5742640-TIM-A-0419
ZDT03 through T05 - With Powered Convenience Outlet (Direct Drive)
Compressors
Size
(each)
Volt
(Tons)
RLA LRA
208-1-60 15.4
83.9
230-1-60 15.4
83.9
T03
(3.0)
208-3-60 10.4
73
230-3-60 10.4
73
208-1-60 19.6
130
230-1-60 19.6
130
T04
(4.0)
208-3-60 13.7
83.1
230-3-60 13.7
83.1
26
OD Fan
Supply
Pwr
Motors
Blower
Conv
(each)
Motor
Outlet
MCC
FLA
FLA
FLA
24
2.3
6
10
24
2.3
6
10
16.3
2.3
6
10
16.3
2.3
6
10
30.5
2.3
7.6
10
30.5
2.3
7.6
10
21.4
2.3
7.6
10
21.4
2.3
7.6
10
Electric Heat Option
Model
kW
Stages
Amps
NONE
-
-
-
E05
4
1
19.2
E07
5.6
1
26.9
E10
8
1
38.5
E15
11.9
2
57.2
E20
15.9
2
76.4
NONE
-
-
-
E05
5.3
1
22.1
E07
7.5
1
31.2
E10
10.6
1
44.2
E15
15.9
2
66.2
E20
21.2
2
88.3
NONE
-
-
-
E05
4
1
11.1
E07
5.6
1
15.5
E10
8
1
22.2
E15
11.9
2
33
E20
15.9
2
44.1
NONE
-
-
-
E05
5.3
1
12.7
E07
7.5
1
18
E10
10.6
1
25.5
E15
15.9
2
38.2
E20
21.2
2
51
NONE
-
-
-
E05
4
1
19.2
E07
5.6
1
26.9
E10
8
1
38.5
E15
11.9
2
57.2
E20
15.9
2
76.4
NONE
-
-
-
E05
5.3
1
22.1
E07
7.5
1
31.2
E10
10.6
1
44.2
E15
15.9
2
66.2
E20
21.2
2
88.3
NONE
-
-
-
E05
4
1
11.1
E07
5.6
1
15.5
E10
8
1
22.2
E15
11.9
2
33
E20
15.9
2
44.1
NONE
-
-
-
E05
5.3
1
12.7
E07
7.5
1
18
E10
10.6
1
25.5
E15
15.9
2
38.2
E20
21.2
2
51
2
Max Fuse
/
1
3
MCA
Breaker
(Amps)
Size
(Amps)
37.5
50
44
50
53.7
60
68.1
70
91.5
100
115.6
125
37.5
50
47.6
50
59.1
60
75.2
80
102.8
110
130.4
150
31.3
40
33.9
40
39.4
40
47.8
50
61.3
70
75.2
80
31.3
40
35.9
40
42.6
45
51.9
60
67.8
70
83.7
90
44.4
60
46
60
55.7
60
70.1
80
93.5
100
117.6
125
44.4
60
49.6
60
61.1
70
77.2
80
104.8
110
132.4
150
37
45
37
45
41.4
50
49.8
50
63.3
70
77.2
80
37
45
37.9
50
44.6
50
53.9
60
69.8
70
85.7
90
Johnson Controls Ducted Systems
Need help?
Do you have a question about the TempMaster ZD Series and is the answer not in the manual?