.2
T05
(5)
230-1-60 24.4 144.2
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZDT03 through T05 - With Powered Convenience Outlet (Belt Drive Single Phase Gas Heat)
Compressors
Size
(each)
Volt
(Tons)
RLA LRA
208-1-60 15.4
83.9
T03
(3)
230-1-60 15.4
83.9
208-1-60 19.6
130
T04
(4)
230-1-60 19.6
130
208-1-60 24.4 144.2
T05
(5)
230-1-60 24.4 144.2
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
28
OD Fan
Supply
Pwr
Motors
Blower
Conv
(each)
Motor
Outlet
MCC
FLA
FLA
FLA
24
2.3
17.4
24
2.3
17.4
31
2.3
17.4
31
2.3
17.4
38
4.4
17.4
38
4.4
17.4
OD Fan
Supply
Pwr
Motors
Blower
Conv
(each)
Motor
Outlet
MCC
FLA
FLA
FLA
24
2.3
17.4
20
24
2.3
17.4
20
31
2.3
17.4
20
31
2.3
17.4
20
38
4.4
17.4
20
38
4.4
17.4
20
Electric Heat Option
Model
kW
Stages
Amps
None
-
-
None
-
-
None
-
-
None
-
-
None
-
-
None
-
-
Electric Heat Option
Model
kW
Stages
Amps
None
-
-
-
None
-
-
-
None
-
-
-
None
-
-
-
None
-
-
-
None
-
-
-
Max
2
Fuse
/
1
MCA
3
Breaker
(Amps)
Size
(Amps)
-
39.5
50
-
39.5
50
-
44.2
60
-
44.2
60
-
52.3
70
-
52.3
70
2
Max Fuse
/
1
3
MCA
Breaker
(Amps)
Size
(Amps)
49.5
60
49.5
60
54.2
70
54.2
70
62.3
80
62.3
80